Comments
Description
Transcript
515 SOUTH AREA OPERATION 1. Purpose
Operating Policies and Procedures Transmission OPP 515 Issued: Supersedes 2007-09-27 515 SOUTH AREA OPERATION 1. Purpose To provide policies for market participants and policies and procedures for the System Controller (SC) to follow when managing the reliable operation of the transmission system and wind power facilities (WPF) operations in the South area of Alberta, except the Empress area which is covered in OPP 503. 2. Background As more wind power facilities (WPF) are added in the Southwest area, more transmission constraints occur in the system such as overloading of transmission facilities. Remedial action schemes (RASs) have been installed to trip or run-back generation to reduce overloads on transmission facilities. Refer to Table 3, Table 4, Table 5 and Table 8 for description of RASs. In situations where a RAS is not triggered, action is required by the SC and other operating entities to remove overloads on transmission facilities. The wind turbine generators at the Magrath WPF, Garden City (226S), are doubly-fed induction machines capable of controlling reactive power. A WindVar device has been installed at the Garden City substation (226S). It will send a command signal to all the wind turbine generators to adjust reactive power in order to regulate the collector substation voltage. The Magrath WPF will operate to a voltage control set point directed by the SC. Garden City (226S) is connected via 891L/863L between Riverbend (T618S) and Magrath (T225S) resulting in a 3 terminal line. This line is protected by a line overcurrent differential scheme. Six 6.6 MVAr independently switched capacitor banks and an 8 MVAr Dynamic VAR (D-VAR) voltage regulation system have been installed at the Summerview substation (354S) for voltage control. The D-VAR operates to a voltage control set point directed by the SC. The Oldman River Hydro (A806S) generation is connected to the Pincher Creek substation (T396S) on the same line as Summerview WPF via 893L, resulting in a 3 terminal line (893L and 893AL). This line is protected by a line overcurrent differential scheme. The wind turbine generators at the Taylor WPF are induction machines with back-to-back rectifierinverter units providing power factor control. The Taylor WPF is located adjacent to the Taylor Hydro generation station which is radially connected to Magrath (T225S). The Kettles Hill WPF is located approximately 7 km from Pincher Creek substation (T396S) and 24 km from Peigan substation (59S). The associated Kettles Hill substation (383S) is T-tapped from 170L. This WPF is comprised of 35 sets of 1.8 MW asynchronous generators, totaling 63 MW. The voltage regulation system consists of five 6.6 MVAr independently switched capacitor banks and an 8 MVAr D-VAR. The Soderglen WPF is comprised of 47 sets of 1.5 MW asynchronous generators, totaling 70.5 MW. The wind turbines are equipped with wind volt-amp-reactive (WindVAR) system for voltage regulation. The associated Soderglen substation (243S) is T-tapped from 725L (Peigan substation 59S – Bowron substation L674S). The Suncor Chin Chute WPF is comprised of 20 sets of 1.5 MW doubly-fed asynchronous generators, totaling 30 MW. The associated Hillridge substation (139S) is T-tapped from 172L (Coaldale T254S – DRAFT 2 Issued for review: 2008-01-28 Page 1 of 14 Transmission OPP 515 South Area Operation Taber T83S). The WPF is equipped with a dynamic voltage regulator together with an 8 MVAr capacitor bank for voltage control. The ENMAX Taber WPF is comprised of 37 sets of 2.2 MW wind turbines, totally 80 MW. The associated Taber Wind substation (C134S) is T-tapped from 607L (Fincastle T336S – Conrad T135S). The reactive power system is comprised of a 4.2 MVAr capacitor bank on each of the two collector system buses and dynamic VAR capability from the wind turbine generators. Dynamic thermal line rating (DTLR) system is installed on the 170L between Pincher Creek T396S and Peigan 59S. Three CAT-1 Remotes monitor the line and transmit the data to the EMS via the CAT Master Station. The EMS will compare and