Mini8 ® Controller

by user

on
Category: Documents
19

views

Report

Comments

Transcript

Mini8 ® Controller
®
Mini8
Controller
Ranged to suit simple multi-loop and data acquisition applications
The Mini8® Controller offers high performance control usually only found in
Eurotherm® panel mount PID controllers. It is also a very competitive and
compact data acquisition device. Its modular design enables its I/O and
feature set to be selected to cater for a wide range of applications from
simple to complex.
• 16 control loops
The Mini8 controller is an ideal partner to a programmable logic controller.
Able to multi-drop on either Serial, Fieldbus or Ethernet communications. It
offers a cost effective alternative to performing analogue measurement or
loop control in a PLC. Implementing these functions in the Mini8 controller
reduces the hardware cost of the PLC, relieving it of the burden of
performing analogue functions, often allowing a lower specification processor
to be used.
• Remote HMI
The feature set is comparable with the Eurotherm 3000 series panel
controllers including its high performance PID control and SP programming
functions together with a range of features such as Maths, Logic and Timing
blocks.
• OEM Security
When used in a data acquisition installation the controller’s high density
analogue I/O can be combined with Eurotherm’s 6000 series paperless
graphic recorder.
Control Optimise Simplify
• 32 analogue inputs
• Modular & compact
• SP programming
• Maths and logic
• Modbus RTU
• DeviceNet® network
• Profibus DP network
• Modbus TCP
• EtherNet/IP
• EtherCAT
Setpoint programming
The Mini8 controller can run up to 8 programmer function
blocks, to follow a user defined series of ramp and dwell
segments. Each programmer is capable of running a program
of up to 16 segments with 8 event outputs. The event outputs
can be used internally within the configuration soft wiring or to
external digital or relay outputs. (Note that this depends on the
type and number of the hardware outputs fitted).
Recipes
Using a PC tool, recipes can be created that can be used to
change the operating parameters of the Mini8 controller simply
by selecting a new recipe via the HMI. This is very useful where
multiple products are processed using the same controller but
require different parameters to be set.
Heater failure detection
The Mini8 controller with a CT3 input card fitted, has the
capability of detecting failures in heater loads connected to its
time proportioned outputs. By measuring the current flowing
through the heaters via 3 current transformer inputs the Mini8
controller can, for up to 8 loops, detect Partial Load failure, Over
Current, as well as SSR short or open circuit. Individual load
current parameters indicate the measurement for each heater.
The current monitor block utilises a cyclic algorithm to measure
the current flowing through one heater per measurement interval.
Toolkit blocks
A range of toolkit functions, including Maths, Logic and Timing
blocks can be used to create custom solutions and small
machine controllers.
Eurotherm iTools Graphical Wiring Editor
The GWE is an extremely easy way to create applications. It
allows users to select the function blocks they wish to use in
their application then connect them together using ‘Soft
Wiring’. The GWE gives the user a pictorial view of exactly what
he has configured and can also be used to monitor runtime
conditions.
Specification
General
Environmental performance
Power supply voltage:
Supply ripple:
Power consumption:
Operation temperature:
Storage temperature:
Operating humidity:
Applied voltage any terminal:
17.8V dc min to 28.8V dc max.
2Vp-p max.
15W max.
0 to 55°C
–10 to 70°C
5% to 95% RH non-condensing
42V pk max.
The Mini8 controller must be mounted in a protective enclosure.
Electromagnetic compatibility (EMC)
EN61326 for Industrial Environments
EMC:
This controller conforms with the essential protection requirements of the
EMC Directive 2004/108/EC, by the application of EMC standard EN61326.
This instrument satisfies the general requirements of the industrial environment
defined in EN 61326.
Electrical safety
Meets EN61010, installation category II,
pollution degree 2
Safety:
INSTALLATION CATEGORY II
This controller complies with the European Low Voltage Directive 73/23/EEC, by
the application of the safety standard EN 61010.
