Stakeholder Comment and Rationale Form AESO AUTHORITATIVE DOCUMENT PROCESS Stakeholder Consultation Draft
by user
Comments
Transcript
Stakeholder Comment and Rationale Form AESO AUTHORITATIVE DOCUMENT PROCESS Stakeholder Consultation Draft
Stakeholder Comment and Rationale Form AESO AUTHORITATIVE DOCUMENT PROCESS Stakeholder Consultation Draft Date: 2011-12-06 Proposed New ISO Rules Section 502.5 Generating Unit Technical Requirements (“New ISO Rules Section 502.5”) Date of Request for Comment [yyyy/mm/dd]: Period of Consultation [yyyy/mm/dd]: 2011/12/06 2011/12/06 Comments From: TransAlta Corporation Date [yyyy/mm/dd]: February 14, 2012 through 2012/02/14 Contact: Kevin T. Van Koughnett Phone: 403-804-2319 E-mail: [email protected] Listed below is the summary description of changes for the proposed new, removed or amended sections of the ISO Rules. Please refer back to the Letter of Notice under the “Attachments to Letter of Notice” section to view the actual proposed content changes to the ISO Rules. Please place your comments / reasons for position underneath (if any). 1. ISO Definitions (a) New There are no new ISO rules definitions associated with proposed New ISO Rules Section 502.5 Stakeholder Comments and/or Alternate Proposal Comment # 1: Insert Comments / Reason for Position (if any) AESO Replies TransAlta suggests there should be a definition for facilities modification, a term which is used throughout the rule and which has important consequences for the owner of a generating unit. The threshold and circumstances of what is and is not considered a facilities modification needs to be clear. In the wind technical rule 502.1, for example, under subsection 1(3) there is clarity added regarding modifications. Given the importance of a functional specification we also suggest that this term should be defined. We provide further comment regarding these definitions below. We will bold these terms in our responses. Issued for Stakeholder Consultation: 2011-12-06 Page 1 Public Information (b) Removals There are no ISO rules definitions removals associated with proposed New ISO Rules Section 502.5. Comment # 2: Insert Comments / Reason for Position (if any) (c) Amendments There are no amendments to ISO rules definitions associated with proposed New ISO Rules Section 502.5. Comment # 3: Insert Comments / Reason for Position (if any) 2. ISO Rules (a) New The AESO’s existing Generator and Load Interconnection Standard (“Technical Standard”) was adopted in 2006. The Technical Standard has a 5 year term, and therefore needs to be reviewed and amended during the 2011-12 timeframe. However, the AESO is transitioning all of its technical requirements including the Technical Standard into new ISO rules, in accordance with the principles and procedures under the AESO’s Transition of Authoritative Documents (“TOAD”) project. The AESO has further determined that it would be most efficient and practical going forward to split the Technical Standard in to separate new load and generating unit technical ISO rules. The first stage of this initiative is to redraft and relocate the applicable generating unit provisions of the Technical Standard into Proposed New ISO Rules Section 502.5. The AESO is endeavoring to represent legally binding requirements and obligations in one of its three authoritative document domains, those being ISO rules, ISO tariff or the Alberta Reliability Standards. The proposed minimum technical requirements of a legally binding nature for existing, modified and new generating units have been set out in the proposed New ISO Rules Section 502.5. It should be noted that, as provisions have been redrafted and relocated in proposed New ISO Rules Section 502.5, the AESO has not intended any essential changes to the policies currently reflected in the Technical Standard for generating units, with some specific and limited exceptions referred to below. The rationale for each of the subsections of proposed New ISO Rules Section 502.5 is provided below. Issued for Stakeholder Consultation: 2011-12-06 Stakeholder Comments and/or Alternate Proposal Comment # 4: Insert Comments / Reason for Position (if any) We suggest that the title of this Rule be “Generating Unit Connection Technical Requirements” and that the word “Connection” is important in giving context to the Rule. In this sense the word “Connection” replaces “Interconnection” in the 2006 standard title. To fully assess if each of our generating units could meet the requirements of rule 502.5 we need to undertake (or review) engineering studies, testing, and install monitoring for each facility. Such assessments and studies take considerable time and require significant resources, and given these resources it would not be prudent to initiate these activities until the final rule is approved by the AUC. Waiting until rule approval allows an accurate gap assessment to be done focused on compliance and solutions and/or as necessary seeking a variance under subsection 4(2). Solutions for larger older existing generating units are complex, can require extensive outages, and can be costly. It is evident in some areas of the proposed rule that the AESO has allowed grandfathering, exemptions, or variances of existing units until modified. The approach appears to be piecemeal and far from being Page 2 AESO Replies comprehensive in taking into consideration the generating unit condition and capabilities particularly in the case of older units designed decades ago to work within the market structures, i.e. regulated rather than competitive, and operational paradigms of those times. Subsection 1 – Applicability The applicability section of the Technical Standard did not clearly state which market participant subcategories were responsible for meeting the requirements. Subsection 1 clarifies that the requirements apply to legal owners of a generating unit including those in an industrial complex, but excludes wind aggregated generating facilities. Comment # 5: Insert Comments / Reason for Position (if any) The Rule is silent on a minimum applicable generating unit size. It is common practice that a standard have a minimum size for applicability as requirements are not the same for small as for large units. The wind technical rule 502.1, for example, applies to generating units 5 MW or larger. Throughout the proposed rule 502.5 references to various applicable minimum generating unit sizes are used but in other places it is silent. For example, subsection 21 is silent on this and would require a Phasor Measurement Unit on a new 1 MW unit. The same would apply to subsection 22 for sequence of event monitoring. And so on for testing, etc. This is likely unintended and needs to be remedied for clarification. We ask the AESO to consider changes to the proposed rule which would exempt small generating units on the Issued for Stakeholder Consultation: 2011-12-06 Page 3 basis of significant expense and minimum impact on the system in terms of operations or reliability. For these and other requirements in the rule we ask the AESO to provide evidence of the system benefits which justify the inclusion of the requirement including the threshold for invoking the requirement. Given the size of the Alberta system with a peak demand exceeding 10,600 MW, we think an applicability threshold of 20 to 25 MW or more would be appropriate. FERC, for example, distinguishes between large and small using a 20 MW threshold. NERC reliability standards usually have a much higher threshold as their focus is on bulk system reliability. The AESO could either have a separate standard/rule for small generating units or, within this rule, define what is required by unit size in each subsection. We ask the AESO to consider the specific aspects of different unit sizes of generating units, their age, and their condition in