select the lesser of calculated dynamic ratings or the 170L maximum ratings and provide visibility to the operators. The major transmission and generation facilities which are presently part of the South area are shown in Figure 1. A list of generation in the South area is provided in Table 1. A portion of AltaLink Operating Procedure T-1.1 has been applied in developing this OPP. Table 2 presents the 69 kV and 138 kV line capacity limits and maximum duration for a sustained overload. The SC must manage interchange levels within the criteria specified by the WECC. The SC maintains energy balance between generation and load within the Alberta control area by dispatching energy offered into the energy market merit order, and dispatching regulating reserve assets in the ancillary service merit order. Any unanticipated changes in generation or load can cause the interchange level on the AB-BC interconnection to go off schedule and may require intervention by the SC to recover the interchange level to the scheduled value. To help the SC maintain the generation-load balance, approval from the SC is required before interconnecting generation to the AIES. 3. Policy • Southwest area generation may be constrained or curtailed due to area system constraints. • The Magrath WPF RAS will operate when either 618S863X is open or both 618S725N and 618S824 are open at Riverbend (T618S) as described in Table 3. • The Irrican Hydro RAS will operate under specific conditions as described in Table 5. • Dynamic thermal line rating (DTLR) will be used for monitoring 170L (Pincher Creek 396S – Peigan 59S). If the DTLR for 170L is not available, static rating will be used in monitoring the line. • The maximum continuous rating generated from the DTLR will be limited to 600 A (143 MVA at rated voltage) in the summer and 720 A (172 MVA at rated voltage) in the winter due to thermal constraint. • The Summerview – Kettles Hill WPF RAS for monitoring 170L (Pincher Creek 396S – Peigan 59S) will base on the DTLR for initiating generation runback signals when the line exceeds 100 % of the DTLR. The RAS will initiate instantaneous generator tripping signals when the line exceeds 140 % of the static rating, regardless of the DTLR. • Upon loss of the DTLR, the Summerview – Kettles Hill WPF RAS will use static summer and winter ratings. • The Summerview – Kettles Hill WPF RAS will operate for overload conditions 786L at Coleman substation (T799S) as described in Table 4. If the line exceeds its preset threshold, this RAS will be triggered. The first stage is to run back the WPF generators and the second stage is to trip the WPF generators if overload still persists in the sequence as specified in Table 4. DRAFT 2 Issued for review: 2008-01-28 Page 2 of 14 Transmission OPP 515 South Area Operation • If the Summerview component of the RAS is not available then the SC will undertake the preemptive action as described in Section 5.5 to curtail Summerview. Similarly, if it is only the Kettles Hill component of the RAS that is unavailable, then only Kettles Hill will be curtailed. • The Soderglen WPF RAS will operate for overload conditions on 725LW at Bowron substation (L674S) or communication link failure as described in Table 8. • Transmission facility overloads caused by single transmission contingencies will be removed by curtailing generation through the operation of RASs and through SC directives as described in Table 6. • System voltage levels will be maintained within operating limits by utilizing the reactive power capability of generators during normal and emergency conditions. The Summerview, Kettles Hill, Soderglen, Suncor Chin Chute, EMMAX Taber, and Magrath WPF operators will comply with voltage adjustment directives (kV) from the SC to adjust the voltage set point within 10 minutes. • Active VAr coordination by the SC, between generators at Oldman River Hydro (A806S), Summerview WPF, Kettles Hill WPF, Soderglen WPF and Transmission Facility Owner (TFO) system compensation devices at Pincher Creek (T396S) is required to keep voltages within desired operating ranges, for the different operating