POLLUTION DEGREE 2
Normally, only non-conductive pollution occurs. Occasionally, however, a
temporary conductivity caused by condensation shall be expected.
Physical
W124 x H108 x D115mm
1Kg typical
DIN rail to EN50022 35 x 7.5 or
35 x 15 horizontally
Dimensions:
Weight:
Mounting:
Approvals
CE, cUL listed (file E57766)
Communications
Network communications support
Modbus RTU:
DeviceNet:
Profibus DP:
Ethernet:
EtherNet/IP:
EtherCAT
Baud rates:
Baud rates:
Baud rates:
Baud rates:
Baud rates:
Baud rates:
RS485, 2 x RJ45, user select switch for 3-wire
or 5-wire
4800, 9600, 19200
CAN, 5-pin standard "open connector" with
screw terminals
125k, 250k, 500k
RS485 via standard 9 pin D connector or
2 RJ45 connectors
Up to 12M set by the Master
Standard Ethernet RJ45 connector
10baseT
Standard Ethernet RJ45 connector
10baseT
100baseT
Standard Ethernet RJ45 connector
10baseT
100baseT
Modbus /DeviceNet /Profibus /Ethernet/EtherNet/IP /EtherCAT are mutually
exclusive options; refer to the Mini8 controller Order Code.
Configuration communications support
Modbus RTU:
RS485, 2 x RJ45, user select switch for 3-wire
or 5-wire
Fixed I/O resources
The PSU card supports 2 independent and isolated relay contacts.
On/Off (C/O contacts, "On" closing the N/O pair)
Relay output types:
<1A (resistive loads)
Contact current:
<42V pk.
Terminal voltage:
Gold
Contact material:
Snubber networks are NOT fitted
Snubbers:
42V pk max.
Contact isolation:
OEM Security
An OEM or reseller can protect their intellectual property by
preventing unauthorised cloning of the configuration.
2 | Mini8 Data Sheet
The PSU card supports 2 independent and isolated logic inputs
Logic (24V dc)
Input types:
–28.8V to +5V dc
Input logic 0 (off):
+10.8V to +28.8V dc
Input logic 1 (on):
2.5mA (approx.) at 10.8V; 10mA max at
Input current:
28.8V supply
110ms min.
Detectable pulse width:
42V pk max.
Isolation to system:
DI8 8-channel logic input card
Input/Output cards
TC8 8-channel and TC4 4-channel TC input card
The TC8 supports 8 independently programmable and electrically isolated
channels, catering for all standard and custom thermocouple types. The TC4
supports 4 channels to the same specification.
Channel types:
Input Range:
Resolution:
Temperature coefficient:
Cold junction range:
CJ rejection:
CJ accuracy:
Linearisation types:
Total accuracy:
Channel PV filter:
Sensor Break:
Input resistance:
Input leakage current:
Common mode rejection:
Series mode rejection:
Isolation channel-channel:
Isolation to system:
TC, mV
–77mV to +77mV
20 bit (∑∆ converter), 1.6µV with 1.6s
filter time
< ±50ppm (0.005%) of reading/ °C
–10°C to +70°C
> 30:1
±1°C
C, J, K, L, R, B, N, T, S, LINEAR mV, custom
±1°C ± 0.1% of reading (using internal CJC)
0.0 seconds (off) to 999.9 seconds, 1st order
low-pass
AC detector: Off, Low or High resistance trip
levels
>100M
<100nA (1nA typical)
>120dB, 47 – 63Hz
>60dB, 47 – 63Hz
42V pk max.
42V pk max.
The DI8 supports 8 independent input channels.
Input
Input
Input
Input
types:
logic 0 (off):
logic 1 (on):
current:
Detectable pulse width:
Isolation channel-channel:
Isolation to system:
RT4 resistance thermometer input card (PT100)
The RT4 supports 4 independently programmable and electrically isolated resistance
input channels. Each channel may connected as 2 wire, 3 wire or 4 wire.
