Tender No. UGVCL/SP/III/567/ 3-Phase CT Meter
Tender No. UGVCL/SP/III/567/ 3-Phase CT Meter ANNEXURE - A Display Parameters for 3-Phase 4 wire LT Static CT Operated 100/5 Amp & 200/5 Amp Energy Meter (TO BE PROVIDED IN FOLLOWING SEQUENCE) Auto Parameters of this mode should display on auto scrolling as well as manually up & down Scroll scrolling using push button Mode Sequence Parameter Notation 1 Display check ------- 1-A 24hrs. total active energy (fundamental+ harmonics) TC Kwh 1-B 24hrs. total reactive energy TC Kvarh lg 1-C MD of 24hours recorded (Cumulative MD) CMD ------------Kw Sr. No. of Meters UTP 2-A 24hrs. total active energy (fundamental+ harmonics) TC Kwh 2-B 24hrs. total reactive energy TC Kvarh lg 2-C MD of 24hours recorded (Cumulative MD) CMD ------------Kw 2 3 CT Ratio 3-A 24hrs. total active energy (fundamental+ harmonics) TC Kwh 3-B 24hrs. total reactive energy TC Kvarh lg 3-C MD of 24hours recorded (Cumulative MD) CMD ------------Kw 4 RTC date & time 4-A 24hrs. total active energy (fundamental+ harmonics) TC Kwh 4-B 24hrs. total reactive energy TC Kvarh lg 4-C MD of 24hours recorded (Cumulative MD) CMD ------------Kw R- Phase Voltage V1 5-A 24hrs. total active energy (fundamental+ harmonics) TC Kwh 5-B 24hrs. total reactive energy TC Kvarh lg 5-C MD of 24hours recorded (Cumulative MD) CMD ------------Kw Y- Phase Voltage V2 24hrs. total active energy (fundamental+ harmonics) TC Kwh 5 6 6-A Signature of Tenderer Place: Company’s Round Seal Date: Page 1 of 11 Tender No. UGVCL/SP/III/567/ 3-Phase CT Meter 6-B 24hrs. total reactive energy TC Kvarh lg 6-C MD of 24hours recorded (Cumulative MD) CMD ------------Kw B- Phase Voltage V3 7-A 24hrs. total active energy (fundamental+ harmonics) TC Kwh 7-B 24hrs. total reactive energy TC Kvarh lg 7-C MD of 24hours recorded (Cumulative MD) CMD ------------Kw R- Phase Line Current I1 8-A 24hrs. total active energy (fundamental+ harmonics) TC Kwh 8-B 24hrs. total reactive energy TC Kvarh lg 8-C MD of 24hours recorded (Cumulative MD) CMD ------------Kw Y- Phase Line Current I2 9-A 24hrs. total active energy (fundamental+ harmonics) TC Kwh 9-B 24hrs. total reactive energy TC Kvarh lg 9-C MD of 24hours recorded (Cumulative MD) CMD ------------Kw 10 B- Phase Line Current I3 10-A 24hrs. total active energy (fundamental+ harmonics) TC Kwh 10-B 24hrs. total reactive energy TC Kvarh lg 10-C MD of 24hours recorded (Cumulative MD) CMD ------------Kw Inst. P.F. (Avg. of 3Ph.) Pr.PF. 11-A 24hrs. total active energy (fundamental+ harmonics) TC Kwh 11-B 24hrs. total reactive energy TC Kvarh lg 11-C MD of 24hours recorded (Cumulative MD) MD ------------Kw Inst. Total active power Pr.Kw. 12-A 24hrs. total active energy (fundamental+ harmonics) TC Kwh 12-B 24hrs. total reactive energy TC Kvarh lg 12-C MD of 24hours recorded (Cumulative MD) CMD ------------Kw 24hrs. apparent energy derived from Vectorial summation of TC Kvah 7 8 9 11 12 13 total (fund+ Harm.) active energy and reactive (lag only) energy Signature of Tenderer Place: Company’s Round Seal Date: Page 2 of 11 Tender No. UGVCL/SP/III/567/ 3-Phase CT Meter 13-A 24hrs. total active energy (fundamental+ harmonics) TC Kwh 13-B 24hrs. total reactive energy TC Kvarh lg 13-C MD of 24hours recorded (Cumulative MD) CMD ------------Kw 14 Rising demand in KW with elapse time 14-A 24hrs. total active energy (fundamental+ harmonics) TC Kwh 14-B 24hrs. total reactive energy TC Kvarh lg 14-C MD of 24hours recorded (Cumulative MD) CMD ------------Kw KW-MD of last billing period i.e. billing MD of 24hours BMD ------------Kw 15 recorded between last two resets [ 15-A 24hrs. total active energy (fundamental+ harmonics) TC Kwh 15-B 24hrs. total reactive energy TC Kvarh lg 15-C MD of 24hours recorded (Cumulative MD) CMD ------------Kw Cumm KWH for Peak hours (Zone1) T1C Kwh 16-A 24hrs. total active energy (fundamental+ harmonics) TC Kwh 16-B 24hrs. total reactive energy TC Kvarh lg 16-C MD of 24hours recorded (Cumulative MD) CMD ------------Kw Cumm. KWH for Night hours (Zone2) T2C Kwh 17-A 24hrs. total active energy (fundamental+ harmonics) TC Kwh 17-B 24hrs. total reactive energy TC Kvarh lg 17-C MD of 24hours recorded (Cumulative MD) CMD ------------Kw Cumm KWH for Lean hours (Zone3) T3C K wh 24hrs. total active energy (fundamental+ harmonics) TC Kwh 16 17 18 18-A Signature of Tenderer Place: Company’s Round Seal Date: Page 3 of 11 Tender No. UGVCL/SP/III/567/ 3-Phase CT Meter 18-B 24hrs. total reactive energy TC Kvarh lg 18-C MD of 24hours recorded (Cumulative MD) CMD ------------Kw MD KW between last two resets – Peak Hours (Zone-1) T1 BMD 19-A 24hrs. total active energy (fundamental+ harmonics) TC Kwh 19-B 24hrs. total reactive energy TC Kvarh lg 19-C MD of 24hours recorded (Cumulative MD) CMD ------------Kw MD KW between last two resets – Night Hours (Zone-2) T2 BMD 20-A 24hrs. total active energy (fundamental+ harmonics) TC Kwh 20-B 24hrs. total reactive energy TC Kvarh lg 20-C MD of 24hours recorded (Cumulative MD) CMD ------------Kw MD KW between last two resets – Lean Hours (Zone-3) T3 BMD 21-A 24hrs. total active energy (fundamental+ harmonics) TC Kwh 21-B 24hrs. total reactive energy TC Kvarh lg 21-C MD of 24hours recorded (Cumulative MD) CMD ------------Kw MD KW for Present Billing – Peak Hours ( Zone -1) T1RMD ------ Kw 22-A 24hrs. total active energy (fundamental+ harmonics) TC Kwh 22-B 24hrs. total reactive energy TC Kvarh lg 22-C MD of 24hours recorded (Cumulative MD) CMD ------------Kw MD KW for Present Billing – Night Hours ( Zone -2) T2RMD ------ Kw 23-A 24hrs. total active energy (fundamental+ harmonics) TC Kwh 23-B 24hrs. total reactive energy TC Kvarh lg 19 20 21 22 23 Signature of Tenderer Place: Company’s Round Seal Date: Page 4 of 11 Tender No. UGVCL/SP/III/567/ 3-Phase CT Meter 23-C MD of 24hours recorded (Cumulative MD) CMD ------------Kw MD KW for Present Billing – Lean Hours ( Zone -3) T3RMD ------ Kw 24-A 24hrs. total active energy (fundamental+ harmonics) TC Kwh 24-B 24hrs. total reactive energy TC Kvarh lg 24-C MD of 24hours recorded (Cumulative MD) CMD ------------Kw MD KW for Present Billing Period ( After last reset) RMD ------ Kw. 25-A 24hrs. total active energy (fundamental+ harmonics) TC Kwh 25-B 24hrs. total reactive energy TC Kvarh lg 25-C MD of 24hours recorded (Cumulative MD) CMD ------------Kw 24 25 26 Voltage failure count phase wise 26-A 24hrs. total active energy (fundamental+ harmonics) TC Kwh 26-B 24hrs. total reactive energy TC Kvarh lg 26-C MD of 24hours recorded (Cumulative MD) CMD ------------Kw 27 Current failure count phase wise 27-A 24hrs. total active energy (fundamental+ harmonics) TC Kwh 27-B 24hrs. total reactive energy TC Kvarh lg 27-C MD of 24hours recorded (Cumulative MD) CMD ------------Kw 28 Voltage unbalance Count 28-A 24hrs. total active energy (fundamental+ harmonics) TC Kwh 28-B 24hrs. total reactive energy TC Kvarh lg 28-C MD of 24hours recorded (Cumulative MD) CMD ------------Kw Signature of Tenderer Place: Company’s Round Seal Date: Page 5 of 11 Tender No. UGVCL/SP/III/567/ 3-Phase CT Meter 29 Curent unbalance Count 29-A 24hrs. total active energy (fundamental+ harmonics) TC Kwh 29-B 24hrs. total reactive energy TC Kvarh lg 29-C MD of 24hours recorded (Cumulative MD) CMD ------------Kw 30 Current reversal count- phase wise 30-A 24hrs. total active energy (fundamental+ harmonics) TC Kwh 30-B 24hrs. total reactive energy TC Kvarh lg 30-C MD of 24hours recorded (Cumulative MD) CMD ------------Kw 31 Magnet