Comments
Description
Transcript
24' See Note 2 12' See Note 3
See Note 2 24' 12' 12' 24' Travel Lane See Note 3 Travel Lane 12' Existing Grade 12' Cabinet Shoulder Travel Lane Cabinet Travel Lane Guardrail (if shown in Plans) TYPE A TYPE B 1. For location where pole foundation is lower than roadway, mount CCTV cabinet on pole. 2. 11/30/2015 � GENERAL NOTES: Install CCTV Pole at locaton shown in Plans. 3. If included, install guardrail at location shown in Plans and in accordance with Design Standards Index 400. LAST REVISION 07/01/15 REVISIO N 11: 36: 56 AM � DESCRIPTION: INDEX FY 2016-17 DESIGN STANDARDS CCTV POLE PLACEMENT NO. 18100 SHEET NO. 1of 1 Dome Type CCTV Camera Dome Type CCTV Camera For Ground Mounted Cabinet For Ground Mounted Cabinet (See Index 18107) (See Index 18107) For Pole Mounted Cabinet For Pole Mounted Cabinet (See Index 18108) (See Index 18108) CCTV Cabinet CCTV Cabinet For Grounding (See Index 18102) Concrete 11: 36: 56 AM Concrete For Grounding (See Index 18102) CONCRETE POLE LAST REVISION 07/01/13 REVISIO N 11/30/2015 STEEL POLE DESCRIPTION: INDEX FY 2016-17 DESIGN STANDARDS TYPICAL CCTV SITE NO. 18101 SHEET NO. 1of 1 1 2" 1 2" ETP Alloy 110 Copper Air Terminal (Class II) UL-96A Listed 2' Min ETP Alloy 110 Copper Air Terminal (Class II) UL-96A Listed 2' Min Bond #2 AWG Tin-Plated Bare Solid Bond #2 AWG Tin-Plated Bare Solid Copper Ground Wire To The Air Copper Ground Wire To The Air Terminal. Terminal. A Steel Pole May Be Used As A Grounding Conductor If It Has Bond #6 AWG Tin-Plated Bond #6 AWG Tin-Plated Sufficient Cross-Sectional Area To Bare Solid Copper Wire To Bare Solid Copper Wire To Equal The Conductivity Of Main Camera Support Base As Camera Support Base As Lightning Conductors Per NFPA 780 Required. Required. And A Minimum Wall Thickness Of 3 16" Or Greater. #2 Wire May Be Routed Internally Or Externally According To Project Requirements #2 AWG Tin-Plated Bare Dome Type For Concrete Poles That Do Not Have Dome Type Solid Copper Wire. CCTV Camera Embedded Ground Wire, Install #2 AWG CCTV Camera Tin-Plated Bare Solid Copper Wire. Clamp To Concrete Pole @ 3' Intervals. Bond To Air Terminal And Ground Rod With Exothermic Welds. 1 2" x 10' PVC Conduit Sleeve Shall Be Provided To Protect Any External Ground Wire From Mechanical Damage. Ensure Conduits Are Sealed To Prevent Water Intrusion. Pole Mounted Cabinet Pole Mounted Cabinet Wire Screen 8" MAX. Finished Grade Ground Rod A 2" MIN. Primary Ground 8" MAX. Rod Assembly Ground Rod B (See Inset A) As Required Ground Rod A Primary Ground Finished Grade 18" M in. 2" MIN. Conduit for Grounding Conductors Pull Box 11: 36: 57 AM 12" Min. 36" Max. #2 AWG To Ground Rod C As Required #2 AWG To Ground Rod C As Required #2 AWG To Ground Rod D As Required #2 AWG To Ground Rod D As Required 5 8" Diameter By 20' Long Concrete 12" Min. 36" Max. 11/30/2015 REVISIO N 07/01/14 5 8" Diameter By 20' Long Copper-Clad Steel Ground Rods Copper-Clad Steel Ground Rods Driven Into Undisturbed Earth Driven Into Undisturbed Earth 40' Typ. STEEL CCTV POLE LAST As Required Exothermic Weld 40' Typ. REVISION Ground Rod B (See Inset A) Pull Box Exothermic Weld Concrete Rod Assembly 18" M in. Conduit for Grounding Conductors CONCRETE CCTV POLE DESCRIPTION: INDEX FY 2016-17 DESIGN STANDARDS GROUNDING AND LIGHTNING PROTECTION NO. 18102 SHEET NO. 1of 4 1/2" ETP Alloy 110 Copper Air Terminal (Class II) 2' Min AIR TERMINAL PLACEMENT (Lowering Device Pole) ƀ" ETP Alloy 110 Copper Air Terminal (Class II) ƀ" ETP Alloy 110 Copper Surface Base Of 8 Square-Inch Air Terminal (Class II) Minimum Contact Area Surface Base Of 8 Square-Inch Per NFPA 780-4.16.3 Minimum Contact Area Per NFPA 780-4.16.3 2' Min 2' Min 2' Min 4' Min #2 AWG Tin-Plated Bare Solid Copper Ground Wire. Bond To Air Terminal #2 AWG Tin-Plated Bare Solid Copper Ground Wire. Bond To Air Terminals Guardrail (if shown in Plans) Guardrail 11: 36: 58 AM (if shown in Plans) AIR TERMINAL PLACEMENT (Cantilever DMS) LAST REVISION 07/01/15 REVISIO N 11/30/2015 AIR TERMINAL PLACEMENT (Span DMS) DESCRIPTION: INDEX FY 2016-17 DESIGN STANDARDS GROUNDING AND LIGHTNING PROTECTION NO. 18102 SHEET NO. 2 of 4 "Sphere Of Influence: 120 Degree" Ground Rod C "Modified Sphere Of Influence: 90 Degree" #2 AWG Ground Rod C #2 AWG Primary Ground Rod A Primary Ground Rod A Ground Rod B Ground Rod D Ground Rod D Ground Rod B Foundation: CCTV or DMS Pole Foundation: CCTV or DMS Pole GROUND ROD ARRAY PLACEMENT (Typical) 20' RODS, 40' SPACING GROUND ROD ARRAY PLACEMENT (Typical Modified) 20' RODS, 40' SPACING #2 AWG Tin-Plated Bare Solid Copper Wire Continuous To Air Terminal #2 AWG Tin-Plated Bare Solid Copper Wire To Ground Rods B, C And D As Required (Connections May Be Combined) #2 AWG Tin-Plated Bare Solid Copper Wire To Pole Mounted Or Ground Mounted Cabinet LAST REVISION 07/01/14 REVISIO N 11/30/2015 11: 36: 59 AM INSET "A" DESCRIPTION: INDEX FY 2016-17 DESIGN STANDARDS GROUNDING AND LIGHTNING PROTECTION NO. 18102 SHEET NO. 3 of 4 "Sphere Of Influence: With Ground Ring" Ground Rod D #2 AWG (Typical) Primary Ground Rod A Foundation: Communication Tower Communication Tower #2 AWG 12" Min./36" Max. From Foundation Ground Rod B Ground Rod C Ground Rod F Ground Rod E GROUND ROD ARRAY PLACEMENT (Communication Tower) 20' RODS, 40' SPACING Tower Leg Grounding Conductors Ground Rod A Ground Rod B Primary Ground 2" MIN. Ground Rod D Rod Assembly 8" MAX. (See Inset A) 18" M in. Ground Rod E Pull Box Exothermic Weld Exothermic Weld #2 AWG #2 AWG #2 AWG #2 AWG To Ground Rod E To Ground Rod