Channel types:
Input range:
Calibration error:
Resolution:
Measurement noise:
Linearity error:
Temp coefficient:
DO8 8-channel digital output card
Lead resistance:
The supply line is protected to limit total card current to 200mA.
Bulb current:
Isolation channel-channel:
Isolation to system:
The DO8 supports 8 independently programmable channels, the output switches
requiring external power supply. Each channel is current and temperature
protected, foldback limiting occurring at about 100mA.
The 8 channels are isolated from the system (but not from each other). To
maintain isolation it is essential to use an independent and isolated PSU.
Channel types:
Channel supply (Vcs):
Logic 1 voltage output:
Logic 0 voltage output:
Logic 1 current output:
Min. pulse time:
Channel power limiting:
Terminal supply protection:
Isolation (channel-channel):
Isolation to system:
On/Off, Time Proportioned
15V dc to 30V dc
> (Vcs - 3V) (not in power limiting)
< 1.2V dc no-load, 0.9V typical
100mA max. (not in power limiting)
20ms
Current limiting capable of driving shortcircuit
load
Card supply is protected by 200mA selfhealing
fuse
N/A (Channels share common connections)
42V pk max.
RL8 8-channel relay output card
The RL8 supports 8 independently programmable channels. This module may
only be fitted in slot 2 or 3, giving a maximum of 16 relays in a Mini8 controller.
On/Off, Time Proportioned
264V ac
2 amps ac
Fitted on module
5V dc, 10mA
220ms
264V 230V nominal
264V 230V nominal
CT3 3-channel current-transformer input Card
The CT3 supports 3 independent channels designed for heater current
monitoring. A scan block allows periodic test of nominated outputs to detect load
(failure) changes.
Channel types:
Factory set accuracy:
Current input range:
Transformer ratio:
Input load burden:
Isolation:
A (current)
Better than ±2% of range
0mA to 50mA rms, 50/60Hz nominal
10/0.05 to 1000/0.05
1W
None (provided by CT)
Resistance/PT100
0 to 420 ohms, –242.02°C to +850°C for
PT100
±0.1ohms ±0.1% of reading, 22 to 420 ohms
±0.3°C ±0.1% of reading, -200°C to +850°C
0.008 ohms, 0.02°C
0.016 ohms, 0.04°C peak to peak, 1.6s
channel filter
0.06 ohms, 0.15°C peak to peak, no filter
±0.02 ohms, ±0.05°C
±0.002% of ohms reading per °C ambient
change relative to normal ambient 25°C
22 ohms max in each leg. Total resistance
including leads is restricted to the 420 ohm
maximum limit. 3 wire connection assumed
matched leads.
300μA
42V pk max
42V pk max
RT4 resistance thermometer input card (PT1000)
The RT4 supports 4 independently programmable and electrically isolated resistance
input channels. Each channel may connected as 2 wire, 3 wire or 4 wire.
Channel types:
Input range:
Calibration error:
Resolution:
Measurement noise:
Linearity error:
Temp coefficient:
Lead resistance:
The Mini8 controller chassis must be earthed (grounded) using the protective
earth stud.
Channel types:
Maximum contact voltage:
Maximum contact current:
Contact snubber:
Minimum contact wetting:
Min. pulse time:
Isolation (channel-channel):
Isolation to system:
Logic (24V dc)
–28.8V to +5V dc
+10.8V to +28.8V dc
2.5mA (approx.) at 10.8V; 10mA max at
28.8V supply
110ms min.
42V pk max.
42V pk max.