deciding applicability. Further, we ask the AESO to provide evidence of the benefits and costs for any advocated approach. As part of this consideration, there should be assessment of multiple unit plants and a minimum applicability size for a unit regardless of the aggregate size of the facility. This assessment should also consider the independence implied in subsection 15. Subsection 2 – Requirements – New Generating Unit Subsection 2 sets out, with clarity, the provisions that apply to a new generating unit. Issued for Stakeholder Consultation: 2011-12-06 Comment # 6: Insert Comments / Reason for Position (if any) Subsection 2(4) dealing with new units is the first mention of “facilities modification” in the proposed rule. It is also indicated in subsection 3(4) for existing units. It is used in numerous other places in the proposed rule. TransAlta suggests that facilities modification be a defined term so that all parties are clear what is and is not included. Page 4 While we appreciate the intent of subsection 2(5) to cover the time period between when a functional specification is approved and when rule 502.5 is effective, we also note the planned effective date per the Letter of Notice is October 1, 2012. An effective date needs to consider the resources of owners and the AESO to assess, develop, and plan any required changes. This in our view also includes ensuring all generating units have a Functional Specification. It may be that significant work has already been done regarding a proposed generating unit and for which a connection application has been made to the AESO but for which a functional specification has not been issued. In the overall permitting of a power plant there are separate applications for the generating units and the connection. It has been typical for the generating unit process to be in advance of the connection process and there are risks the functional specification may come too late in the process for alignment with the generating unit design. We are also concerned that the effective date proposed of approximately six months after approval is far too short for generating units to meet new requirements and should be similar to the approach of NERC for reliability standards where the effective date after approval provides adequate time for the owner to take the necessary steps to comply. Subsection 3 – Requirements – Existing Generating Unit Subsection 3 sets out the provisions that apply to an existing generating unit, including clarifications as to what subsections of proposed New ISO Rules Section 502.5 are not applicable. Comment # 7: Insert Comments / Reason for Position (if any) See comment above regarding facilities modifications. See comments below regarding functional specifications. Issued for Stakeholder Consultation: 2011-12-06 Page 5 Subsection 4 – Functional Specification Consistent with current practice, subsection 4 enables the AESO to approve of and issue a functional specification for a generating unit project, which will set out technical details with regard to design, construction and operation of the generating unit connection project and any associated transmission system connection facilities. Consistent with technical requirements under other ISO rules, Subsection 4(2) allows for variances in a functional specification under certain conditions. Comment # 8: Insert Comments / Reason for Position (if any) There is no distinction made in subsection 4 between a new and an existing generating unit. For a new unit there would be a Functional Specification as part of the connection process whereas for most existing units there would not be a Functional Specification. Does the AESO plan to provide Functional Specifications for existing units that do not have a Functional Specification? If so, please outline a process and timeline. TransAlta believes the functional specification is an important and fundamental component of the proposed rule. Without the existence of a Functional Specification the variance and flexibility provided by subsection 4(2) is not available as the subsection states that the Functional Specification itself may contain material variances from section 502.5. No other mechanism is provided for the existing generating facility owner to avail themselves of the same provisions. The Functional Specification for a generating unit is an important document and it is referenced in the following subsections apart from subsection 4: 2(5), 3(1), 6(2), 7(1), 7(3), 8(6), 8(7), 11(4), 11(9), 14(1), 16(2), 16(3), 17(3), 18(1), 18(4), 21(1) and 21(3). Interpretation of rule 502.5 is problematic without a Functional Specification for each generating unit and, as such, we are concerned the proposed rule 502.5 will be technically deficient if this is not addressed. Given the importance of the Functional Specification in interpretation of this rule the AESO should make it a defined term as noted above. As well, the AESO needs to ensure there is a functional specification for all existing units. Issued for Stakeholder Consultation: 2011-12-06 Page 6 Subsection 5 – Successor to Prior Requirements Comment # 9: Insert Comments / Reason for Position (if any) Subsection 5 clarifies that proposed New ISO Rules Section 502.5 succeed the generating facilities provisions of the Technical Standard. Subsection 6 – Operating Voltage Requirements Subsection 6 requires the market participant to clearly state the voltages to which the generating unit will be designed at both the point of connection and the generator terminals. In Alberta, the voltage levels may vary considerably from the nominal voltage, therefore, having the legal owner clearly stating the values to be voltages at the point of connection and the generating unit terminals allows the AESO to fairly ensure the compliance of all legal owners with regard to: (a) The voltage ride-through requirements; (b) Voltage regulation; and (c) The reactive power requirements of the generating unit. This subsection also makes the legal owner aware of the voltage range at that facility so that they may properly specify, design and purchase the appropriate equipment. Comment # 10: Insert Comments / Reason for Position (if any) TransAlta suggests that the wording “the connection of” be added in subsection 6(1) so that it would read “proposes to be used for the connection of the generating unit:” TransAlta suggests in subsection 6(2) that the wording “in subsection 6(1)(a)” be added so that it would read “approves of the operating voltage value in subsection 6(1)(a) proposed by the legal owner,” The AESO should approve the voltage in subsection 6(1)(a), i.e. the transmission voltage, but should not approve the voltage in subsection 6(1)(b) which is the voltage at the generator terminals. We can understand why the AESO would need to approve the transmission voltage at the point of connection in 6(1)(a) but not the generator voltage. We have no issue with provision of the information in 6(1)(b) to the AESO but disagree that it should be approved by the AESO. The wording throughout subsection 6 and the rule should reflect this distinction between approval and information. We suggest that subsection 6(5) be sequenced in order of the subsections within the rule for clarity of presentation. Issued for Stakeholder Consultation: 2011-12-06 Page 7 Subsection 7 – Maximum Authorized Real Power Subsection 7 requires the participant to submit in writing the maximum value that the generating unit can ever be operated at, under ideal circumstances while meeting other requirements of proposed New ISO Rules Section 502.5. Many generating units can operate above nameplate values under the proper conditions, so to properly study the behaviour of the generating units in respect to the transmission system, this maximum value needs to be clearly stated. This value is also