conditions encountered in the Southwest area. The operating ranges for the voltage at the Pincher Creek (T396S) 138 kV bus are defined in OPP 702. This operating range is applicable to Oldman River Hydro (A806S), Kettles Hill (383S) and Summerview (354S) 138kV bus voltage as well. • If the Summerview WPF, Kettles Hill, Soderglen, Suncor Chin Chute, ENMAX Taber or the Magrath WPF cannot comply with a voltage adjustment directive within 10 minutes, the WPF operator will immediately inform the SC and provide reasons along with the estimated time when the voltage set point adjustment can be made. The SC will assess the area requirements and take alternative action if required. See Section 5.1 and Section 5.2 for details. • Following any area contingency or during emergency conditions, the SC may issue directives to curtail load or generation output to maintain system reliability or protect system facilities. In order to achieve the desired result: − The WPF generation at Magrath, Summerview, Kettles Hill, Soderglen, Suncor Chin Chute, ENMAX Taber and Taylor must be capable of being curtailed within 10 minutes to the MW level identified by the SC. − Load or generation output must not exceed the level identified by the SC during the time a directive is in effect. • If generation cannot be curtailed within 10 minutes, the SC will, when practical, direct AltaLink to remove the generation by opening the interconnection breaker or transmission facility to maintain system reliability or protect system facilities. AltaLink can trip but cannot close the interconnection breaker 52/T1 at Garden City (226S), 138 kV breaker at Soderglen (243S), 138kV breaker at Kettles Hill (383S), 138CB1 at Summerview (354S), 138 kV breaker (52/B1) at Suncor Hillridge (139S), or 138 kV breaker at Taber Wind Farm (C134S). • In order to allow the SC to maintain the energy balance between generation and load within the AIES, the following policy applies: − Generator operators must obtain SC approval before interconnecting generation to the AIES. DRAFT 2 Issued for review: 2008-01-28 Page 3 of 14 Transmission OPP 515 South Area Operation 4. − WPF operators must obtain SC approval before energizing a feeder to restore wind generation after a forced or planned outage to any feeder in the wind farm collector system. − Generator operators must obtain SC approval before increasing generation output after being tripped, ran back due to the operation of a RAS or curtailed by the SC. Responsibilities 4.1 System Controller The SC will: 4.2 • Issue directives to generator operators and/or AltaLink to curtail generation as required to remove transmission facility overloads in the Southwest area. • Issue directives to Summerview, Magrath, Soderglen, Kettles Hill, Suncor Chin Chute, and ENMAX Taber WPF operators for voltage set point adjustments as required. Generation Facility Operators The generation facility operators will: • Comply with directives to curtail generation within 10 minutes to the MW level identified by the SC. • Not allow their generation output to exceed the level identified by the SC during the time a curtailment directive is in effect. • Receive approval from the SC before interconnecting generation to the AIES. • Receive approval from the SC before increasing generation output after being tripped, ran back due to the operation of a RAS, or directed by the SC. • Inform the SC immediately if they are unable to comply with a voltage adjustment directive within 10 minutes and provide reasons along with the estimated time that the voltage adjustment can be made. In addition: 4.3 • WPF operators must receive approval from the SC before energizing a feeder to restore wind generation after a forced or planned outage to any feeder in the wind farm collector system. • The Summerview, Kettles Hill, Soderglen, Suncor Chin Chute, ENMAX Taber, and Magrath WPF operators will comply with directives from the SC to adjust the voltage set point within 10 minutes. Transmission Facility Owner • AltaLink can take immediate action to operate transmission facilities to protect their equipment, public or personnel safety or