Bulb current:
Isolation channel-channel:
Isolation to system:
Resistance/PT1000
0 to 4200 ohms, –242.02°C to +850°C for
PT1000
±0.8ohms ±0.1% of reading, 220 to 4200 ohms
±0.2°C ±0.1% of reading, -200°C to +850°C
0.6 ohms, 0.15°C
0.2 ohms, 0.05°C peak to peak, 1.6s
channel filter
0.6 ohms, 0.15°C peak to peak, no filter
±0.2 ohms, ±0.05°C
±0.002% of ohms reading per °C ambient
change relative to normal ambient 25°C
22 ohms max in each leg. Total resistance
including leads is restricted to the 4200 ohm
maximum limit. 3 wire connection assumed
matched leads.
300μA
42V pk max
42V pk max
AO8 8-channel and AO4 4-channel 4-20mA output card
The AO8 supports 8 independently programmable and electrically isolated mA
output channels for 4-20mA current-loop applications. The AO4 supports 4
channels to the same specification. The AO4 and AO8 modules may only be
fitted in slot 4.
Channel types:
Output range:
Setting accuracy:
Resolution:
Isolation channel-channel:
Isolation to system:
mA (current) Output
0-20mA, 360Ω load max.
±0.5% of reading
1 part in 10000 (1uA typical)
42V pk max.
42V pk max.
Load failure detection
Requires CT3 module.
Max number of loads:
Max loads per CT:
Alarms:
Commissioning:
Measurement interval:
16 Time Proportioned Outputs
6 loads per CT input
1 in 8 Partial load failure, Over current,
SSR short circuit, SSR open circuit
Automatic or manual
1 sec – 60 sec
Mini8 Data Sheet | 3
Process alarms
Software features
Toolkit blocks
User wires:
User values:
2 input maths:
Orderable options of 30, 60, 120 or 250
32 real values
24 blocks Add, subtract, multiply, divide, absolute
difference, maximum, minimum, hot swap,
sample and hold, power, square root, Log, Ln,
exponential, switch
24 blocks AND, OR, XOR, latch, equal, not equal, greater
2 input logic:
than, less than, greater than or equal to, less
than or equal to
4 blocks AND, OR, XOR
8 input logic:
8 input multiple operator:
4 blocks Maximum, Minimum, Average. Input/Outputs
to allow cascading of blocks
4 blocks 8 sets of 8 values selected by input parameter
8 input multiplexer:
2 blocks 2 decades (8 inputs giving 0 to 99)
BCD input:
2 blocks Max, min, time above threshold
Input monitor:
16 point linearisation:
2 blocks 16-point linearisation fit
Polynomial fit:
2 blocks Characterisation by poly fit table
Switchover:
1 block Smooth transition between two input values
8 blocks OnPulse, OnDelay, OneShot, MinOn Time
Timer blocks:
2 blocks Up or down, Directional flag
Counter blocks:
2 blocks Alarm at Threshold value
Totaliser blocks:
Real time clock:
1 block Day & time, 2 time based alarms
Transducer scaling:
2 blocks Transducer Auto-tare, calibration & comparison
cal
PID control loop blocks
Number of Loops:
Control modes:
Control outputs:
Cooling algorithms:
Tuning:
Auto manual control:
Setpoint rate limit:
Output rate limit:
Other features:
Number of alarms:
Alarm types:
Alarm modes:
32 analogue, 32 digital, 32 Sensor break
Absolute high, absolute low, deviation high,
deviation low, deviation band, sensor break,
logic high, logic low, rising edge, falling edge,
edge
Latching or non-latching, blocking, time delay
Setpoint programmer
The Setpoint Programmer is a software orderable option.
Number of programs:
Number of segments:
Number of event outputs
Digital inputs:
Power failure action:
Servo start:
8
128
8 per program (64 total)
Run, Hold, Reset, Run/Hold, Run/Reset,
Program Advance, Skip, Segment, Sync
Ramp, Reset, Continue
PV, SP
Recipes
Recipes are a software orderable option.