A To Ground Rod B To Ground Rod D #2 AWG To Ground Rods C+F Pull Box 5 8" #2 AWG To Ground Rods C+F 12" Min. 12" Min. 36" Max. 36" Max. 5 8" Diameter By 20' Long Diameter By 20' Long Copper-Clad Steel Ground Rods Structure Or Device Copper-Clad Steel Ground Rods Driven Into Undisturbed Earth Requiring Grounding Driven Into Undisturbed Earth 11: 36: 59 AM Grounding Conductors 40' Typ. GROUND ROD ARRAY PROFILE (Communication Tower) LAST REVISION 07/01/14 REVISIO N 11/30/2015 COMMUNICATION TOWER 40' Typ. DESCRIPTION: INDEX FY 2016-17 DESIGN STANDARDS GROUNDING AND LIGHTNING PROTECTION NO. 18102 SHEET NO. 4 of 4 Air Vent Dual Fans Area To Remain Clear For Full Width And Depth Shelf Ethernet Switch, Video Encoder Area To Remain Clear For Full Width And Depth Preterminated Fiber Optic Patch Panel CCTV Interface Panel Sliding Drawer Area To Remain Clear For Full Width And Depth Protection 5 3 Protection RU TVSS Surge 1 4" TVSS Surge Video 19" EIA Rack With Tapped 10-32 Threaded Holes And Terminal Server 36" 1 RU 1 RU 3 RU 1 1 3 4" 1 1 4" 5 3 4" 1 RU 1 RU 2 RU 1 Full Width And Depth RU Area To Remain Clear For 1 Sliding Drawer RU Cabinet Front CCTV Interface Panel 3 4" Preterminated Fiber Optic Patch Panel 1 Full Width And Depth 1 2" Area To Remain Clear For 3 And Terminal Server 3 4" Ethernet Switch, Video Encoder 1 Shelf 3 4" Full Width And Depth 1 Area To Remain Clear For 3 4" Air Vent TVSS Protected Outlets For Equipment Video GFI Protected Convenience Outlet Data Data Power Power For Portable Tools Power Distribution Assembly Service Entrance, Breaker, 3 Primary AC Power Filter, RU Primary AC Power Filter, 5 Service Entrance, Breaker, 1 4" Power Distribution Assembly Ground Bussbar (Number Of Outlets - Project Specific) Ground Bussbar (Number Of Outlets - Project Specific) 22" 24" SIDE VIEW FRONT VIEW 11: 37: 00 AM GENERAL NOTES: 1. Cabinet layout is for pole or base mounted installations. 2. All dimensions and scale are approximate. 3. The minimum CCTV cabinet dimensions shall be 36"H X 24"W X 22"D. 4. Conduit entrances are in bottom of cabinet. 5. There shall be front and rear doors. Both doors shall have the hinged 6. Cabinet layout represents preferred placement of typical devices. Project-specific designs may not include all components illustrated here. LAST REVISION 07/01/07 REVISIO N 11/30/2015 side next to the pole when pole mounted. DESCRIPTION: INDEX FY 2016-17 DESIGN STANDARDS TYPICAL CCTV CABINET EQUIPMENT LAYOUT NO. 18104 SHEET NO. 1of 1 TVSS Protection Power Distribution For Equipment Power AC Service Assembly Optional Power Supply Local Management Port RS-232 Optional Power Ethernet Supplies From 10/100 Base TX/RX GFI Electric Utility Convenience Outlet(s) For Portable Tools Composite Video TVSS Ethernet 100/1000 Base FX Ethernet Ethernet Switch 10/100 Base TX/RX Video Encoder Single Mode Fiber Optic Maintenance Cabinet Access RS-232/422/485 CCTV Camera Serial Data TVSS Terminal Server May Be One Maintenance Local Management Port Access RS-232 Or More Devices 11: 37: 00 AM LEGEND Data Ethernet Power 11/30/2015 TVSS Transient Voltage LAST REVISION 07/01/07 REVISIO N Surge Suppressor DESCRIPTION: INDEX FY 2016-17 DESIGN STANDARDS CCTV BLOCK DIAGRAM NO. 18105 SHEET NO. 1of 1 CCTV Cabinet 2" PVC Conduit For Routing Cabling To Camera Between Cabinet And Pole 1 2" Fiber Optic Communications Fiber Optic Pull Box PVC Grounding Conduit #4 AWG Ground Wire Conduits (As Shown On Plans) To Power Service Assembly Fiber Optic Power Conduit Communications Conduits (As Shown On Plans) GENERAL NOTES: 1. Contractor shall splice fiber optic cables in cabinet to preterminater patch panel. 2. Furnish and install TVSS protection on all video, data, and power cabling in cabinet. 3. Ensure that all electronic equipment power is protected and conditioned with TVSS 4. Sizes and types of conduits and innerducts for network communications between the pullbox and cabinet are stated in the contract documents. 5. See Index 18102 for grounding requirements. 6. All network communications conduits and ducts shall be sealed with approved waterproof duct plugs and seals. LAST REVISION 07/01/13 REVISIO N 11/30/2015 11: 37: 01 AM devices. DESCRIPTION: INDEX FY 2016-17 DESIGN STANDARDS GROUND MOUNTED CCTV CABINET NO. 18107 SHEET NO. 1of 1 Pole Mounted Cabinet * (See Detail A) Field adjust pole-mounted cabinet height to achieve Pole Mounted Cabinet best access for maintenance (See Detail A) personnel given site conditions as directed by the Engineer. Avoid conflicts with handhole. 1 2" 1 Fiber Optic Communications Conduit RGS (As Shown On Plans) Power Conduit 1 2" Fiber Optic Pull Box PVC Conduit Fiber Optic Pull Box 1 2" 1 3' For Grounding Fiber Optic Communications Conduits Fiber Optic Communications Conduits (As Shown On Plans) (As Shown On Plans) Power Conduit To Power Service Assembly RGS 1 2" Power PVC Conduit For Grounding Conduit Power Conduit To Power Service Assembly STEEL POLE CONCRETE POLE Composite Composite Camera Cable Camera Cable CCTV CCTV Cabinet Cabinet Pole Plate With Stainless Steel Band � GENERAL NOTES: 1 1 2" RGS Conduit Riser For 2" PVC Conduit Riser Pole Opening For Cabinet For Fiber Optic Drop Entrance Shall Be Factory Installed 1. Contractor shall splice fiber optic cables in cabinet to preterminated patch panel. 2. Furnish and install TVSS protection on all cabling in cabinet. Cable Power Into Cabinet From 3. Furnish and install secondary TVSS protection on outlets for equipment in cabinet. 