the environment. AltaLink will notify the SC of these actions as soon as possible. • AltaLink will comply with directives from the SC to remove generation by opening the interconnection breaker or transmission facility unless such action could result in damage to equipment, risk to public or personnel safety, or risk of undue damage to the environment. DRAFT 2 Issued for review: 2008-01-28 Page 4 of 14 Transmission OPP 515 South Area Operation • 5. AltaLink cannot close the interconnection breaker at Garden City 226S (52/T1), Soderglen 243S, Kettles Hill 383S, Summerview 354S (138CB1), Suncor Hillridge 139S (52/B1) or Taber Wind Farm C134S (134B138-607AL) System Controller Procedures 5.1 Adjusting the voltage set point at Magrath WPF To adjust the voltage set point at Magrath WPF the SC will: 5.2 1. Direct the operational contact as listed in Table 7 (confidential) to adjust the voltage to the new set point. 2. If informed by the WPF operator that he is unable to comply with the voltage adjustment directive: a. Assess the area requirements considering the estimated time that the WPF operator can make the voltage set point adjustment. b. Take alternative action if required (including tripping of generation or load). c. Record the date, time and description of the event along with the WPF operator’s reason for the inability to comply with the voltage adjustment directive in 10 minutes in the System Controller Shift Log as described in OPP 1301. Adjusting the voltage set point at Oldman River Hydro, Summerview WPF, Soderglen WPF and Kettles Hill WPF The SC will: 1. 2. Coordinate operation of Pincher Creek (T396S) 138 kV bus voltage by: a. Coordinating VAr adjustments from Oldman River Hydro and Summerview WPF, and Kettles Hill WPF to provide area voltage support while maintaining a VAr balance between the generating assets. Refer to Table 7 (confidential) for operational contacts. b. Requesting the AltaLink South Transmission Operator to switch area reactive devices as required. c. Checking VAr flows at the Oldman River Hydro, Summerview, Soderglen and Kettles Hill substations for proper VAr control coordination among Oldman River Hydro, Summerview WPF and Kettles Hill WPF and the reactive devices, and making adjustments as required. If informed by the WPF operator that he is unable to comply with the voltage adjustment directive: a. Assess the area requirements considering the estimated time that the WPF operator can make the voltage set point adjustment. b. Take alternative action if required (including tripping of generation or load). c. Record the date, time and description of the event along with the WPF operator’s reason for the inability to comply with the voltage adjustment directive in 10 minutes in the System Controller Shift Log as described in OPP 1301. DRAFT 2 Issued for review: 2008-01-28 Page 5 of 14 Transmission OPP 515 South Area Operation 5.3 Removing overloads on facilities in the Southwest Area under N-1 contingency condition If an N-1 contingency results in overload conditions the SC will: 5.4 1. Verify the overload condition. 2. If an alarm for RAS initiation has been received: a. Take no action if the overload has been removed. b. If the overload persists determine additional manual remedial action required as identified in Table 6, then go to step 4. 3. If a RAS initiation alarm has not been received, refer to Table 6 and determine the action required to remove the overload on the affected facility. 4. If the manual remedial action requires the curtailment of generation, then: a. Determine curtailment volume required by applying the curtailment ratio as identified in Table 6 and then determine the reduced generation level (i.e. reduced generation level = current generation level – curtailment volume). b. Direct the operational contact as listed in Table 7 (confidential) to reduce generation down to the reduced generation level. c. If the DTLR is not available, use static rating in calculating the amount of generation curtailment for mitigating 170L (Pincher Creek T396S and Peigan 59S) overload. 5. If the overload persists curtail additional generation until the overload is removed. 