required to properly design the transmission system. Comment # 11: Insert Comments / Reason for Position (if any) Subsection 7(4) should be worded such that “A generating unit must not be operated in excess of its maximum authorized real power unless directed by the ISO.” We have added “unless directed by the ISO” because it is foreseeable in emergency conditions that the AESO may want every MW possible and subsection 7(4) as presently proposed would preclude the generator from providing such MWs even though they may be capable of doing so. Such time periods are short in duration and are within the stable operating capabilities of a generating unit. MARP is defined in context of the proposed power factor range, i.e. the reactive power range. If the required power factor range changes, as we propose, then MARP will change. As elaborated below we accept the AESO view as expressed for PPA units that there is a normal operating condition power factor range which is a subset of the overall abnormal/emergency operating range. We assert that MARP should be defined on the normal operating condition range for all generating units. MARP, as defined, also determines the Maximum Capability of the generating unit. Maximum Capability is a market term which is the maximum amount of MW a generating unit can and must offer into the power pool. In our view there is a clear distinction between normal and abnormal operating conditions. Further, the AESO has construed this rule as specifying the “minimum requirements”. In our view MARP should be defined by normal operating conditions and these are the minimum requirements. The maximum requirements are under abnormal operating conditions. Issued for Stakeholder Consultation: 2011-12-06 Page 8 MARP and MC as so defined have wide impacts on what capacity is available in the energy market. Is it FEOC to define MARP as proposed or is it inefficient, reduces competitiveness, and unfair? If reactive power can be provided by other than generators does this not suggest a market for this ancillary service? Do reactive power services provided by generators meet the need for reactive power in the most fair, efficient and effective manner, or are there better ways to meet the need? Subsection 8 – Reactive Power Requirements for All Generating Units Subsections 8(4) through 8(6) allow the participant to apply for a reduction in the reactive power/power factor requirement in the under excited region of the reactive capability curve. The AESO is aware of the concerns that depending on the specific location of the generator unit, operating near the bottom of the D-curve may result in the unit becoming unstable. In the AESO’s opinion, it would be appropriate to reduce the reactive power requirement, if provided with technical back up to this concern. Comment # 12: Insert Comments / Reason for Position (if any) In subsection 8(1) we suggest striking the phrase “and approved of by the ISO under subsection 6(2)”. As above, we do not think it is appropriate for the AESO to approve generator terminal voltages. A generator capability curve separates regions of allowed operation inside the curve from regions of forbidden operation outside the curve. The curve is provided at rated generator terminal voltage. It is important to note that as the terminal voltage changes within the generator continuous voltage rating of +/- 5% that the curve shifts affecting the allowable operation regions and reactive power capabilities. We disagree that the appropriate power factor range for normal operating conditions is 0.90 producing and 0.95 absorbing vars at the generator terminals at rated voltage. This is notwithstanding that this range was included in the 2006 standard. Subsequent to the 2006 standard there have been a series of concerns raised by generator owners about the capability of existing generating units to meet these requirements. While some issues have been addressed for PPA units, in our view the matter of reactive power remains unresolved. We think that the AESO should undertake to provide studies which would justify appropriate reactive power requirements for generators consistent with Alberta’s Issued for Stakeholder Consultation: 2011-12-06 Page 9 market design, various system operating conditions, and generator operating practices based on machine condition and limiter margins. The AESO has also ascribed a different power factor range for normal operating conditions in this and other documents. The AESO has also ascribed an abnormal or emergency power factor range as being 0.90 producing and 0.95 absorbing vars at the generator terminals. The distinction between normal and abnormal is also connected to the descriptions of long term and short term, and static and dynamic. These distinctions are important and require careful consideration in the development of this rule. For example, in the wind technical rule 502.1, the reactive power range is 0.95 pf producing vars and 0.985 pf absorbing vars at the generator terminals based on dynamic reactive power. This smaller range is, as such, implied as being the most important to the AESO. This suggests a smaller dynamic range should be applicable for all generating units rather than the 0.90 producing and 0.95 absorbing vars at the generator terminals. We also note that for Purchase Power Arrangement generating units a distinction is made between normal and abnormal/emergency operating conditions and the reactive power applicable to different operating conditions. See additional comments under subsection 9. In subsection 8(3) the reactive power capability should be stated as subject to the limiter margins and the machine condition. For clarity, a limiter is not usually set at the value where the reactive power requirement intersects the capability curve but at a margin less than the capability curve value. As such the reactive power Issued for Stakeholder Consultation: 2011-12-06 Page 10 range is usually less than that shown on the capability curve and the available power factor range is narrowed. This is especially so for UEL settings. It must also be noted that capability curves are stated at 1.0 pu terminal voltage and reactive capability shifts as the voltage changes between +/- 5% of the terminal voltage. In many ways we think the approach taken for PPA units is preferable because it was based on the actual capabilities of the various units resulting from the technical review of the Independent Assessment Team. It is reasonable to expect generator operation within tested limits and considering the machine condition. We disagree with the characterization of the requirements as being “the minimum requirements” in subsection 8(3). TransAlta believes that all generating units should provide real power and reactive power recognizing the distinction made between “normal operating conditions” and “abnormal or emergency conditions”. We view the requirements of subsection 8(3) as being for abnormal or emergency conditions and not for normal operating conditions. We suggest that normal operating conditions define the minimum requirements. The “minimum gross real power” in subsection 8(3) is vague in that it states “without any additional wear and tear beyond normal operation.” Who is to decide what the “minimum gross real power” is for a generating unit? The purpose in including the phrase regarding “wear and tear” requires clarification. This does not appear to be language appropriate to a rule but to an information document. In subsection 8(4) the conditions for exception appear to be only for “stability concerns”. The AESO also needs to allow exceptions based on generator condition, core end heating, and appropriate limiter margins for existing units. This must be focused not only on defining normal Issued for Stakeholder Consultation: 2011-12-06 Page 11 operating conditions for