11: 37: 01 AM Power Service Assembly One Pulling Elbow (2)Conduit Risers Type LB 2" For (1)1 Camera Composite Cable (1)For Fiber Optic 1 2" For Power Communications Conduits (As 11/30/2015 FRONT VIEW SIDE VIEW Shown On Plans) 4. Sizes and types of conduits and innerducts for network communications between the pull box and cabinet are stated in the contract documents. 5. Ensure that equipment cabinet is bonded to CCTV pole grounding system. 6. All network communications conduits and ducts shall be sealed with approved waterproof duct plugs and seals. 7. Pole mounted cabinets shall be mounted with hinges next to the pole. LAST REVISION 07/01/07 REVISIO N DETAIL A DESCRIPTION: INDEX FY 2016-17 DESIGN STANDARDS POLE MOUNTED CCTV CABINET NO. 18108 SHEET NO. 1of 1 1 2" ETP Alloy 110 Copper 24' Air Terminal Class II Removable Top Cap Connectors And Camera Wiring Pole Top Junction Box Pole Fitter Divided Channel Arm U-Bolt U-Bolt Clamps Clamps Cable Stop Block Conduit To Be Bolted Here Disconnect Unit Fitter 3-Way Tracking Guide And Support Pulley Pulley EPDM O-Ring Seal CCTV Lowering Cable Interior Conduit Pole Details On Contact Connector Disconnect Unit Lower Contact Connector Assembly Socket Separate Drawing Ground Rod Base Disconnect Sealing Gasket Ring Mount To Side Of Pole Camera Junction Box Unit Cover Guide Pin And Stabilizing Weight Double Support Arms Camera Connectors Sealing Gasket Camera Mounting Bracket And Dome Flange (Between Lower Contact Assembly And Junction Box) Strain Relief Fitting Dome Type CCTV Camera (TYP) TVSS Surge Protection For Power, Data And Video GENERAL NOTES: 1. Lowering device to be shipped ready for pole attachment to include 100 ft. of composite power and signal cable prewired to lowering device at the factory. 2. The lowering device manufacturer shall supply both a portable lowering tool with a manual hand crank and a half-inch chuck variable-speed reversible industrial-duty electric drill that matches the winch's manufacturer-recommended revolutions per minute. One lowering tool per every 10 lowering devices is required. 3. The lowering device manufacturer shall provide an on-site installation inspection and operator instruction and certification. This ensures the product is assembled correctly and that all necessary persons are trained in the proper, safe operation of the system. Before erecting the first pole the contractor must contact the lowering device supplier and schedule a manufacturer's representative to be on-site. Design camera mounting arm and connection to tenon according to FDOT Structures Manual (current edition). 5. Camera to be mounted to camera junction box and stabilizing weight via 1 6. Use air terminal extension when the pole top junction box is wider than top of pole. 7. The stainless steel device lowering cable shall be installed inside the pole within a 1 8. All communication and power cables must be neatly bundled and secured. 9. Use a Camera Lowering Device listed on the Approved Product List (APL). 1 2" Standard NPT Pipe Thread. 1 4" diameter PVC conduit. CAMERA MOUNTING WITH LOWERING DEVICE 10. See Index 18113 for concrete pole details and Index 18111 for steel pole details. LAST REVISION 01/01/10 REVISIO N 11/30/2015 11: 37: 02 AM CAMERA LOWERING DEVICE DETAIL 4. DESCRIPTION: INDEX FY 2016-17 DESIGN STANDARDS CAMERA MOUNTING DETAILS NO. 18110 SHEET NO. 1of 2 Bond #4 AWG Tin-Plated Bare Solid Copper Ground Wire To Camera Support Base By An Aluminum To Copper #2-#14 AWG Pole Plate With Stainless Steel Band Lug. Attached To Camera Base With A Stainless Steel Screw. (Or Method Approved By Engineer) Remove Paint Or Protective Coating Where Attaching Lug. Bracket Design May Vary By CCTV Manufacturer Fixed Mounting Bracket Must Be Strain Relief Designed To Match Mounting Fitting Provisions For CCTV Camera Camera Connector Harness Supplied To Match Camera A A Cabling To Camera Dome Type Camera Assembly (TYP) Cast In Place 2" Galvanized Nipple For Concrete Poles. Hole With Nipple Grommet For Steel Poles. FIXED MOUNTING BRACKET DETAIL Not To Scale Pole Plate With Stainless Steel Band (Or Method Approved By Engineer) Varies (2' Max.) 1 2" 6 Dia. Verify the pole type, the dimensions of the pole at the point of M 1. a x .) D ia . GENERAL NOTES: (3 0 " installation of the camera mount, and angle with respect to the 2. V a r ie s roadway before manufacturing camera mount assembly. Design camera mounting arm and connection to the pole according to FDOT Structures Manual (current edition). 3. No field welding shall be permitted. 4. Mounting bracket arm shall be level after installation. 5. The contractor shall submit shop drawings for the proposed fixed The Contractor Shall Coordinate Bracket Design And Flange Connection With CCTV Camera Manufacturer For 11: 37: 03 AM Mounting The CCTV Camera Housing mounting arm, signed and sealed by a Professional Engineer registered in the State of Florida, to the Engineer for review and approval. 6. SECTION AA See Index 18113 for concrete pole details and Index 18111 for steel 7. Galvanized pipe connections and conduit entry points shall be sealed in accordance with Section 630 of the Standard Specifications. LAST REVISION 01/01/10 REVISIO N 11/30/2015 pole details. CAMERA MOUNTING WITH FIXED BRACKET DESCRIPTION: INDEX FY 2016-17 DESIGN STANDARDS CAMERA MOUNTING DETAILS NO. 18110 SHEET NO. 2 of 2 FOUNDATION NOTES: 1. Concrete: Class IV (Drilled Shaft) with a minimum 4,000 psi INSTALLATION NOTES: POLE NOTES: 1. 1. The pole shaft shall be round or 16 sided or more with a constant taper of 0.14 2. Pole shaft may be either One or Two sections (with telescopic field splice). b. Position one cable guide 2" below the handhole. 