6. When the facility that caused the overload returns to service cancel the curtailment directive and/or permit generation to return to normal operation if curtailed by RAS. 7. Record the date, time and description of the event in the System Controller Shift Log as described in OPP 1301. Loss of Magrath WPF RAS If the Magrath WPF RAS is unavailable, including loss of the RAS communication path, as described in Table 6, the SC will: 5.5 1. Receive a ‘Magrath WPF RAS fail’ alarm and/or notification that the RAS is unavailable. 2. Issue a directive to curtail the Magrath WPF to 0 MW in 30 minutes; refer to Table 7 (confidential) for operational contact. 3. If the Magrath WPF fails to curtail, then direct the AltaLink South Transmission Operator to trip the 138 kV breaker (52/T1) at Garden City (226S) if the Magrath WPF fails to curtail. 4. When the Magrath WPF RAS returns to service, cancel the curtailment directive. 5. Record the date, time and description of the event in the System Controller Shift Log as described in OPP 1301. Loss of Summerview – Kettles Hill WPF RAS If a component of the RAS is not available, the SC will: 1. Receive an alarm and/or notification. DRAFT 2 Issued for review: 2008-01-28 Page 6 of 14 Transmission OPP 515 South Area Operation 2. Check with the AltaLink Transmission Operator and/or WPF operators to identify the impact to the integrity of the RAS. 3. If it is so identified and confirmed by AltaLink that the automatic RAS actions to both Summerview WPF and Kettles Hill WPF will not be functioning, then 4. 5. 5.6 a. Issue a directive to curtail the Summerview WPF to 0 MW in 30 minutes. b. Direct the AltaLink South Transmission Operator to trip the 138 kV breaker (138CB1) at Summerview 354S if the Summerview WPF fails to curtail. c. Issue a directive to curtail the Kettles Hill WPF to 0 MW in 30 minutes. d. Direct the AltaLink South Transmission Operator to trip the 138 kV breaker (52S1) at Kettles Hill 383S if the Kettles Hill WPF fails to curtail. If it is so identified and confirmed by AltaLink that only the automatic RAS actions to Summerview WPF will not be functioning while the rest of the RAS remains intact, then a. Issue a directive to curtail the Summerview WPF to 0 MW in 30 minutes; refer to Table 7 (confidential) for operational contact. b. Direct the AltaLink South Transmission Operator to trip the 138 kV breaker (138CB1) at Summerview 354S if the Summerview WPF fails to curtail. If it is so identified and confirmed by AltaLink that only the automatic RAS actions to Kettles Hill WPF will not be functioning while the rest of the RAS remains intact, then a. Issue a directive to curtail the Kettles Hill WPF to 0 MW in 30 minutes; refer to Table 7 (confidential) for operational contact. b. Direct the AltaLink South Transmission Operator to trip the 138 kV breaker (52S1) at Kettles Hill 383S if the Kettles Hill WPF fails to curtail. 6. When the component returns to service, cancel the curtailment directives. 7. Record the date, time and description of the event in the System Controller Shift Log as described in OPP 1301. Removing overload on 786L under normal system condition When 786L is overloaded (it may happen during summer light load and high export conditions), the SC will: 5.7 1. Curtail Summerview WPF with curtailment ratio 4.5 to 1. 2. Direct the AltaLink South Transmission Operator to trip the 138 kV breaker (138CB1) at Summerview (354S) if the Summerview WPF fails to curtail. 3. If overload still persists, curtail Kettles Hill WPF with curtailment ratio 4.5 to 1. 4. Direct the AltaLink South Transmission Operator to trip the 138 kV breaker (52-S1) at Kettles Hill 383S if the Kettles Hill WPF fails to curtail. 5. If overload still persists, curtail Castle River WPF with curtailment ratio 4.5 to 1. Loss of Soderglen WPF RAS If the Soderglen WPF RAS is unavailable or loss of both “A” and ‘B” teleprotection channels, the SC will: DRAFT 2 Issued for review: 2008-01-28 Page 7 of 14 Transmission OPP 515 South Area Operation 1. Issue a directive to curtail the Soderglen WPF to 0 MW in 30 minutes; refer to Table 7 (confidential) for operational contact. 