each unit but the expectations under abnormal and emergency conditions, and the duration of such abnormal conditions. Accommodation for different types of generation and the age/condition of units needs to be carefully considered. We note that subsection 8(7) goes beyond what is specified in the wind technical rule 502.1 in that it makes no distinction between dynamic and static external reactive power and requires all external resources to be dynamic. Further, the dynamic reactive power for wind farms includes consideration of the one second overload capability of the dynamic var equipment. In essence this defines “dynamic” as being equal to or less than one second. This dynamic range, as noted above, is also smaller being 0.95 pf producing vars and 0.985 pf absorbing vars at the generator terminals. When accommodations are provided for one type of generation then that accommodation should also be available to other types of generation. TransAlta disagrees with subsection 8(7). A generating unit can produce real power and reactive power, and we assert that they are two separate products. Reactive power can be provided by other than generating units, e.g. capacitor banks, Static Var Compensators, or series compensation. It can be located in many places on the power system. We ask if the AESO has considered procuring reactive power through market mechanisms rather than the approach of requiring generators to expend significant resources to provide this service to the system without compensation. Different types of generating units have differing abilities to provide reactive power. This is acknowledged by the AESO in the proposed subsection 8(7) by noting the use of external resources. When external resources are required then this recognizes the limits of the capabilities of the generating unit. The conclusion of the AESO is that the generator owner needs to augment the Issued for Stakeholder Consultation: 2011-12-06 Page 12 capabilities of the generator and that this is FEOC. In our view this conclusion is wrong. Our assertion is that the market should be invoked to provide the most economic response. In an energy-only market, as in Alberta, generators do not receive capacity payments and in other markets which specify a power–factor deadband without compensation, it is done in the context of such generators receiving a capacity payment for providing generation capability in those markets. In Alberta, apart from ancillary services, the only compensation is for the provision of real power. There is no compensation for reactive power provided by generators. A transmission facility owner that adds equipment such as capacitors or a SVC to provide reactive power is compensated. This is discriminatory. Clearly the AESO views reactive power as important and valuable. However, the AESO extracts this valuable service from generators without compensation. The points above, taken together, suggest that reactive power is a separate product and producers of reactive power should be compensated for provision of reactive power. We do not presuppose any particular methodology for compensation for reactive power and suggest that the AESO begin consultation on market mechanisms to procure this valuable service. In addition to the FERC report noted below we refer the AESO to the report “Reactive Power As An identifiable Ancillary Service” prepared for the Transmission Administrator of Alberta in March 2003 by Laurits R Christian Associates. It is punitive to impose additional reactive power requirements on older generating units where external resources would have to be installed. External reactive power resources would only be used in abnormal or Issued for Stakeholder Consultation: 2011-12-06 Page 13 emergency operating conditions and these by definition are low probability events. As such external equipment could be put in place but unused for the vast majority of time. The generation facility owner is forced to invest in equipment which results in no additional revenue but increased costs in a market structure that does not provide any mechanism for recouping these costs through market prices or through the tariff. It is TransAlta’s view that the Maximum Capability should be defined for normal conditions and with a normal power factor range that is much smaller than that proposed in this rule. This would allow the generating units to more economically provide real power through increased Maximum Capability for the vast majority of its operating hours in any year. In abnormal or emergency conditions the real power output could be reduced so as to provide a wider range of reactive power as needed. The proposed power factor range is inefficient. We would also expect that the above approach would increase the competitiveness of generation and through competitive forces have a positive impact on electricity prices. The AESO also needs to bear in mind that the limitations on reactive power supply occur when the generator is producing at its maximum real power output. In a competitive market a specific generator at a specific location may or may not be dispatched and if dispatched may not be at its maximum real power output. This to a generator makes the last increment of capacity highly valuable and the reactive power requirement eliminates and precludes dispatch of available real power capacity given the constrained Maximum Capability prescribed by the AESO. Issued for Stakeholder Consultation: 2011-12-06 Page 14 Subsection 9 – Additional Reactive Power Requirements for a Generating Unit with a Power Purchase Arrangement Comment # 13: Insert Comments / Reason for Position (if any) This section requires the applicable participant to meet certain requirement in regards to reactive power obligations under normal and abnormal system conditions. Subsection 9(3) requires the hydro generating units subject to PPAs to meet the requirements of subsection 8. From a preliminary review of TransAlta’s hydro units we are not in compliance at this time with the requirements as proposed. These units were never intended to operate as described and their design does not allow such operation. Extensive upgrades to the generating units would be required to comply with this requirement and/or significant reductions in the Maximum Capability ratings of the units. Most of this section covers policies already in place by the AESO, however for clarity, these requirements have been incorporated into proposed New ISO Rules Section 502.5 to allow participants to find all requirements to design, build, maintain and/or modify facilities under dedicated ISO rules. For background information please refer to the document Application Guideline Generator Interconnection Requirements – Reactive Power available at: http://www.aeso.ca/downloads/AESO_PPA_Reactive_Power_Guidelines.pdf Of particular note, subsection 9(10) specifies the requirements that will be applicable to generating units that are currently the subject of a power purchase arrangement once that power purchase arrangement ends. In subsection 9(5) what are described as “abnormal or system emergency conditions” needs to be further elaborated, for example, in delineating how long generating units need to operate outside of normal conditions. Based on a preliminary review of our thermal plants, TransAlta has concerns with several of our generating units due to core end heating and stable rotor turn faults which limit our capability to comply with the reactive power requirements. The older the unit the more this is a concern. Subsection 9(7) appears to not consider these additional concerns and is only focused on stability. The wording in 9(8) and 9(9) is unclear as to what reactive power requirements apply to the increment which is the excess above existing MARP. The wording should be clear as to what the MW quantity is and