tamper count 31-A 24hrs. total active energy (fundamental+ harmonics) TC Kwh 31-B 24hrs. total reactive energy TC Kvarh lg 31-C MD of 24hours recorded (Cumulative MD) CMD ------------Kw 32 Neutral Disturbance Count 32-A 24hrs. total active energy (fundamental+ harmonics) TC Kwh 32-B 24hrs. total reactive energy TC Kvarh lg 32-C MD of 24hours recorded (Cumulative MD) CMD ------------Kw 33 Total Tamper Count 33-A 24hrs. total active energy (fundamental+ harmonics) TC Kwh 33-B 24hrs. total reactive energy TC Kvarh lg 33-C MD of 24hours recorded (Cumulative MD) CMD ------------Kw Signature of Tenderer Place: Company’s Round Seal Date: Page 6 of 11 Tender No. UGVCL/SP/III/567/ 3-Phase CT Meter Mode : 1 Parameters of this mode should manually up & down scrolling using push button (PushButton) Sequence Parameter Notation 1 Display check ------- 2 Sr. No. of Meters UTP 3 CT Ratio 4 RTC date & time 5 R- Phase Voltage V1 6 Y- Phase Voltage V2 7 B- Phase Voltage V3 8 R- Phase Line Current I1 9 Y- Phase Line Current I2 10 B- Phase Line Current I3 11 Inst. P.F. (Avg. of 3Ph.) Pr.PF. 12 Inst. Total active power Pr.Kw. 13 24hrs. Total active energy (fundamental+ harmonics) TC Kwh 14 24hrs. Total reactive energy TC Kvarh lg 15 24hrs. Apparent energy derived from Vectorial summation of TC Kvah total (fund+ Harm.) active energy and reactive (lag only) energy 16 Rising demand in KW with elapse time 17 MD KW for Present Billing Period ( After last reset) RMD ------ Kw. 18 KW-MD of last billing period i.e. billing MD of 24hours BMD ------------Kw recorded between last two resets [ 19 MD of 24hours recorded (Cumulative MD) CMD ------------Kw 20 Cumm KWH for Peak hours (Zone1) T1C Kwh 21 Cumm. KWH for Night hours (Zone2) T2C Kwh Signature of Tenderer Place: Company’s Round Seal Date: Page 7 of 11 Tender No. UGVCL/SP/III/567/ 3-Phase CT Meter 22 Cumm KWH for Lean hours (Zone3) T3C K wh 23 MD KW between last two resets – Peak Hours (Zone-1) T1 BMD 24 MD KW between last two resets – Night Hours (Zone-2) T2 BMD 25 MD KW between last two resets – Lean Hours (Zone-3) T3 BMD 26 MD KW for Present Billing – Peak Hours ( Zone -1) T1RMD ------ Kw 27 MD KW for Present Billing – Night Hours ( Zone -2) T2RMD ------ Kw 28 MD KW for Present Billing – Lean Hours ( Zone -3) T3RMD ------ Kw 29 Voltage failure count phase wise 30 Current failure count phase wise 31 Voltage unbalance Count 32 Curent unbalance Count 33 Current reversal count- phase wise 34 Magnet Tamper Count 35 Neutral Disturbance count. 36 Total Tamper Count Signature of Tenderer Place: Company’s Round Seal Date: Page 8 of 11 Tender No. UGVCL/SP/III/567/ 3-Phase CT Meter Mode : 2 Parameters of this mode should display manually up & down scrolling using push button Sequence Parameter Notation 1 Inst. P.F.Phase 1 P.F1 2 Inst. P.F.Phase 2 P.F2 3 Inst. P.F.Phase 3 P.F3 4 Phase Sequence - Voltage 5 Phase Sequence -Current 6 Frequency 7 Cumm. KVARH ( Lead) 8 Cumm. KVARH-lag for peak hours (Zone1) 9 Cumm KVARH-lag for night hours (Zone2) 10 Cumm KVARH-lag for balance hours (Zone3) 11 Cumm. KVAH for peak hours (Zone1) 12 Cumm KVAH for night hours (Zone2) 13 Cumm KVAH for balance hours (Zone3) 14 Avg. PF for last billing – Peak Hours (Zone-1) 15 Avg. PF for last billing – Night Hours (Zone-2) 16 Avg. PF for last billing – Lean hours (Zone-3) 17 MD KVA after last billing – Peak Hours (Zone-1) 18 MD KVA after last billing – Night Hours (Zone-2) 19 MD KVA after last billing – Lean Hours (Zone-3) 20 MD KVA between last two resets – Peak Hours (Zone-1) 21 MD KVA between last two resets – Night Hours (Zone-2) 22 MD KVA between last two resets – Lean Hours (Zone-3) Mode : 3 Hz Parameters of this mode should display manually up & down scrolling using push button Sequence