2. Direct the AltaLink South Transmission Operator to trip the 138 kV breaker at Soderglen 243S if the Soderglen WPF fails to curtail. DRAFT 2 Issued for review: 2008-01-28 Page 8 of 14 DRAFT 2 Issued for review: 2008-01-28 185L Shell Waterton T502S Yarrow T995S 164L Drywood T415S 146L 162L Glenwood T229S 225L Spring Coulee T385S 225L Magrath T225S Taylor Hydro Plant Taylor WPF 891L 863L 185L 55 Glenwood Magrath WPF Garden City 226S Irrican Hydro 314S Raymond Reservoir T313S 225L 824L Taber T83S 610L Fincastle T336S Warner T344S Stirling T67S Conrad T135S ENMAX Taber WPF 134S Suncor Chin Chute WPF Hillridge Chin Chute 139S T315S 820L Shell Waterton T379S Kettles Hill 383S Riverbend T618S Lakeview L593S 820L Coaldale T254S 172L L146S L241S 770L 607L Castle River WPF 239S 893L Pincher Creek T396S Soderglen WPF 243S Bowron L674S L111S L 725A Coleman T799S Cowley Ridge WPF 322S 170L 170L 725L N. Lethbridge T370S 72 5L 893AL 180L McBride Lake 240S Ft. Macleod T15S 170L 924L Summerview Oldman River WPF Hydro Summerview A806S 354S 911L Peigan 59S 172L Monarch T492S To Milo Junction 923L To Natal B-1S Lundbreck T513S 53 Ft. Macleod N To E. Stavely T928S To Burdett T368S 6. 786L To Cranbrook To Langdon T102S To Janet T74S Transmission OPP 515 South Area Operation Figures and Tables Figure 1 South area generation facilities 1201L 69 kV Plants 138 kV Hydro 240 kV Thermal 500 kV Wind Existing Page 9 of 14 Transmission OPP 515 South Area Operation Table 1 Generation in South Area Generator Substation Castle River WPF 239S Chin Chute Hydro T315S Cowley Ridge WPF Capability (MW) 39.54 11 322S 40.775 Drywood Power Plant T415S 6 ENMAX Taber WPF C134S 80 Irrican Hydro 314S 7 Kettles Hill WPF 383S 63 Magrath WPF 226S 30 McBride Lake WPF 240S 75.2 Oldman River Hydro A806S 32 Raymond Reservoir T313S 18 Soderglen WPF 243S 70.5 Summerview WPF 354S 68.4 Suncor Chin Chute WPF 139S 30 Taylor Hydro Taylor Hydro Plant 12 Taylor WPF Taylor Hydro Plant 3.4 Table 2 AltaLink Transmission Line Capacity Limits and Alarms1 Alarm Emergency 69 kV & 138 kV Line flow Maximum Duration >100% and <110% 10 minutes 110% 0 minutes Critical Comment Critical limit must not be exceeded. Overload must be removed immediately. 1. As per AltaLink Operating Procedure T-1.1. Table 3 Magrath WPF RAS Following the closure of City of Lethbridge 138kV loop (824L line), the Magrath WPF RAS has been modified accordingly. If either 618S863X is open or both 618S725N and 618S824 are open for 10 seconds or more, a signal will be sent to trip the circuit breaker 52/T1 at I-226S. Breaker Monitoring Point Trigger Status 618S725N AND 618S824 Open Trip high side breaker 52/T1 at Garden City (226S). 618S863X Open Trip high side breaker 52/T1 at Garden City (226S). 225S4 Open Trip 225S15 at Magrath substation 225S DRAFT 2 Issued for review: 2008-01-28 Automatic Remedial Action Page 10 of 14 Transmission OPP 515 South Area Operation Table 4 Summerview – Kettles Hill WPF RAS Monitoring Point At Peigan 170LW (59S – 170BL tap) Runback/Trip Setting (MVA) > 140 % of the static rating: > 100 % of the dynamic rating At Pincher Creek 170LW (T396S – 170AL tap) > 140 % of the static rating: > 100 % of the dynamic rating At Coleman 786L (T799S – BCTC Natal) >139 >185 Summer Winter >111 >148 Summer Winter Automatic Remedial Action • Trip Summerview WPF generators (34.5 kV breakers – 35CB11 and 35CB21). • If overload still persists, trip the 138 kV breaker (52-S1) at Kettles Hill 383S • Run-back Summerview WPF generators until facility loading is within limit, • If overload still persists, run-back Kettles Hill WPF generators until facility loading is within limit. • Trip Summerview WPF generators (34.5 kV breakers – 35CB11 and 35CB21) • If overload still persists, trip the 138 kV breaker (52-S1) at Kettles Hill 383S • Run-back Summerview WPF until facility loading is within limit. • If overload still persists, run-back Kettles Hill WPF generators until facility loading is within limit. • Trip Summerview WPF generators (34.5 kV breakers – 35CB11 and 35CB21). • If overload still persists, trip the 138 