what the required reactive power is related to that MW quantity. There should be a clear statement that the PPA committed capacity plus 2% is subject to 9(4) and any excess above this amount is subject to 8(3) for reactive power. The reactive power requirements for the generating unit should then be detailed for the overall modified unit. It is unclear as to what is required at Issued for Stakeholder Consultation: 2011-12-06 Page 15 various levels of output and under what operating conditions. The AESO is attempting to incorporate the guidelines from the following document into this rule: http://www.aeso.ca/downloads/AESO_PPA_Reactive_P ower_Guidelines.pdf. The following is extracted from it: “The reactive power capability and reactive margins provided by synchronous generators are critical to maintaining reliable and efficient operation of the Alberta Interconnected Electric System (AIES) and must be adequate for normal operation as well as fault and post-contingency operating conditions.” (emphasis added) We do not think the proposed rule adequately includes some of the aspects of this guideline nor provides adequate clarity. It is interesting that this AESO document references the following FERC report on reactive power: http://www.ferc.gov/EventCalendar/Files/200503101444 30-02-04-05-reactive-power.pdf. The FERC report deals extensively with compensation for reactive power. TransAlta objects to subsection 9(10) and we suggest it be deleted. The subsection contemplates an event eight years in the future which is longer than the normal five year update/review cycle for rules and standards. In the intervening time or at the next review the requirements in the rule referred to in subsection 8 may have been changed. Our suggestions in this consultation would, for example, substantially change subsections 8 and 9. While it may be acceptable that the AESO may require compliance of a generating unit if the unit is modified in the future, it is not acceptable to tie such compliance in a technical rule to a future contractual event. Reactive power is an ancillary service. The fundamental rationale for requiring reactive power is to ensure the safe and reliable operation of the transmission system by ensuring system voltages are stable. If reactive Issued for Stakeholder Consultation: 2011-12-06 Page 16 power is required for reliability then surely the need is now and having an event eight years in the future trigger a requirement means you don’t need it now and you don’t need it for reliability. If it is needed now for reliability then the requirement should be now and the need for, the costs of provision, and how best to procure this ancillary service have to be fully considered. TransAlta believes that all generating units should provide real power and reactive power recognizing the distinction made between “normal operating conditions” and “abnormal or emergency conditions”. Further, the definition of MARP as in subsection 7 seeks to limit the maximum output of a generator at all times based on reactive power requirements for “abnormal or emergency conditions”, i.e. 0.90 pf producing vars and 0.95 pf absorbing vars. It is inappropriate to limit a generating unit all the time when extreme operating conditions are only for short durations during those conditions. It is inefficient and uneconomic to reduce potential production in all hours when the reduction is only needed in very few hours. TransAlta proposes that all generating units (whether PPA or not) have real power and reactive power requirements specified for “normal operating conditions” and “abnormal or emergency conditions”. Because there is clearly a difference between such operating conditions and that a generator could produce more real power under normal conditions the AESO is putting the generator in the position of withholding power by understating its Maximum Capability under normal operating conditions. We believe that Maximum Capability should be specified under “normal operating conditions” in keeping with FEOC. The withholding of real power subverts FEOC and confiscates real power capacity paid for by investors. Clearly a generating unit can produce both real power Issued for Stakeholder Consultation: 2011-12-06 Page 17 and reactive power, and we assert they are two separate products. Reactive power is a separate product and producers of reactive power should be compensated for provision of reactive power. It is discriminatory to generators to preclude them from producing real power for which they are compensated so that they may provide reactive power for which they are not compensated. Reactive power is an ancillary service and should not be procured by the AESO without compensation as a condition of connection to the system. Subsection 10 – Voltage Ride-Through Requirements All generating unit must have the capability to support the transmission system during system disturbances. Therefore, each generating unit must have some capability for voltage ride through. The basic approach to the requirements for existing generating units has been carried over from the existing Technical. Subsection 10 allows new generating units to be able to ride through system disturbances that result in voltages as low as 0% and as high 120% for specified periods of time. This requirement has been amended to align with the direction that the industry is taking for new generating units. Please refer to FERC orders 661 and 693. Comment # 14: Insert Comments / Reason for Position (if any) The wording with subsection 10 generally refers to either existing or new generating units but does not refer to a modified generating unit. However, subsection 10(1) makes no distinction between existing and new generating units. As elaborated below this distinction should be made and/or subsection 10(1) should be reduced to +/- 5% for all units. TransAlta objects to subsection 10(1) which requires continuous operation at +/-10% of the operating voltage level specified in subsection 6(1)(a). Normal generator operation is for +/- 5% continuous operating voltage around that specified in 6(1)(b). Continuous operation is different than transient periods where voltage excursions may exceed the continuous operating voltage for short periods of time. We request that proposed subsection 10(1) be changed to reflect a +/5% continuous requirement. The +/-10% continuous requirement is not highlighted as a new requirement in the Letter of Notice and as such the proposed rule should be changed to reflect the 2006 Standard. This is the context of the existing requirement in Issued for Stakeholder Consultation: 2011-12-06 Page 18 subsections 3.1 and 3.4 of the 2006 standard. Subsection 3.1 states “The combination of the generator and transformer capabilities shall allow for a total operating voltage range of +/- 10%.” and “The voltage set point must be adjustable by the generating unit operator and dispatchable from the AESO System Controller within +/-5% of the nominal generator interface voltage.” The intention is that the +/-5% range of the generating unit in combination with off-load transformer taps of +/- 5% would meet the overall +/10% range in subsection 3.1 as noted above. Subsection 10 must be read in conjunction with subsections 11 and 14 as the clear intent of subsection 11 is +/- 5% AVR and subsection 14 with +/- 5% transformer taps. Subsection 3.4 of the 2006 standard states “generating units shall not trip for system voltage excursions within 0.9 and 1.1 per unit.” There is a clear distinction between “continuous” and “excursions”. Existing generating units were designed to operate consistent with the 2006 or earlier standards. A review of our existing generating units identified we could not meet the +/-10% proposed continuous voltage requirement in subsection 10(1) of rule 502.5. The requirement