3. Use only circumferential welds at base. c. Position other cable guide 1" directly below the top of 4. Up to two longitudinal seam welds are permitted. 5. Longitudinal seam welds within 6" of circumferential welds shall be complete Cable Supports: Electrical Cable Guides and Eyebolts. inches per foot. compressive strength at 28 days for all environment a. Locate top and bottom cable guides within the pole classifications. aligned with each other. 2. Reinforcing Steel: ASTM A615 Grade 60. 3. Anchor Bolts: ASTM F1554 Grade 55 with ASTM A563 Grade A heavy-hex nuts and plate washers. ASTM F2329 the tenon. galvanization. 4. d. Position Park Stands 2" below the top of the handhole. Install Anchor Bolts in accordance with Section 649-5 of the penetration welds. Longitudinal seam welds on female section of telescopic field splices shall be complete penetration welds for the splice length plus six inches. Specifications. 2. 5. Lowering Device Installation Notes: tube thickness. a. 6. All other areas, size the partial penetration welds to at least 60% of the pole Foundation applies to slopes 1:4 or flatter. Place the lowering cable that moves within the pole in an interior conduit to prevent it from tangling or The foundation for the CCTV structure shall be constructed in accordance with Section 455 of the Specifications except that no payment for the foundation shall be made under 6. Welding Code (Steel) ANSI/AWS D1.1 (current edition). For additional welding pole. Ensure that any electrical wire within the pole requirements see AASHTO Standard Specifications for Structural Supports for is routed securely and free from slack. Section 455. b. Perform all welding in accordance with the American Welding Society Structural interfering with any electrical wire that is in the Mount lowering arm perpendicular to the roadway or Highway Signs, Luminaires and Traffic Signals, Section 5.15, Welded Connections. 7. as shown in the plans. Position CCTV pole so that the Identification tag: Furnish each pole with a 2"x4" (max.) aluminum identification tag, secured to pole camera can be safely lowered without requiring lane with stainless steel screws. closures. Locate inside pole and visible from handhole. Provide Financial Project ID, pole height, manufacturer's name, yield strength (Fy c. Coordinate all lowering device hardware requirements of steel) and pole base wall thickness. (including Tenon, Tenon mounting plates, parking stands, etc.) with lowering device manufacturer. 8. Except for Anchor Bolts, all bolt hole diameters shall be equal to the bolt diameter plus 1/16", prior to galvanizing. Hole diameters for anchor bolts shall 3. Pole Installation Notes: a. Install pole plumb. b. The pole shall not be erected until the foundation not exceed the bolt diameter plus 1/2". 9. This Design Standard is considered fully detailed and no shop drawings are necessary. Submit Shop Drawings for minor modifications not detailed in the plans. concrete has achieved 70% of the minimum specified 28 day compressive strength. 4. Refer to Index No. 18108 for conduit and cabinet 10. Pole Material Specifications: a. mounting details. Pole: ASTM A1011 Grade 50, 55, 60 or 65 (less than 1/4") or ASTM A572 Grade 50, 60 or 65 (greater than or equal to 1/4") or ASTM A595 Grade A (55 ksi yield) or Grade B (60 ksi yield). b. Steel Plates and Pole Cap: ASTM A36 or ASTM A709 Grade 50. c. Weld Metal: E70XX. d. Bolts: ASTM A325, Type 1. Nuts: ASTM A563. Washers: ASTM F-436. e. Handhole frame: ASTM A709 Grade 36 or ASTM A36. f. Handhole cover: ASTM A1011 Grade 50, 55, 60 or 65. g. Stainless steel screws: AISI Type 316. h. Galvanization: Nuts, bolts and washers: ASTM F2329. All other steel: ASTM A123. 11. Additional wire access holes not shown in this Design Standard shall not exceed 1½" in diameter. 12. Verify CSL access tubes will not interfere with anchor bolt installation before 11: 37: 03 AM excavating the shaft. When CSL access tube locations conflict with anchor bolt locations, move the CSL access tube location ± two inches along the inner circumference of the reinforcing cage. Notify the Engineer before excavating the shaft if the CSL access tube locations cannot be moved out of conflict with 11/30/2015 anchor bolt locations. LAST REVISION 07/01/13 REVISIO N GENERAL NOTES DESCRIPTION: INDEX FY 2016-17 DESIGN STANDARDS STEEL CCTV POLE NO. 18111 SHEET NO. 1of 4 Pole Pole Camera With Lowering Interior Camera With Fixed Device Mounting Bracket Conduit Handhole Handhole SHAFT DESIGN TABLE ORIENTATION VIEW ORIENTATION VIEW Air Terminal Air Terminal (See Index 18102) (See Index 18102) Coordinate Coordinate Mounting Method Mounting Method Pole Overall Height (ft) Shaft Diameter Shaft Length Longitudinal Reinforcement Pole Cap Plate Pole Tenon Pole Top Plate 50 4'-0" 10'-0" (12)#11 55 4'-0" 10'-6" (12)#11 60 4'-6" 11'-0" (16)#11 65 4'-6" 12'-0" (16)#11 70 5'-0" 12'-6" (18)#11 5½" Minimum Inside Diameter 2' Of Pole Raceway For Camera Mounting Details See Index 18110 For Camera Mounting Details Diameter Of 1 2" Handhole Shall Be 90° From The Lowering Arm And Away From Approaching Traffic ¡ Of Handhole Top Of Drilled Overall H eight 7" x 27" ± 2' -9" Length Section 2 Overall H eight Splice Length Pole Raceway 2" Hole With Nipple Grommet BASE PLATE AND ANCHOR BOLT DESIGN TABLE Base Plate Base Plate Anchor Pole Overall Diameter Thickness Bolt Circle Height (ft) (in.) (in.) (in.) 7" x 27" ± No.Bolts Anchor Bolt Diameter (in.) Minimum Anchor Bolt Anchor Bolt Embedment Projection (in.) (in.) 1 2" Handhole Shall Be 90° From The Lowering Arm And Away From Approaching Traffic ¡ Of Handhole 2' -9" Inside See Index 18110 Length Section 2 5½" Minimum Splice Length Length Section 1 Length Section 1 Pole Top Plate 50 27 2.5 22 6 1.25 31 8.5 55 28 2.5 23 6 1.25 33 8.5 60 33 2.5 27 6 1.5 34 9.5 65 35 2.5 29 6 1.5 35 9.5 70 40 2.5 33 6 1.75 38 10.5 Top Of Shaft Drilled Shaft Finish Finish Grade Grade POLE DESIGN TABLE* Section 1(Top) Pole Overall Height (ft) 11/30/2015 Joint Length Wall Thickness (in.) Tip Dia.