kV breaker (52-S1) at Kettles Hill 383S • Run-back Summerview WPF generators until facility loading is within limit, • If overload still persists, run-back Kettles Hill WPF generators until facility loading is within limit. Note: • All monitored points have a 10 second time delay to confirm the overload. • When the loading of the element exceeds the runback setting as specified in Table 4, then a runback signal will be initiated. After initialization of the runback signal, it is expected that the wind generation runback scheme will remove the overload in 60 seconds. If the loading of the element has not yet dropped below 100% of its rating within 90 seconds, then a trip signal will be initiated to trip the WPF. • Whenever the loading of the element exceeds the trip setting as specified in Table 4, then a trip signal will be initiated immediately, and overrides the runback signal. • The maximum continuous rating generated from the DTLR will be limited to 600 A (143 MVA) in the summer and 720 A (172 MVA) in the winter. DRAFT 2 Issued for review: 2008-01-28 Page 11 of 14 Transmission OPP 515 South Area Operation Table 5 Irrican RAS Monitoring Point Trigger Status Automatic Remedial Action Breaker 67S2 and breaker 67S225 Both open Trip Irrican Hydro generation. Breaker 67S820 and breaker 67S225 Both open Trip Irrican Hydro generation. Breaker 254S820 and breaker 67S225 Communication link between 67S and 254S and 67S225 Both Open Trip Irrican Hydro generation. Both the link fails and breaker 67S225 open Trip Irrican Hydro generation. Breaker 67S3 Open Trip Irrican Hydro generation. 67S 19LW feeder protection Operated Trip Irrican Hydro generation. 67S T1 protection Operated Trip Irrican Hydro generation. 67S3 maintenance switch in maintenance mode Operated Trip Irrican Hydro generation. Lost for more than 4 seconds Trip Irrican Hydro generation. Communication link at Irrican Note: A breaker is declared “open” by either the breaker status or the maintenance switch operation. Table 6 Contingency initiated automatic and SC curtailments N-1 Contingency/ RAS Condition Possible Overloaded Facility(s) See Note 911L(59S – 74S) • 170L(59S-15S) • 725L(674S725BL Tap) 5 59S T1 • 170L(59S-15S) • 725L(674S725BL Tap) 5 170L (59S – 15S) • 725L(674S725BL Tap) DRAFT 2 Issued for review: 2008-01-28 SC Action1 1. Curtail Soderglen WPF. 2. If overload still persists, curtail Soderglen WPF to 0 MW. 3. Direct the AltaLink South Transmission Operator to trip the 138 kV breaker at Soderglen 243S if the Soderglen WPF fails to curtail. 1. Curtail Soderglen WPF. 2. If overload still persists, curtail Soderglen WPF to 0 MW. 3. Direct the AltaLink South Transmission Operator to trip the 138 kV breaker at Soderglen 243S if the Soderglen WPF fails to curtail. 1. Curtail Soderglen WPF 2. Direct the AltaLink South Transmission Operator to trip the 138 kV breaker at Soderglen 243S if the Soderglen WPF fails to curtail. Curtailment Ratio2 2.5:1 2.5:1 4:1 Page 12 of 14 Transmission OPP 515 South Area Operation N-1 Contingency/ RAS Condition Possible Overloaded Facility(s) 170L(396S – 239S– 799S) • 170L(383S Tap-59S) 725L(674S– 111S– 618S) • 725L(59S – 243S Tap) • 170L (59S – 15S) See Note 4 725L(59S–674S) • 170L(59S383S Tap) 786L (T799S – B1S) • 170L (T396S – 59S) 4 170L (T396S – 59S) • 786L (799S – Natal) 4 DRAFT 2 Issued for review: 2008-01-28 SC Action1 3. If overload still persists, curtail Summerview WPF 4. If Soderglen curtailment causes 170L (383S – 59S) overloaded, further curtail Summerview WPF 1. Curtail Summerview WPF. 2. Direct the AltaLink South Transmission Operator to trip the 138 kV breaker (138CB1) at Summerview 354S if the Summerview WPF fails to curtail. 1. Curtail Soderglen WPF. 2. Direct the AltaLink South Transmission Operator to trip the 138 kV breaker at Soderglen 243S if the Soderglen WPF fails to curtail. 3. If overload still persists, curtail Summerview WPF. 4. Direct the AltaLink South Transmission Operator to trip the 138 kV breaker (138CB1) at Summerview 354S if the Summerview WPF fails to curtail. 