could be met if every unit transformer was replaced with a new transformer which utilized an appropriate on-load tapchanger. On-load tapchangers would be unusual for generator transformers given the high currents and reliability concerns. Replacement of such transformers, if so directed, would also need to be coordinated with the PPA holders and be consistent with the change in law provisions of the PPAs to provide cost recovery. Non-PPA generating units would have no such mechanism for cost recovery. The costs are significant and this requirement needs to be carefully considered. For new generators the generator design would need to include the +/- 10% requirement which could be met but with at increased cost. Issued for Stakeholder Consultation: 2011-12-06 Page 19 In subsections 10(3), 10(4) and 10(5) the word disturbance should be bolded as it is a defined term in the Glossary. In 10(3)(b) the first “for” should likely be “from”. See also a further comment below regarding a ride through chart for existing units. We suggest in 10(3) that the normal and delayed clearing times be as specified in the functional specification for the generating unit. We note that such times are “specific to the location” and yet the rule does not indicate how and when such clearing times will be provided to the owner. Subsection 10 must be consistent with Alberta TPL reliability standards as regards clearing times and expectations for ride through beyond such clearing times suggests a possible misalignment between requirements. We suggest the AESO review for consistency. Subsections 10(3) and 10(4) apply to existing units whereas subsection 10(5) applies to new units. Subsection 10(4) deals with auxiliary equipment connected at the generator terminal voltage which may cease working and cause the unit to go off line. We wonder why this does not apply to new units. Auxiliary equipment is also dealt with in subsection 15(2) and we would suggest consolidation of the requirements for clarity. The simplest solution would be to delete 10(4) and leave 15(2) as is or move the requirements to 15(2). The distinctions between existing (10(3) and 10(4)) and new (10(5)) units is confusing and while appendix 3 shows requirements for new units there is no Appendix for existing units. We suggest an appendix be added for existing units. Issued for Stakeholder Consultation: 2011-12-06 Page 20 We are confused as to the distinction between 10(3)(b) and 10(4) where the various requirements are 40 cycles or 666 ms and 625 ms post disturbance. Why is it not sufficient to state the requirements for normal and delayed clearing times as in 10(3)(a) which appears similar to what is shown in Appendix 3. If the fault is not cleared by these clearing times then why should a generating unit be required to ride through longer than such clearing times? The times stated in 10(3)(b) and 10(4) appear to be more onerous than those shown in Appendix 3. Why would this requirement be made more onerous for existing units than for new units at the 15% and 20% voltage levels? What are the criteria and principles used by the AESO to propose different requirements? Appendix 3 related to subsection 10(5) is essentially the same as the proposed NERC PRC-024-1 ride through standard with the exception that Appendix 3 shows a +/10% continuous voltage range whereas NERC shows a +/- 5% range. The proposed NERC standard is still in the development process, has not been approved by NERC and has not proceeded to the FERC approval process. It is notable that the proposed implementation of the NERC standard after approval is up to four years after approval. The AESO’s proposed implementation is within six months of approval for rule 502.5. The NERC standard may not be approved by NERC or may not be approved for a considerable time and so if subsection 10(5) was approved in Alberta it may not be aligned with and may exceed North American requirements. Our understanding is that it is not the intent of the AESO to impose more onerous reliability standards in Alberta than approved by NERC. If the AESO intends to proceed as proposed then our request is for an explanation of the alternatives and consideration of the benefits and costs to the system. Issued for Stakeholder Consultation: 2011-12-06 Page 21 Subsection 11 – Automatic Voltage Regulator Subsection 11 sets out the requirements for the automatic voltage regulator and the basic approach has been carried over from the existing Technical Standard. Comment # 15: Insert Comments / Reason for Position (if any) Subsection 11(6) is unclear. A distinction is being made regarding the point of control but we are unsure what is intended. Subsection 11(8) is unclear. A distinction is being made regarding the point of control but we are unsure what is intended. Subsection 11(9) is unclear. A distinction is being made regarding multiple units and multiple AVRs but we are unsure what is intended and what concern is being addressed. Subsection 12 – Frequency and Speed Governing Requirements Subsection 12 sets out the requirements for the governor systems and the basic approach has been carried over from the existing Technical Standard, with the one exception noted below. Subsection 12(4) contains the following: “If the frequency of the generating unit while connected to the transmission system remains greater than sixty one point seven (61.7) Hz or less than fiftyseven (57) Hz for more than ten (10) minutes, then the generating unit must be immediately removed from service.” Comment # 16: Insert Comments / Reason for Position (if any) There is confusion between Appendix 4 and subsection 12(3). Is the intent that a unit may trip immediately if the frequency range of 57 HZ to 61.7 Hz is exceeded (under-frequency or over-frequency) but is allowed to not trip for up to 10 minutes? Please clarify and explain the rationale for the 10 minutes. Normal practice would be for an instantaneous trip < 57 Hz and > 61.7 Hz. The AESO has discussed this requirement in work group sessions with generating unit owners and a consensus was reached that this is appropriate to include this in proposed New ISO Rules Section 502.5. It was, however, recommended that the AESO seek broader input in particular from distribution facility owners, industrial system owners, etc. Subsection 13 – Power System Stabilizer Comment # 17: Insert Comments / Reason for Position (if any) Subsection 13 sets out the requirements to install power system stabilizers and has been amended to add requirements that had previously existed in WECC policies, which the AESO has currently been enforcing. Issued for Stakeholder Consultation: 2011-12-06 Page 22 Subsection 14 – Transmission System Step-Up Transformer Subsection 14 sets out the requirements for the step-up transformer and the basic approach has been carried over from the existing Technical Standard. Comment # 18: Insert Comments / Reason for Position (if any) We take exception to the wording in 14(1) and suggest that the phrase “and reactive power” be deleted. Reactive power requirements are measured at the generator terminals at the voltage as defined in 6(1)(b). The transformer steps up the subsection 6(1)(b) voltage to the subsection 6(1)(a) voltage. The transformer is beyond the measurement point for reactive power. While we appreciate that 14(4) effectively grandfathers existing transformers except if replaced this can be problematic and should cover existing spare transformers or spare transformers that may be on order. Recently when the transformer at Sundance 6 failed we used the spare transformer and it did not exactly match the transformer it replaced. Allowances must be made for use of spares which are designed to be used for various generating units. Transformer size has implications in determining Maximum Capability and where the transformer size