Number of recipes:
Tags:
8
24 tags in total
0, 4, 8 or 16 Loops (order options)
On/Off, single PID, Dual channel OP
Analogue 4-20mA, Time proportioned logic
Linear, water, fan, or oil
3 sets PID, One-shot auto-tune
Bumpless transfer or forced manual output
available
Ramp in units per sec, per min or per hour
Ramp in % change per second
Feedforward, Input track, Sensor break OP,
Loop break alarm, remote SP, 2 internal loop
setpoints
Mechanical Details
Allow min 25mm
above and below
each unit
Allow min 25mm
for terminals and
cables
Mounting Information
The Mini8 controller is intended to be horizontally mounted
on symmetrical DIN Rail to EN50022-35 or 35 x 35 x 15
108mm
124mm
4 | Mini8 Data Sheet
115mm
Communications Interface LEDs
Legend Colour
RN/RUN Green
Function
Run mode
LEDs
Action
On – Running
Blinking – Standby/Config
Off – Not Running
RUN (EtherCAT only)
Off – the device is Initialisation, INIT state
Blinking – the device is in the Pre-Operational state
Single Flash – the device is in the Safe Operational state
On- the device is in the operational state
Flickering – the device is booting, but has not entered INIT state
CC
Green
Configuration activity
On – N/A
Blinking – Config Traffic
Off – N/A
FC
Green
Field Comms activity
On – Connected
Non-enhanced DeviceNet®
Blinking – Ready
Off – Offline
Modbus, Profibus, and Ethernet
Off – No traffic or offline
Blinking – Comms Traffic
NET
MOD
ERR
Bi-Col
Bi-Col
RED
Network Status
(enhanced
DeviceNet only)
Off – Offline
Blinking Green – Online but no connections
On Green – Online with connections
Blinking Red – Connection timed out
On Red – Total connection failure
Blinking Red/Green – Comms fault
Network Satus
(EtherNet/IP only)
Off – Not online
Flashing Green – Online but no connection
Steady Green – Online and operating correctly
Flashing Red – Connection timeout
Steady Red – Duplication of IP address
Flashing Green and red – Initialisation
Module Status
(enhanced
DeviceNet only)
Off – Power not supplied to network
On Green – DeviceNet interface operational
On Red – Power not supplied to controller or Checksum failure
Blinking Red/Off – Recoverable fault. Comms. error between
network and DeviceNet interface
Blinking Red/Green – Power-up tests, failure to enter cyclic states
or invalid baud rate
Module Status
(EtherNet/IP only)
Off – Not online
Flashing Green – Online but no connection
Steady Green – Online and operating correctly
Flashing Red – Connection timeout
Steady Red – Duplication of IP address
Flashing Green and Red – Initialisation
Error Status Indication
(EtherCAT only)
Off - No error
On - Application Failure, no communications with Mini8
Power Supply
Legend
Supply
24V
24V
0V
GND
24V dc
24V dc
0V
Ground
Legend
P
Colour
Green
Function
Indicates Power status
A
Red
Indicates Relay A state
B
Red
Indicates Relay B state
Action
On – Power On
Off – Power Off
On – Energised
Off – De-Energised
On – Energised
Off – De-Energised
RL8
AO8/A04
Relay Output
(slots 2 and/or 3 only)
Ananlogue Output
(slot 4 only)
Contact voltage/current –
264V ac/2A RMS max.
Output current – 0 to 20mA
360 ohm max. load.
ISOLATION (264V ac Basic)
• Channel to Channel: 264V ac Basic
• Channel to system: Reinforced
ISOLATION
• Channel to Channel: 42V pk.
• Channel to system: 42V pk.
Note.
Protective earth conductor MUST be
used if RL8 module is fitted.
Note.
AO4 supports Channels
1 to 4 only.
Legend
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Function
RLY1 A
RLY1 B
RLY2 A
RLY2 B
RLY3 A
RLY3 B
RLY4 A
RLY4 B
RLY5 A
RLY5 B
RLY6 A
RLY6 B
RLY7 A
RLY7 B
RLY8 A
RLY8 B
Legend
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Function
OP1+
OP1–
OP2+
OP2–
OP3+
OP3–
OP4+
OP4–
OP5+
OP5–
OP6+
OP6–
OP7+
OP7–
OP8+
OP8–
Standard I/O Connections
Linked
This terminal can accept wire
sizes 0.2 - 2.5mm (24 – 12 awg).