(in.) Base Dia. (in.) Length Wall Thickness (in.) Tip Dia.(in.) Base Dia. (in.) Minimum Splice Length (in) --- --- --- --- 50'-0" 0.25 10 17 --- 50 ELEVATION WITHOUT LOWERING DEVICE 11: 37: 04 AM ELEVATION WITH LOWERING DEVICE Section 2 (Bottom) 24'-0" 0.25 10.5 13.875 28'-3" 0.25 13.031 17 21 55 30'-0" 0.25 10.781 15 27'-6" 0.3125 14.125 18 24 60 35'-0" 0.25 13.094 18 27'-9" 0.3125 17.094 21 27 65 34'-0" 0.25 14.406 19.188 34'-0" 0.3125 18.219 23 30 70 33'-3" 0.25 16.719 21.375 40'-0" 0.3125 20.375 26 33 * Diameter Measured Flat to Flat LAST REVISION 07/01/13 REVISIO N POLE DESIGN TABLES DESCRIPTION: INDEX FY 2016-17 DESIGN STANDARDS STEEL CCTV POLE NO. 18111 SHEET NO. 2 of 4 Pole Base Diameter Shaft Diameter 2 X Anchor Bolt Diameter 1" a p( 2"L Mi n 2' . ) Anchor Bolt Circle Edge of Base Plate C See Joint Weld Detail 1" Min. Handhole Ring Anchor Bolts Equally Spaced (See Table) Silicone Caulk C Double Nuts, Top Nut may 4" Base Plate And Pole be half height 'Jam' Nut. 6" Center of Drilled Shaft, 3"X Ɓ" Backing Ring 3 8" B Plate Washer B ¼" CSL Tube (Typ.) Base Plate Longitudinal Thickness Reinforcement Eq. Base Plate Opening Spaced (See Table #5 Tie Bars 6 " C (T o y ve p .) r For Reinforcement) (1) Bolt Diameter Anchor Bolt Circle (Max.) Base Plate Diameter SECTION A-A Center of Drilled Shaft FOUNDATION PLAN Leveling Nut (Anchor Bolts and Conduits Not Shown) Base Plate Diameter D 1" D Shaft Diameter Projection M in. Anchor Bolt Anchor Bolt Drilled Shaft Anchor Bolts 1" x 1" Chamfer 4" Ɓ" 45° 3" x Ɓ" Backing Ring A 4" Cover ( Top) 1" Min. 1' -7½ " Ɓ" Shaft Length (Wall Thk. +Ɗ") x Wall Thk. 6 Sp. @ Silicone Caulk Pole Wall Thk. +Ɗ" Wire Screen M in. Pole See Section 2 (Bottom) on Pole Design Table for Wall Thk. A 1' -0" 2' -3" Cover Plate 5" SECTION C-C Handhole Ring Base Plate Opening See Spec. 649-6 JOINT WELD DETAIL Tip Diameter or Base Diameter Sp. @ Measured Flat to Flat 1' -6" ( M ax. ) M in. 1' -0" Em bedm ent Anchor Bolt Finish Grade Center of Pole Typ. (See Pole Notes) Wall 0.6 x Wall Thickness 7" measure center Min. Break Radius to flat = 0.25 x (Inside Radius) 11/30/2015 BASE PLATE AND ANCHORAGE ELEVATION # 5 Ties 11: 37: 07 AM Inside Radius Break Radius Typical Drilled Shaft Spacing 1" Thickness Double Nuts (Typ.) 6" Cover (Typ.) SECTION B-B SECTION D-D (Conduits and CSL Tubes Not Shown) (Conduits, Reinforcement, and CSL Tubes Not Shown) (16-Sided Pole Shown, 18-Sided and Round Pole Similar) LAST REVISION 07/01/13 REVISIO N BASE PLATE AND FOUNDATION DETAILS DESCRIPTION: INDEX FY 2016-17 DESIGN STANDARDS STEEL CCTV POLE NO. 18111 SHEET NO. 3 of 4 � Pole (8) ƍ" Ø Holes 4" Equally Spaced 1" Handhole Frame 1" Plate Pole Wall (12) ƍ" x 3" Slots Tenon Wall Provide Cover Plate Cable Guide For Wire Working Park Stand Steel Chain Mounted Partial Penetration Weld ½" F Tie Off or Hinge Mounted With Pad Lock Tab ƅ" Tenon Plate 2" 1 4" Stainless Steel Hex Head Screws, Typ. (2) Park Stands (Inside Shaft Wall) F 1" Handhole Cover 7" x 27" ± 1 2" Ensure Handhole Is Designed For Use With The Portable Plate Tack Welded 3 16" Thick Cover Clip Typ. Tip Dia. 6" Lowering Tools That Are Used To + ƃ" Operate The Lowering Device System Identification Tag (See Pole Notes) 2" 1 2" Ø Drill & Tap Hole In Handhole Rim. Supplied With 6" SECTION F-F 1 2" 1'-5" (Typ.) 1'-5" Ø x 3" Bolt 1'-7" For 70' Pole (2) Cable Guides For Wire Tie Off 1'-7" (Typ.) 1'-7" 1'-9" For 70' Pole 1 2" POLE TOP PLATE DETAIL Nut Holder With Fastener SECTION E-E At 180° From Handhole (Interior of Pole) 3 4" 1 1'-7" (Typ.) HANDHOLE DETAIL 1'-9" For 70' Pole Ɓ" X 3"W X 1ƀ"H Plate Cable Guide 1'-5" (Typ.) Ƅ" Ø Rod with E 1" Inner Ø Ƅ" Ø Eye Bolt Pole Wall 2" ƈ" 1" 1'-7" For 70' Pole Typical E Pole Wall with 1" Inner Ø similar to Cable 5 Wall Thickness Guide Detail 5 1 8" 6" O.D. x Ɓ" Wall x 12" (Min.) Wall Thickness 1" Ø Hole 7 1 4" ƅ" Ø Hole allow 1ƃ" legs, 1 4" Bend rod to Long Tenon ƅ" Thick Tenon Plate Min. with 5ƀ" Ø Center Hole ROD OPTION EYE BOLT OPTION ƈ" (4) ƍ" Ø Holes 1 2" PARK STAND DETAIL ƈ" (4) Ƃ" x 3Ɓ" Bolt With Typical Hex Nut, (1) Washer, ƀ" Plate ƈ" Ɓ" and (1) Lock Washer Ƅ" Ø Rod with Pole Top Plate 1" Inner Ø POLE CAP PLATE POLE TENON ASSEMBLY DETAIL 1 1 8" 11: 37: 08 AM Pole (or Tenon) Wall (POLE WITHOUT LOWERING DEVICE) (POLE WITH LOWERING DEVICE) 11/30/2015 5 2 16" Note: Install all handhole and opening covers prior to shipping. For Poles with Lowering Device, install Pole Cap Plate when Tenon Assembly is not installed. CABLE GUIDE DETAIL LAST REVISION 01/01/16 REVISIO N POLE DETAILS DESCRIPTION: INDEX FY 2016-17 DESIGN STANDARDS STEEL CCTV POLE NO. 18111 SHEET NO. 4 of 4 LOWERING DEVICE INSTALLATION NOTES: POLE NOTES: 1. 1. Place the lowering cable that moves within the pole in an Pole Material Specifications: 6. interior conduit to prevent it from tangling or interfering with Provided a Class 3 surface finish in accordance with Specification Section 400. any electrical wire that is in the pole. Ensure that any a. electrical wire within the pole is routed securely and free Pole: Use Class VI Concrete with 6 ksi minimum strength at transfer. 