1. Curtail Summerview WPF. 2. Direct the AltaLink South Transmission Operator to trip the 138 kV breaker (138CB1) at Summerview 354S if the Summerview WPF fails to curtail. 1. If overload persists on 170L and is less than 125 MVA Summer / 151 MVA Winter then curtail Summerview WPF. 2. If overload persists still on 170L and is greater than 125 MVA Summer / 151 MVA Winter and the Summerview WPF does not curtail generation, then direct the AltaLink South Transmission Operator to trip the 138 kV breaker (138CB1) at Summerview 354S. 3. If overload still persists, curtail Kettles Hill WPF. 4. Direct the AltaLink South Transmission Operator to trip the 138 kV breaker (52-S1) at Kettles Hill 383S if the Kettles Hill WPF fails to curtail. 1. Curtail Summerview WPF. 2. If Summerview fails to curtail, direct the AltaLink South Transmission operator to trip the 138 kV breaker (138CB1) at Summerview 354S. Curtailment Ratio2 2:1 1.5:1 2:1 2:1 1.5:1 2:1 2:1 Page 13 of 14 Transmission OPP 515 South Area Operation Possible Overloaded Facility(s) N-1 Contingency/ RAS Condition • 225L(67S313S Tap) • 170L(383S Tap-59S) See Note SC Action1 Magrath WPF RAS unavailable n/a 1. Curtail Taylor WPF. 2. Direct the AltaLink South Transmission Operator to trip the 69 kV breaker 225S15 at Magrath (T225S) if the Taylor WPF fails to curtail. 3. If overload persists curtail Irrican generation 4. If overload still persists on 170L (59S – 383S Tap), curtail Summerview WPF. 1. Curtail Taylor WPF. 2. Direct the AltaLink South Transmission Operator to trip the 69 kV breaker 225S15 at Magrath (T225S) if the Taylor WPF fails to curtail. 3. If overload persists curtail Irrican generation 4. If overload still persists on 170L (59S – 383S Tap), curtail Summerview WPF. See Section 5.4 Summerview – Kettles Hill WPF RAS unavailable n/a See Section 5.5 Soderglen WPF RAS unavailable or loss of both “A” and ‘B” teleprotection channels n/a See Section 5.7 863L (618S-226S225S) 225ST1 • 225L(67S313S Tap) • 170L(383S Tap-59S) 3 Curtailment Ratio2 1.5:1 1.5:1 2:1 1.5:1 1.5:1 2:1 n/a n/a Note: 1. The required SC actions aim to enabling the system to withstand the contingency (N-1) as listed in above table. The SC or Operation Coordination Group may take necessary measure(s), if required, to prepare the system to withstand next contingency (N-1-1) in real time. 2. Curtail this amount of generation (MW) for every 1 MVA of overload on the overloaded facility. 3. Magrath WPF RAS will trip Magrath WPF for breaker ‘open’ condition at Riverbend (T618S) as described in Table 3. 4. Summerview – Kettles Hill WPF RAS will operate for Summerview/Kettles Hill WPF if loading on any affected facility is greater than the trigger limits as described in Table 4. 5. Soderglen WPF RAS will operate if loading on any affected facility is greater than the trigger limits as described in Table 8. 6. A SCC Application has been developed for this table. Table 7 Contact Information Confidential View confidential Table 7 DRAFT 2 Issued for review: 2008-01-28 Page 14 of 14 Transmission OPP 515 South Area Operation Table 8 Soderglen RAS Monitoring Point Trigger Status Automatic Remedial Action At Bowron L674S 725LW terminal Winter Setting: >143 MVA (112% of rated capacity) Trip Soderglen WPF Summer Setting: >102 MVA (112% of rated capacity) Trip Soderglen WPF Communication link fails Trip Soderglen WPF* Communication link between Peigan and Soderglen Note: * Soderglen 138 kV breaker will be tripped within 400 ms in case of a communication failure between Peigan and Soderglen 7. Revision History Issued Description 2007-09-27 Supersedes 2007-06-14 2007-06-14 Supersedes 2007-03-15 2007-03-15 Supersedes 2006-09-29 2006-09-29 Supersedes interim OPP effective 2006-08-09 2006-08-09 Approved for interim implementation, supercedes 2006-04-27 2006-04-27 Supersedes revised interim OPP effective 2005-07-27 2005-07-27 Supersedes revised interim OPP effective 2005-06-14 2005-06-14 Supersedes interim OPP effective 2005-06-03 2005-06-03 Supersedes OPP effective 2004-10-14 2004-10-14 Supersedes interim OPP effective 2004-07-30 2004-07-30 Approved for interim implementation, effective 2004-07-30 New issue DRAFT 2 Issued for review: 2008-01-28 Page 15 of 14