should not limit MC. Thermal rating of transformers and operational practices are the responsibility of the owner. It appears that the AESO is inserting itself into considerations of generating unit reliability as well as operational risks assumed by the generating unit owner. Transformers can be loaded consistent with dynamic ratings based on guidelines, loading history, test results and ambient temperatures. It is not appropriate for the AESO to specify the details of the transformers for a generating unit beyond that which is necessary to deal with the aspects of how it Issued for Stakeholder Consultation: 2011-12-06 Page 23 connects to the transmission system, i.e. we do not take issue with 14(3)(a) through (c). We note that a TFO can decide the ratings, including overload ratings, of their facilities including, for example, lines and transformers. Yet, here, the AESO is attempting to specify the ratings and operations of generator transformers. Taken further, it would not be appropriate, for example, for the AESO to specify whether the generating facility owner uses one or two transformers in their substation or to specify the form of cooling for transformers. The generating facility owner has every incentive to design and operate their transformers considering risks, reliability and economics. Section 15 – Auxiliary Systems Subsection 15 sets out the requirements for the critical auxiliary system to meet minimum standards so that multiple units will not go off line for single point of failure and that these auxiliaries must be considered when studying the voltage ride capability of the facility. The AESO has experienced issues with facilities where the generating unit may have been able to ride through disturbances but the critical auxiliary system caused the generating unit to trip or go offline. As well, Alberta Reliability Standard TPL-002-AB-0 System Performance Following Loss of a Single BES Element does not allow for cascading for the loss of a single bulk electric system element. Comment # 19: Insert Comments / Reason for Position (if any) In addition, see comments above under subsection 10. The question in subsection 15(1) is essentially to identify potential common mode failures for multiple unit power plants. A literal interpretation of “independent” would mean no common or shared equipment and systems. Some of our multiple unit generating plants have common systems and as such each generating unit is not independent. Further, it is typical for multiple unit power plants to have common station service, for example. We are unable to determine if station service itself as supplied by a separate transmission connection is independent of events beyond the point of connection of the generating transformer. It would be helpful if “auxiliary systems” and “independent” were defined so that we would know what Issued for Stakeholder Consultation: 2011-12-06 Page 24 is and what is not included and intended. While we appreciate that in subsection 15(1) it says “for new or modified existing generating unit”, a modification may not be to any of the common systems. This effectively says that if you touch the generating unit it must meet all the requirements. This is not appropriate. For example, if you changed the transformer you would have to remediate all other aspects of the generating unit to comply. We would suggest wording similar to that found in subsection 22(3) which says if you modify that particular piece of equipment then it must be brought up to compliance. Subsection 16 – Generating Unit Disconnection and Interrupting Devices Subsection 16 sets out the requirements for the generating unit breakers and the basic approach has been carried over from the existing Technical Standard. Subsection 17 – Isolating Devices Subsection 17 sets out the requirements for the generating unit disconnect switch(es) and the basic approach has been carried over from the existing Technical Standard. Subsection 18 – Power Quality Subsections 18(6) and (7) amends and clarifies the requirements for generating units to not introduce excessive voltage unbalances on to the transmission system and how they are calculated. The previous requirement in the existing Technical Standard was to related voltage unbalance at distribution voltages. This new requirement is more appropriate for transmission systems. Comment # 20: Insert Comments / Reason for Position (if any) Subsection 16 should be applicable to new units. Again the subsection is heavily referenced to having a functional specification for the generating unit. For example, expected fault currents are provided in the functional specification which informs equipment selection for a new plant. Comment # 21: Insert Comments / Reason for Position (if any) Similar comments as in subsection 16. Comment # 22: Insert Comments / Reason for Position (if any) The applicable standards are referenced as to that version in effect at the time a functional specification for the generating unit is approved. Again, a functional specification for each unit is needed to ensure clarity of which version of standards apply.. Why does table 1 refer to <= 25 kV when this rule is for Issued for Stakeholder Consultation: 2011-12-06 Page 25 generating units connected to the transmission system? Subsection 19 – Grounding Comment # 23: Insert Comments / Reason for Position (if any) Subsection 19 sets out the requirements for the generating unit grounding and the basic approach has been carried over from the existing Technical Standard. Subsection 20 – Lightning and Other Surge Protection Comment # 24: Insert Comments / Reason for Position (if any) Subsection 20 sets out the requirements for the generating unit surge protection and the basic approach has been carried over from the existing Technical Standard. Subsection 21 – Synchrophasor Measurement System Subsection 21 requires new or existing units with an upgraded protection system to install a synchrophasor measurement system. The application of synchrophasor measurement systems on generating units will allow the AESO to better analyze the response of the generating units to system disturbances, which assist the AESO in developing mitigating requirements for the reliability of the transmission system. It will also allow the AESO to better monitor compliance to the ISO rules and requirements. The generating unit owners and operators will also be able to use this data to analyze the behaviour of the generating unit for the model revalidation requirements and determine if the generating unit is operating as designed. Issued for Stakeholder Consultation: 2011-12-06 Comment # 25: Insert Comments / Reason for Position (if any) It is unclear whether a PMU is required to be added for an existing unit which is uprated by a small amount. This needs to be clarified in a definition of what a facilities modification is and is not. Subsections 21(3)(b) and 21(4) refer to “records”. We suggest for clarity that subsection 21(2) be modified to replace the word “made” with “recorded” so that it is understood what “records” are referred in these subsections. Page 26 Subsection 22 – Internal Sequence of Event Monitoring Subsection 22 adds additional requirements regarding what must be monitored within the generating unit. The additional requirements only apply to new or modified generating units. In the AESO’s opinion, in order to properly analyze the root cause of some system disturbances, greater detail is required from generating units in regards to their behaviour during these disturbances. Subsection 23 – Provision of Data and Modeling Information Subsection 23 deals with the provision of data for both new and modified generating units. This section was added so that the AESO can ensure it has the information required to properly model the behaviour of the generating unit in relation