POWER SUPPLY SPECIFICATON
Power supply voltage: 17.8V dc min to 28.8V dc max.
Power comsumption: 15W max.
Legend Function
D1
Digital Input 1
D2
Digital Input 2
C
Digital Input Common
A1
Relay A n/open
A2
Relay A n/closed
A3
Relay A Common
B1
Relay B n/open
B2
Relay B n/closed
B3
Relay B Common
Note.
Digital Inputs: ON requires greater than
10.8V with 2mA drive, 30V max.
Relay Contacts: 1 Amp max, 42V dc max.
COMMUNICATIONS
Communications connection
terminals are version dependant.
TC8/TC4
RT4
DI8
CT3
DO8
Thermocouple Input
2, 3, 4 Wire RTD Input
Logic Input
Transformer Input
Logic Output
ISOLATION
• Channel to Channel: 42V pk.
• Channel to system: 42V pk.
ISOLATION
• Channel to Channel: 42V pk.
• Channel to system: 42V pk.
ISOLATION
• Channel to Channel: 42V pk.
• Channel to system: 42V pk.
ISOLATION
• Channel to Channel: N/A
• Channel to system: N/A
ISOLATION
• Channel to Channel: N/A
• Channel to system: 42V peak with
independant supply
Note.
Input specification as for
Standard I/O above.
Note.
Isolation provided by current
transformers.
Notes.
Requires 24V dc supply.
* Linked internally.
Note.
TC4 supports Channels 1 to 4
only.
Legend
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Function
TC1+
TC1–
TC2+
TC2–
TC3+
TC3–
TC4+
TC4–
TC5+
TC5–
TC6+
TC6–
TC7+
TC7–
TC8+
TC8–
Legend
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Function
CH1 I+
CH1 S+
CH1 S–
CH1 I–
CH2 I+
CH2 S+
CH2 S–
CH2 I–
CH3 I+
CH3 S+
CH3 S–
CH3 I–
CH4 I+
CH4 S+
CH4 S–
CH4 I–
Wire
Connections
2 3 4
Legend
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Function
D1+
D1–
D2+
D2–
D3+
D3–
D4+
D4–
D5+
D5–
D6+
D6–
D7+
D7–
D8+
D8–
Legend
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Function
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
In1 A
In1 B
No connection
In2 A
In2 B
No connection
In3 A
In3 B
*
Legend
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Function
Supply in +
Supply in +
OP1+
OP2+
OP3+
OP4+
Supply & OP
Supply & OP –
Supply in +
Supply in +
OP5+
OP6+
OP7+
OP8+
Supply & OP
Supply & OP –
*
Mini8 Data Sheet | 5
Order Code
1
2
3
15
16
17
4
5
6
7
8
9
10
11
12
13
MINI8
Basic Product
Mini8 Controller
MINI8
5 Temperature Units
C
F
11 Wires
Centigrade
Fahrenheit
30
60
120
250
1 Control Loops
ACQ
4LP
8LP
16LP
IO Acquisition only
4 Control loopsr
8 Control loops
16 Control loops
2 Programs
0PRG
1PRG
XPRG
No programs
1 profile – 50 programs
Multi-profiles – 50 programs
(Note 1)
6-9 IO Slots 1, 2, 3, 4
XXX
TC4
TC8
RT4
AO4
AO8
DO8
CT3
RL8
3 PSU
VL
24V dc
DI8
No module fitted
4 Ch TC input
8 Ch TC input
4 Ch RTD PT100/PT1000
input
4 Ch 4-20mA O/P
(Note 3)
8 Ch 4-20mA O/P
(Note 3)
8 Ch logic O/P
3 Ch CT input
(Note 4)
8 Ch relay O/P
(Note 5)
8 Ch logic input
10 Applications
4 Communications
Non isolated Modbus
Slave
ISOLMBUS Isolated Modbus RTU
Slave
DEVICENET DeviceNet Slave
PBUSRJ45 Profibus Slave RJ45
(Note 2)
Profibus Slave 9 Pin
PBUS9PIN
D type (Note 2)