7. Provide a 1" minimum cover. b. Prestressing Strands: ASTM A416 Grade 270 low relaxation. 8. Provide handhole and coupler cover plates made of non-corrosive c. Reinforcing Steel: ASTM A615 Grade 60. d. Spiral Reinforcing: ASTM A1064 Cold-Drawn. e. Bolts: ASTM F1554, Grade 55. following sheets. Include the following information using inset numerals Nuts: ASTM A563, Grade A Heavy Hex. with 1" height or as approved in the Producers' Quality Control Program: from slack. 2. Mount lowering arm perpendicular to the roadway or as shown materials. Attach cover plates to poles using lead anchors or threaded in the plans. Position CCTV pole so that the camera can be inserts embedded in the poles in conjunction with round headed chrome safely lowered without requiring lane closures. 3. plated screws. Coordinate all lowering device hardware requirements 9. (including Tenon, Tenon mounting plates, parking stand, etc.) with lowering device manufacturer. Washers: ASTM F436. Provide Identification Markings on the poles where indicated on the Financial Project ID Pole Manufacturer f. Steel plates and Pole Cap: ASTM A36 or ASTM A709 Grade 50. g. Galvanization: Bolts, nuts and washers: ASTM F2329 Pole Length 10. Install pole plumb. 11. Tie ground wires to the interior of reinforcing steel as necessary to All other steel: ASTM A123 2. The pole shall be round or 12-sided. prevent displacement during concreting operations. 3. Cut the tip end of the prestressed strand first or simultaneously with 12. the butt end. This Design Standard is considered fully detailed and no shop drawings are necessary. Submit Shop Drawings for minor modifications not detailed in the plans. 4. For spiral reinforcing, one turn is required for spiral splices and two turns are required at the top and bottom of poles. 5. 13. Storage, Handling and Erection locations shown may vary within ± 3". For Reinforcing Steel, lap splice to consist of a 3'-0" lap length at each splice. No more than two opposing rebar to be spliced at the same Stagger lap splices as needed. 11/30/2015 11: 37: 09 AM cross section. LAST REVISION 07/01/14 REVISIO N GENERAL NOTES DESCRIPTION: INDEX FY 2016-17 DESIGN STANDARDS CONCRETE CCTV POLE NO. 18113 SHEET NO. 1of 4 Conduit Entry Hole C Air Terminal (See Index 18102) Air Terminal (See Index 18102) Coordinate Mounting Method Coordinate Mounting Method Pole Tenon Removable Cap Plate 1" Lifting Hole 1" Lifting Hole 2" Couplings A 2" Coupling For Pole B Without Lowering Device 2' -0" Camera Plane Camera (See Index 18110 For Mounting Details) d ol M Camera (See Index 18110 For Mounting Details) m ea S Interior Conduit for 5½" Min. Inside Diameter 5½" Min. Inside Diameter of Pole Raceway Pole w/ Lowering Device of Pole Raceway D 2" Coupling With Cap at 90° To Handhole Box To Provide Cable Entry Point For Camera Cables Conduit Entry Hole Ground Lug Handhole Box Pole Identification Markings 1" Lifting Hole POLE CONFIGURATION TOP VIEW 1" Lifting Hole 12-SIDED POLE DESIGN TABLE* Pole Identification Markings Shall be 90° From the Lowering Arm (2) 2" Couplings With Caps at 90° To Handhole Box Min.Wall Pole Burial Total Void Thickness Thickness Tip Butt Strand Strand Length Height Depth Taper** Taper Tip Butt End Diameter Diameter Pattern Diameter*** (ft) (ft) (ft) (in/ft) (in/ft) (in) (in) (in) (in) 63 50 13 0.18 0.18 3 3 12 23.34 1 0.6" 69 55 14 0.18 0.18 3 3 12 24.42 1 0.6" 75 60 15 0.18 0.18 3 3 12 25.5 2 0.6" 80 65 15 0.18 0.18 3 3 12 26.4 2 0.6" 86 70 16 0.18 0.18 3 3 12 27.48 2 0.6" Shall be 90° From the Lowering Arm and Away From Approaching Traffic 2' -0" 2' -0" and Away From Approaching Traffic Handhole With Cover 6" 6" Handhole With Cover 6' -3" Typ. 6' -3" Typ. Pole Identification Markings Min.Wall Pole (2) 2" Couplings With Caps at 90° To Handhole Box ROUND POLE DESIGN TABLE Class NS Concrete Class NS Concrete Burial Burial Depth Depth Pole Pole Burial Length Height Depth (ft) (ft) (ft) 63 69 75 4'-0" Ø 11: 37: 10 AM 55 60 ELEVATION WITHOUT LOWERING DEVICE 86 65 70 Min.Wall Min.Wall Total Void Thickness Thickness Tip Butt Strand Strand Taper** Taper Tip Butt End Diameter Diameter Pattern Diameter*** (in/ft) (in/ft) (in) (in) (in) (in) Option 1 0.216 0.192 3 3.76 12.15 25.76 3 0.5" Option 2 0.18 0.172 3 3.5 12.0 23.34 4 0.5" 13 Option 1 0.216 0.192 3 3.83 12.15 27.05 3 0.5" Option 2 0.18 0.173 3 3.5 12.0 24.42 4 0.5" 14 Option 1 0.216 0.192 3 3.9 12.15 28.35 3 0.5" Option 2 0.18 0.173 3 3.5 12.0 25.5 4 0.5" 15 4'-0" Ø 80 ELEVATION WITH LOWERING DEVICE 50 Design Option Option 1 0.216 0.192 3 3.96 12.15 29.43 3 0.5" Option 2 0.18 0.174 3 3.5 12.0 26.4 4 0.5" Option 1 0.216 0.192 3 4.03 12.15 30.73 3 0.5" Option 2 0.18 0.174 3 3.5 13.0 28.48 4 0.5" 15 16 * Diameter Measured Flat to Flat 11/30/2015 ** Totaltaper applies to pole,strands,and reinforcing. *** For 12-Sided Pole and Round Pole Option 2 Stress prestressed strand to 70% of Ultimate before Transfer. For Round Pole, Option 1 Stress Prestressed strand to 60% of Ultimate before Transfer. LAST REVISION 07/01/13 REVISIO N POLE DESIGN TABLES DESCRIPTION: INDEX FY 2016-17 DESIGN STANDARDS CONCRETE CCTV POLE NO. 18113 SHEET NO. 2 of 4 1.25" Pitch 3" Pitch 1.25" Pitch 3'-0" Varies Burial Depth #5 Gage Spiral Reinforcing ¡ * Spiral wire may be wrapped in two directions given that an equivalent SPIRAL REINFORCING ELEVATION (Strands, Holes, and Fixtures Not Shown) area of spiral wire is provided to that shown