Stakeholder Comment and Replies Matrix AESO AUTHORITATIVE DOCUMENT PROCESS
by user
Comments
Transcript
Stakeholder Comment and Replies Matrix AESO AUTHORITATIVE DOCUMENT PROCESS
Stakeholder Comment and Replies Matrix AESO AUTHORITATIVE DOCUMENT PROCESS Proposed “Allowable Dispatch Variance” Amended ISO Rule Definition (“Allowable Dispatch Variance Definition Amendment”) Date of Request for Comment [yyyy/mm/dd]: Period of Consultation [yyyy/mm/dd]: 2014-04-29 2014-04-29 Definitions – Amended Existing “allowable dispatch variance” means, for each generating source asset as measured from the dispatch quantity: (i) plus or minus five (5) MW for a generating source asset with a maximum capability of two hundred (200) MW or less, or (ii) plus or minus ten (10) MW for a generating source asset with a maximum capability of greater than two hundred (200) MW. through 2014-05-28 Proposed Rationale “allowable dispatch variance” means: Wind aggregated generating facilities cannot control their output when wind speed is decreasing, but they can control their output when wind speed is increasing and if they are equipped with new control technology. Accordingly, the AESO proposes to change the definition of “allowable dispatch variance” to also apply to wind aggregated generating facilities. (i) for each generating source asset, other than a wind aggregated generating facility, as measured from the dispatch quantity: (a) plus or minus five (5) MW for a generating source asset with a maximum capability of two hundred (200) MW or less; or (b) plus or minus ten (10) MW for a generating source asset with a maximum capability of greater than two hundred (200) MW; (ii) for each wind aggregated Final Draft for Internal Approval to File: 2014-08-19 The dispatch quantity of a wind aggregated generating facility is based on its in-merit energy offer. If its potential real power capability in real-time is less than the dispatch quantity, the lower boundary of the allowable dispatch variance is measured from that potential real power capability. The wind aggregated generating facility will remain in compliance as long as its output does not exceed the dispatch Stakeholder Comments and/or Alternate Proposal Capital Power 1. Capital Power appreciates the AESO’s commitment to consult with stakeholders on changes to the ISO Rules Framework. After reviewing the draft definition of ADV, Capital Power understands the proposed amendments to apply only to non-exempt wind aggregated generating facilities (as described in ISO Rules Section 304.3 and 502.1) that are dispatched on non-zero dollar offer blocks. As a result, Capital Power does not oppose the changes. ENMAX 2. Conceptually, ENMAX agrees that there should be allowable dispatch AESO Reply 1. Acknowledged. 2. To remain in compliance with a dispatch, each wind aggregated generating facility Page 1 of 4 generating facility with a maximum capability of two hundred (200) MW or less: (a) five (5) MW greater than the dispatch quantity and five (5) MW less than the potential real power capability, if the potential real power capability is less than the dispatch quantity; or (b) plus or minus five (5) MW from the dispatch quantity, if the potential real power capability is greater than or equal to the dispatch quantity; and (iii) for each wind aggregated generating facility with a maximum capability of greater than two hundred (200) MW: (a) ten (10) MW greater than the dispatch quantity and ten (10) MW less than the potential real power capability, if the potential real power capability is less than the dispatch quantity; or (b) plus or minus ten (10) MW from the dispatch quantity, if the potential real power capability is greater than or equal to the dispatch quantity. Final Draft for Internal Approval to File: 2014-08-19 quantity by more than the allowable dispatch variance. If the potential real power capability of a wind aggregated generating facility is greater than or equal to the dispatch quantity, the allowable dispatch variance is measured from the dispatch quantity as it is for a generating source asset that is not a wind aggregated generating facility. variances associated with wind aggregated generating facilities, at least when the wind is increasing. For the following reasons, however, ENMAX is less clear on the usefulness of a lower limit on wind production. Additional work on some definitions may help. 3. There appears to be no definition of the term “potential real powercapability.” It is not clear to ENMAX whether it is: (i) the maximum output of a wind aggregated generating