Parameter 1 High Resolution display for KWH 2 High Resolution display for KVARH-Lag 3 High Resolution display for KVAH Signature of Tenderer Place: Company’s Round Seal Notation Date: Page 9 of 11 Tender No. UGVCL/SP/III/567/ 3-Phase CT Meter ANNEXURE - B Tamper Logic & threshold values for 3 Ph. 4 Wire 100/5 & 200/5 Amp. CT Operated static energy meters Tamper Logics / Conditions & (Occurrence & Restoration) Persistence Time Sr No Type of Tamper Require ment Occurrence Voltage 1 2 3 4 5 Voltage Failure Current Failure Voltage Unbalance Current Unbalance Current reversal Phase wise Vx< 40% of Vref irrespective to any other phase voltage Phase wise All voltages > 75 % of Vref. - (Vmax - Vmin) > 10% of max Voltage of 3 phase voltages and all voltages > 60% of Vref . - Phase wise All voltages > 75 % of Vref. All voltages > 75 % of Vref. Signature of Tenderer Place: Current Ix > 10% of Ib Restoration Persist Time 15 Minutes Ir or Iy or Ib < 2% of actual max. current and any one phase has value > 10% lb Ix > 10% of Ib For at least any one phase (Diff. of Actual Max current & Actual Min current ) > 30 % of Actual maximum current and all phase has value greater than 10% Ib Ix > 10% of Ib, direction of current reverse and PF value > 0.2 Voltage Vx > 75% vref i.e. 180 V irrespective to any other phase voltage 15 15 Minutes 5 Minutes lr or Iy or Ib > 2% of actual max. current and any one phase has value > 10% lb Minutes (Vmax-Vmin ) <10% of max voltage of 3 phase voltages 15 Minutes 15 Minutes Company’s Round Seal Persist Time Current 5 Minutes 5 Minutes (Diff. of Actual Max current & Actual Min current ) < 30 % of Actual maximum current Ip > 10% of Ib, direction of current forward and PF value > 0.2 5 Minutes 5 Minutes Date: Page 10 of 11 Tender No. UGVCL/SP/III/567/ 3-Phase CT Meter 6 7 Magnetic Influence Neutral Disturbance 8 Low Voltage 9 High Voltage When magnet influence start affecting the accuracy, meter should start recording at Imax - - - - Phase to Neutral voltage for any two phases is > 350 volts and for remaining phase is < 5OV Vx > 40% of Vref & Vx< 75 % of Vref Vx > 115% of Vref When magnet influence stop affecting the accuracy, meter should start recording at actual load 1 Minute 1 Minute 15 Minutes Phase to Neutral voltage for all the 3 phases > 75 % Vref 5 Minutes Ix > 10% of Ib For at least any one phase 15 Minutes Vx > 75 % of Vref 5 Minutes Ix > 10% of Ib For at least any one phase 15 Minutes Vx < 110% Vref ( 264 V) 5 Minutes Ix > 10% of Ib Note: For tamper logics, following points shell be taken in consideration 1. During Neutral disturbance tamper, All voltage related tampers (i.e. Voltage Failure, Voltage Unbalance, High Voltage & Low Voltage) shall not logged. 2. During High Voltage & Low Voltage tampers Voltage unbalance tamper shall not logged. 3. During Voltage failure Tamper, Voltage Unbalance & Low Voltage tamper shall not logged. 4. During current failure Tamper, Current Unbalance tampers shall not logged. 5. During power failure duration, if any tampers persisting, those tampers shall not get recovered until it meets the logic for restoration and duration of respective tamper shall be from occurrence of that tamper irrespective of power failure duration. 6. For tamper events logging, snap shot data i.e. instantaneous parameters, active energy register reading (Total kwh) & date & time should be corresponds to starting of occurrence and starting of restoration. 7. Snap shot of date and time should be available for occurrences and restorations of events. 8. Low PF tamper feature is not required in display as well as memory. Instead of that, MD reset counts may be added in display-1 mode. Signature of Tenderer Place: Company’s Round Seal Date: Page 11 of 11