in this standard and the cover requirements are met. Final Grade Location ¡ Of Handhole 6" ½" Grd. Lug 4'-3" 1'-6" 9" 1" Lifting A Total Taper 1" Lifting Hole 4" x 12" Conduit Entry Holes At 0° and 180° from Handhole 1'-0" Plug Hole 1ƀ" Ø Drain Hole Tip End (Top) #2 AWG Stranded Ground Conductor 4ƀ" x 30" Handhole A ½" Grd. Lug Grounded to Reinf. Cage Butt End (Bottom) 2" Couplings With Cap Burial Depth Pole Height 0.30 L 0.53 L 0.17 L Storage and Handling 0.30 L 0.70 L Erection Pole Length (L) STRAND LEGEND POLE ELEVATION (Strands and Reinforcing Not Shown) ∆ - Prestressed Strand - (4) #5 Rebar (Shown) or (6) #4 Rebar 9° Tip or Butt Diameter Tip or Butt Diameter Measured Flat to Flat Measured Flat to Flat � Void & Section � Void & Section � Void & Section � Void & Section 36° ss ne ck i h e T l abl al W eT e S ss ne ck i Th e l abl al W eT e S ss ne ck i h e T l abl al W eT e S 18° 18° Strands spaced equally around pole Strands spaced equally around pole Circular Void SECTION A-A SECTION A-A STRAND PATTERN 1 STRAND PATTERN 2 (12 - SIDED) (12 - SIDED) St r a n da n d Re b a rL a y o u t ess n k c hi lT l l e a W ab eT Se 1" Mi n 1 ½ " 1" Mi n ( T y p .a r o u n dp o l e ) Co v er Circular Void 1 ½ " Co v er Circular Void #5 Gage Spiral Strand and Rebar spaced equally #5 Gage Spiral around pole SECTION A-A SECTION A-A STRAND PATTERN 3 STRAND PATTERN 4 (ROUND - OPTION 1) (ROUND - OPTION 2) Note: Strands and Rebar shown are continuous from Tip End to Butt End. LAST REVISION 01/01/16 REVISIO N 12/2/2015 #5 Gage Spiral d an tr 1: 04: 05 PM #5 Gage Spiral Circular Void Co ve r S of r t te la F en C to " ½ e 1 cl ir C 1" M i n 1 ½ Co " C ve i rc Ce r n l te e r to F of l a t Str a nd 9° 1" M i n DESCRIPTION: INDEX FY 2016-17 DESIGN STANDARDS CONCRETE CCTV POLE NO. 18113 SHEET NO. 3 of 4 Tip Dia. - 2¾" Tip Dia. - 2¾" (± ¼") (± ¼") Tenon Wall Bolt Circle � Bolt Circle (8) ƅ" x 2" Slots Equally Spaced (4) ƅ" Ø Holes Equally Spaced ƅ" Tenon Plate 5 8" 2 ¼" Cap Plate 1 2" 1 from ¡ bar to side surface 2" of handhole (Typ. ea. side) Ƅ" R (Typ.) 1 2" 5 Ø Tip Dia. (± ¼") I.D. (2) Park Stands, O.D. Plate Ƅ" Each Side of Handhole (Pipe Option Shown) Tip Dia. (± ¼") O.D. Plate D SECTION B-B D CAP PLATE DETAIL 4½" x 30" Handhole Ƌ" Ø Hole B B 2" R 3 4" 7 8" 1 (4) ƀ" Ø Nut with Flat Tenon With 3-¼" Ø x 20 Hex Head Washer 2" Provide Cable Guide Ƅ" Galvanized Steel Plate, Ɓ" Cap Plate 1 4" 5 1 4" Ɓ" 7 1' -0" M in. 7 9" 1 4" ƃ" Plate Provide a Tenon Cap and Fix to the Cap Set Screws, Equally Spaced. 1 2 2" Bend at Three Corners 3" 6" O.D. x ¼" Wall x 12" (Min.) Long ½" Ø x 2Ƅ" Min. Insert To Tenon Be Cast Into Pole (See ƙ" Ø Hole Note 2) (4) ƀ" Ø x 18" Galv. Bolts with (4) ƀ" Ø Nut with Flat Washer 15" Embedment, equally spaced 7 8" (See Note 3 for alternate (2) ƌ" Ø Holes connector) #5 Bar x 5'-0" Long Centered 5 8" Tenon TENON COVER Plate In Wall HANDHOLE DETAIL Pole (4) ƀ" Ø x 18" Galv. Bolts with 15" Embedment, Equally Spaced (See Note 3 for Ƅ" Ø Eye Bolt with alternate connector) ½" x 1½" SCH. 40 Pipe 1" Inner Ø 1 2" TOP OF POLE DETAIL WITH LOWERING DEVICE 4 Ƅ" Ø Nut Ƅ" Ø Nut EYE BOLT OPTION PIPE OPTION Notes: 1. Install all handhole and opening covers prior to shipping. 2. Install ½" Ø x 5" long stud with hex nut in insert before shipment. 3. As an alternate, embed (4) ½" ø x 18" stainless steel threaded SECTION D-D - PARK STAND DETAIL rods with a threaded nut. At top of rod, thread a coupling nut to attach plate w/ (4) ½" x 1¾" stainless steel bolts. 4. Handhole frame may be Cast Aluminum 356.2. LAST REVISION 07/01/13 REVISIO N 11: 37: 13 AM 1 2" 4 Pole 11/30/2015 3" 3" TOP OF POLE DETAIL WITHOUT LOWERING DEVICE DESCRIPTION: INDEX FY 2016-17 DESIGN STANDARDS CONCRETE CCTV POLE NO. 18113 SHEET NO. 4 of 4 � Varies NOTES: ƀ" ETP Alloy 110 Copper Air Terminal (Class II) 1. Install DMS Foundation at location shown in Plans. Surface Base Of 8 Square-Inch Minimum Contact Area 2. Extend Catwalk from DMS to outer edge of paved Per NFPA 780-4.16.3 shoulder but not less than four feet in length. Walk-In Dynamic 3. If included, Install guardrail at location show in Message Sign Plans and in accordance with Design Standards (DMS) Index 400. Catwalk Varies Varies Drilled Shaft Guardrail See Note 3 See Note 2 Catwalk See Note 1 Shoulder (Paved) DMS Structure Travel Lane Travel Lane Note: Actual number Travel Lane Travel Lane and direction of travel lanes varies. Travel Lane Ground Line 19'-6" Min. Clearance Shoulder Travel Lane TYPICAL ELEVATION VIEW CANTILEVER SIGN STRUCTURE TYPICAL PLAN VIEW DMS CANTILEVER SIGN STRUCTURE ƀ" ETP Alloy 110 Copper Air � � Terminal (Class II) Surface Base Of 8 Square-Inch Minimum Contact Area Per NFPA 780-4.16.3 Varies Drilled Shaft Varies Guardrail Catwalk Shoulder (Paved) DMS Structure Catwalk Travel Lane Note: Actual number Varies See Note 3 Varies and direction of travel See Note 3 See Note 2 lanes varies. Travel Lane See Note 1 See Note 1 Travel Lane Travel Lane Drilled Shaft Travel Lane Travel Lane Guardrail Ground 11: 37: 14 AM 19'-6" Min. Clearance Line TYPICAL ELEVATION VIEW SPAN SIGN STRUCTURE 11/30/2015 TYPICAL PLAN VIEW DMS SPAN SIGN STRUCTURE Shoulder LAST REVISION 07/01/15 REVISIO N GENERAL LAYOUT DESCRIPTION: INDEX FY 2016-17 DESIGN STANDARDS DYNAMIC MESSAGE SIGN WALK-IN NO. 18300 SHEET NO. 1of 9 ƀ" ETP Alloy 110 Copper Air Terminal (Class II) Surface Base Of 8 Square-Inch Minimum Contact Area Per NFPA 780-4.16.3 2-2" Threaded Couplings 2-2" Threaded Couplings 2 Watertight Flexible Conduits ƀ" ETP Alloy 110 Copper (2" Power And 