ENETMBUS Ethernet Modbus
TCP/IP Slave
DeviceNet M12
DNETM12
Connector Slave
EtherNet/IP
ENETIP
ETHERCAT EtherCAT
MODBUS
STD
EC8
FC8
No configuration
8 Loop extrusion controller
(Note 6)
Requires 8LP or 250 wires
and modules placed in the
following slots
Slot 1 = TC8
Slot 2 = CT3 or XXX
Slot 3 = DO8
Slot 4 = DO8
8 Loop furnace controller
Requires 8LP or 250 wires
and modules placed in the
following slots
Slot 1 = TC8
Slot 4 = AO8
Eurotherm Limited
12 Recipes
NONE
RCP
No recipes
8 Recipes
ENG
FRA
GER
SPA
ITA
English
French
German
Spanish
Italian
14 Configuration Software
English
ENG
NONE No DVD
ITOOLS Eurotherm iTools DVD &
Mini8 Controller
documentation
16 Calibration Certificates
XXXXX
CERT1
CERT2
None
Certificate of Conformity
Factory input aalibration
per input (Note 7)
XXXXX Standard
EU0725 OEM Security
Notes
1.
2.
3.
4.
5.
6.
7.
HA031260
SUBMINI8/SHUNT/249R.1
RES250
RES500
CTR100000/000
CTR200000/000
CTR400000/000
CTR500000/000
iTools/None/3000CK
SUB21/IV10
Eurotherm Limited pursues a policy of continuous development and product
improvement. The specifications in this document may therefore be changed without
notice. The information in this document is given in good faith, but is intended for
guidance only.
Eurotherm Limited will accept no responsibility for any losses arising from errors in
this document.
Document Number HA028480 Issue 10
Standard
Extended
If 4 Loops ordered 4
programmers are supplied; 8 or
16 loops ordered 8 programmers
are supplied.
Profibus motherboard fitted.
AO4/AO8 in slot 4 only.
Only 1 CT3 per Mini8.
RL8 in slots 2/3 only.
EC8 is a preconfigured version of
Mini8 offering 8 control loops
with Heat/Cool logic outputs.
CERT2 is 5 point calibration.
Accessories
All rights are strictly reserved. No part of this document may be reproduced, modified,
or transmitted in any form by any means, nor may it be stored in a retrieval system
other than for the purpose to act as an aid in operating the equipment to which the
document relates, without the prior written permission of Eurotherm Limited.
Scan for local
contacts
XXXXX
WL005
17 Specials
13 Manual Language
Eurotherm by Schneider Electric, the Eurotherm logo, Chessell, EurothermSuite,
Mini8, Eycon, Eyris, EPower, EPack, nanodac, piccolo, versadac, optivis, Foxboro
and Wonderware are trademarks of Schneider Electric, its subsidiaries and affiliates.
All other brands may be trademarks of their respective owners.
Faraday Close, Durrington,
Worthing, West Sussex, BN13 3PL
Phone: +44 (01903) 268500
Fax: +44 (01903) 265982
www.eurotherm.com/worldwide
30 30 User Wires
60 User Wires
120 User Wires
250 User Wires
15 Warranty
Engeering/DVD manual
2.49R Precision resistor
250R resistor for 0-5V dc OP
500R resistor for 0-10V dc OP
10A Current transformer
25A Current transformer
50A Current transformer
100A Current transformer
Configuration clip
0-10V input adaptor
© Copyright Eurotherm Limited 2015
14
July 2015
Fly UP