facility under maximum wind conditions, which output could be less than the facility’s maximum capability due to one or more turbines being off line, and as (presumably) to be reported in accordance with Rule 306.5; or (ii) the maximum output likely given current (real time) forecasts, as ENMAX understands is to be reported in accordance with sections 25(4) and (5) of Rule 502.1. It would be helpful to have an explicit definition. If “potential real power capability” is intended to mean “available capability,” the latter term should be used and perhaps re-defined with wind generators in mind. must produce its potential real power capability (within 5 MW or 10 MW depending on its size) if it is in-merit, even if its potential is falling in real time. A wind aggregated generating facility cannot physically withhold in-merit energy. 3. “Potential real power capability” is defined in Appendix 2 of section 502.8 of the ISO rules, SCADA Technical and Operating Requirements, as follows: “Potential real power capability, being the real power that would have been produced at the point of connection without wind aggregated generating facilities curtailment and based on real time meteorological conditions at each available wind turbine generator”. Available capability (AC) is not related to wind speed on site. AC as it relates to a generating source asset is the maximum MW that the source asset is physically capable of providing. Page 2 of 4 4. It is not clear to ENMAX 4. The energy dispatch will be how the potential real power based on the offer. For a wind capability of a wind farm offering at zero (0) aggregated generating dollars, the energy dispatch facility could be less than will be the maximum the dispatch quantity. capability (MC) assuming ENMAX assumes that this there is no derating. The situation would arise when system controller will not a wind facility has submitted constantly re-dispatch the an offer volume (at zero wind farm as its potential real dollars or otherwise) that it power capability fluctuates as is not able to achieve. long as it remains in-merit. Presumably, however, the System Controller would immediately re-dispatch the wind generator to the level it is capable of achieving. 5. ENMAX believes that additional clarity on this rule will be particularly important in situations in which both wind and non-wind generators face curtailments due to limitations on available transmission capability under the to-be-developed TCM Rule(s). TransCanada 6. As per comments made in the matrix for Section 304.3, “potential real power capability” is unclear. Without clarity on this TCE cannot assess this proposed definition change. Suncor Energy Products Inc. 7. The AESO is proposing an Allowable Dispatch Final Draft for Internal Approval to File: 2014-08-19 5. If the transmission constraint management (TCM) directive is lower than the energy dispatch, the wind generator will have to limit itself to the TCM directive, as per section 302.1 of the ISO rules. 6. Please see AESO Reply #3. 7. A dispatch pilot conducted in Page 3 of 4 Variance (ADV) of 5 MW above or below the dispatch quantity for wind facilities < 200 MW if the potential real power is equal or greater to the dispatch quantity. Suncor believes that the ADV is too low for wind facilities of this size. Suncor’s Wintering Hills is an 88 MW facility consisting of 55 - 1.6 MW turbines. Under the AESO’s proposed ADV of 5 MW, the variance band is equivalent to only 3.1 turbines in capacity. The AESO’s proposed ADV does not take into consideration the size of the turbines at individual wind farms. With turbines available in the 3 to 5 MW range, wind generators risk ADV noncompliance due to unscheduled turbine down time. The ADV should be a percentage of the wind facility’s total capacity. In the case of Wintering Hills an ADV of 10% would be equivalent to 8.8 MW and represents a more reasonable operational limit. Final Draft for Internal Approval to File: 2014-08-19 2012 by the AESO using 2 X 66 MW wind farms indicated that staying within the Allowable Dispatch Variance (ADV) as production goes down was more challenging for the market participant than staying within the ADV as production goes up. This finding from the dispatch pilot is addressed in the proposed definition. The wind farm described in Suncor’s example will remain in compliance, because, if turbines go down, then the wind farm’s potential real power capability will go down. The AESO is committed to monitoring the effectiveness of the rule and will make improvements as necessary. Page 4 of 4