to the transmission, and to confirm that the generating unit is in compliance with sections of proposed New ISO Rules Section 502.5. Comment # 26: Insert Comments / Reason for Position (if any) Subsection 22(3) as worded is applicable to only existing units that have SOE equipment already installed. The subsection is silent on the situation where an existing unit does not have SOE equipment. Subsection 22 does not specify how long SOE records have to be retained nor what the process may be for information requests related to such SOE records. Comment # 27: Insert Comments / Reason for Position (if any) Subsections 23(4) and 23(5) require reports that demonstrate a generating unit can meet the requirements of subsection 10. It would be helpful if they AESO were to convey what an acceptable methodology would be and what the contents of such a report should contain. There is a typo in subsection 23(5) which refers to subsection 9 and it should be subsection 10. Subsection 24 – Testing Intervals Subsection 24 sets out requirements to provide a model validation or reactive power verification report in terms of both format and timing. Comment # 28: Insert Comments / Reason for Position (if any) We suggest that in subsection 24(2) that this be 90 business days. We note 24(9) refers to 60 business days. Where timelines are used in the rule then the approach should be consistent and we prefer business days. Subsection 24(4)(e) is vague. Any modification is likely to change the behaviour of a generating unit. We suggest this be deleted. Subsection 25 – Reporting Issued for Stakeholder Consultation: 2011-12-06 Comment # 29: Insert Comments / Reason for Position (if any) Page 27 Subsection 25 sets out requirements to provide a model validation or reactive power verification report in terms of both format and timing. This subsection was added to clarify the reporting requirements to the market participants. Subsection 26 – Baseline Testing Comment # 30: Insert Comments / Reason for Position (if any) Subsection 26 sets out the requirements for the generating unit baseline testing and the basic approach has been carried over from the existing Technical Standard. Subsection 27 – Reactive Power Verification and Re-verification Testing Subsection 27 sets out the requirements to test that the reactive power requirements of proposed New ISO Rules Section 502.5 have been met. Reactive power verification has been an existing WECC policy that the AESO has been enforcing. This subsection has been added to clarify the testing requirements to the participants. Subsection 28 – Model Revalidation Testing Comment # 31: Insert Comments / Reason for Position (if any) Re-verification testing must be subject to agreement with the generator owner as testing must be scheduled and coordinated with other activities providing adequate lead time to efficiently undertake such tests. While testing is normally scheduled as part of a new or modified unit going into service, a re-verification is done on request and may not be possible within the specified time horizon. It may be planned within the specified period but not undertaken and/or the report not yet be prepared. Comment # 32: Insert Comments / Reason for Position (if any) Subsection 28 sets out the requirements for the generating unit model revalidation testing and the basic approach has been carried over from the existing Technical Standard. The following reference sections in the existing Technical Standard that have not been included in proposed New ISO Rules Section 502.5: Comment # 33: Insert Comments / Reason for Position (if any) Section 1.1 – Purpose This section was removed to align with the principals of the TOAD project. Issued for Stakeholder Consultation: 2011-12-06 Page 28 Section 1.3 – Definitions This section was removed to align with the principals of the TOAD project. Section 1.4 – Modifications This section was removed to align with the principals of the TOAD project. Section 1.5 – Requirement For Review This section was removed to align with the principals of the TOAD project. Section 1.6 – Document Change History This section was removed to align with the principals of the TOAD project. Section 2.5 – Clearance and Access This section was removed as it referenced codes that do not fall under the jurisdiction of the AESO. Section 4.0 – Load Interconnection Requirements Proposed New ISO Rules Section 502.5 does not include the requirements for load facilities. These facilities will be the subject of separate ISO rules and be consulted on separately as the requirements for generating facilities and load facilities are significantly different. (b) Removals No removal of ISO rules provisions are being proposed for proposed New ISO Rules Section 502.5. Comment # 34: Insert Comments / Reason for Position (if any) (c) Amendment No amendments to ISO rules provision are being proposed for proposed New ISO Rules Section 502.5. Comment # 35: Insert Comments / Reason for Position (if any) Issued for Stakeholder Consultation: 2011-12-06 Page 29 (d) Other (Stakeholders wishing to comment on specific provisions are requested to copy the provision into this area and provide comments) Comment # 36: Insert Comments / Reason for Position (if any) In the Letter of Notice dated December 6, 2011 the AESO has indicated an effective date for Rule 502.5 of October 1, 2012. The new requirements of Rule 502.5 are not trivial and would necessitate extensive review of the capabilities and settings of each generating unit. Such reviews would not be initiated until the rule is approved by the AUC. Once reviews are complete and gaps identified then the owner must either seek an exemption or variance under subsection 4(2) or develop mitigation plans to address the gaps. The AESO is also invoking new processes for units unable to meet specific requirements and which require engineering studies to be undertaken. As well, any changes, if required, must be thoroughly designed and planned and coordinated with outage schedules for the units. Coordination is also required, for example, if the unit is governed by a PPA, with the PPA holders and be consistent with the change of law provisions within such PPAs. In TransAlta’s view the effective date should be two years from AUC approval. The implications of Rule 502.5 are significant and TransAlta requests and suggests that the AESO host a technical consultation meeting to review and clarify the requirements of each subsection. Our preliminary review of our generating units has disclosed numerous concerns with various requirements and we need a fuller understanding of the requirements than that conveyed by what is written in the proposed rule. We need to understand why these are the minimum requirements. What studies have been done and what Issued for Stakeholder Consultation: 2011-12-06 Page 30 evidence supports the proposed requirements? The issue of the draft rule on December 6, 2011 has in our view provided insufficient time for the industry to properly assess the implications of the new rule. TransAlta also suggests the AESO host separate consultation meetings focused on both a reactive power market and technical requirements. This should also focus on what is the appropriate reactive power range for normal operating conditions. This could be coordinated with the suggested studies in subsection 8. Further the testing requirements within this rule are extensive and again we suggest the AESO host a technical consultation meeting on what the expectations are for each test. We would, for example, like to see the sections in the Information Document 2011-012R regarding testing be expanded. We highlight, for example, subsection 23(4) regarding demonstrating capability to meet voltage ride through as an area of particular interest. Issued for Stakeholder Consultation: 2011-12-06 Page 31