2" Communications) Air Terminal (Class II) 2 Watertight Flexible Conduits Surface Base Of 8 (2" Power And 2" Communications) Square-Inch Minimum Contact Area Per NFPA 780-4.16.3 ƀ" ETP Alloy 110 Copper Air Terminal (Class II) Surface Base Of 8 Square-Inch Minimum Contact Area Per NFPA 780-4.16.3 Pole Mounted Cabinet Pole Mounted Cabinet 2-2" Threaded Guardrail (if shown in Plans) Couplings 2-2" Threaded 2-2" Rigid Metal Conduits Couplings With Std Sweeps 2-2" Rigid Metal Conduits With Std Sweeps Guardrail Handhole (if shown in Plans) Handhole One 2" PVC Conduit One 2" PVC Conduit For Electrical Service For Electrical Service One 2" PVC Conduit One 2" PVC Conduit For Fiber Optic For Fiber Optic One Communications, One Communications, 2" PVC Conduit Spare 2" PVC Conduit Spare (As Shown On Plans) (As Shown On Plans) Conduit Exit Oriented See Sheet 3 for Conduit In Necessary Direction Details and Sheet 4 Ground Rod Details SPAN DMS See Sheet 3 for Conduit EVER DMS L CANTI Details and Sheet 4 Ground Rod Details NOTES: 1. Conductors for grounding shall be connected to steel framework that has been cleaned to base metal by use of bonding plates having contact area of not less than 8 square inches or by welding or brazing. Drilling and tapping the steel structure to accept a threaded connector is also an acceptable method. 2. If steel framework is to be drilled and tapped to accept threaded connector, the threaded connector shall be galvanized and have at least 5 threads fully engaged and secured with a jam nut to the steel framework. 3. Bends in the conduit shall not be less than the minimum bending radius for the cable contained in the conduit. 4. Catwalk and handrail design and installation shall comply with AISC, 11: 37: 15 AM AASHTO, and OSHA requirements as applicable. 5. All data, fiber optic and power cables for the DMS shall be completely encased within the sign structure or in conduit. 11/30/2015 6. Permanently stamp/mark foundation to conduit locations. 7. Transition conduit in foundation to underground conduit with appropriate LAST REVISION 07/01/15 REVISIO N reducer outside the limits of the foundation. DESCRIPTION: INDEX FY 2016-17 DESIGN STANDARDS DYNAMIC MESSAGE SIGN WALK-IN NO. 18300 SHEET NO. 2 of 9 Two Watertight 2" Flexible Conduits Air Ternimal For Electrical Service And Top Truss Chord Communications 3 4" 2-2" Threaded Couplings Door Hinge 5 For Power And Communications 11 Gauge 2' Max Access Door Handhole Cover DMS NOTES: Removable Top Plate 1. Two J-Hooks To Support 10 3 4" Air Terminal 7 8" DMS Cabinet may be pole or ground mounted Door Latch / Handle depending on project requirements. 2 R= Separately Power And Communications Cable 2. 5 16" See sheet 4 for additional conduits for grounding. The number and placement of Hole, Typ. Conduit Entrance Location Handrail conduits are approximate. Per DMS Manufacturer Field adjust pole-mounted DMS cabinet height Back Truss Chord HANDHOLE COVER 3. Post to achieve best access for maintenance personnel given site conditions as directed by the Engineer. Avoid conflicts with stiffeners, handhole and maintenance of anchor bolts. Grating 1 4" A Dia. Stainless Steel 5" Hex Head Screws, Typ. Tack Welded Cover Clip, Typ. 4" x 3 8" 10" A Catwalk Handhole Frame Made Full Penetration Weld 21 R = 2" Continuous With A Bottom Truss Chord Pole Mounted Full Penetration Cabinet 2-2" Threaded Weld Couplings For 2-2" Rigid Metal Rigid Metal Conduit Conduits With Ground Mounted HANDHOLE FRAME Std Sweeps Cabinet Handhole 4" Top Of Conduits Fiber Optic Splice Box (See Index 17700) Finished Grade (Varies) Spare Spare Conduit Conduit (2" PVC) (2" PVC) 3 8" 1' -0" Fiber Optic Pull Box Or Partial Penetration Weld See Note 3 Varies 2' -6" to 4' -0" 1" Wire Screen - See Spec. 649-6 1 4" Handhole Frame Stainless Steel Hex Head Screws, Typ. Tack Welded Cover Clip Typ. Finished Grade (Varies) 11 Gauge Handhole Cover Power Conduit SECTION A-A (2" PVC) To Power Service Assembly Transition Conduit Outside Foundation (Thru Handhole) Fiber Optic 11: 37: 16 AM Communications Conduit (2" PVC) (As Shown On Plans) Spare Conduit (2" PVC) Fiber Optic Communications Conduit (2" PVC) (As Shown On Plans) 2" PVC Grounding Conduits Power Conduit (2" PVC) LAST REVISION 07/01/14 REVISIO N 11/30/2015 To Power Service Assembly Grounding Conduit (2" PVC) TYPICAL DMS CONDUIT DETAIL CANTILEVER/SPAN SIGN STRUCTURE DESCRIPTION: INDEX FY 2016-17 DESIGN STANDARDS DYNAMIC MESSAGE SIGN WALK-IN NO. 18300 SHEET NO. 3 of 9 20' Radius Each ƀ" ETP Alloy 110 Copper Air "Sphere Of Influence" 2' Min. Terminal (Class II) Surface Base Of 8 Square-Inch Minimum Contact Area Per NFPA 780-4.16.3 4' 40' Min. (Typical) Ground Rod D Ground Rod A Sign Structure Foundation Ground Rod C Dynamic Message Shoulder Travel Lane Travel Lane Sign (DMS) Per Clear Zone Requirements Ground Rod B #2 AWG Tin-Plated Bare Solid Copper Ground Wire. Bond To Air Terminal And Ground Rod With Exothermic Weld Catwalk GROUND ROD PLACEMENT DETAIL (TYPICAL) #2 AWG Tin-Plated Bare Solid Copper Wire Continuous To Pole Mounted Air Terminal #2 AWG Tin-Plated Cabinet Bare Copper Wire To Ground Rods B, C AND D As Required Ground Mounted Cabinet Ground Wire From DMS Cabinet To Ground Rod #2 AWG Tin-Plated Bare Solid Copper Handhole Wire to Pole Mounted or Ground Mounted Cabinet INSET 'A' #2 AWG Tin-Plated Bare Solid Copper Ground Wire To Air Terminal Ground Wire to DMS Cabinet Ground Rod A Primary Ground Finished Grade Ground Rod B Power Conduit (2" PVC) To Power Sercive Assembly 18" M in. As Required Finished Grade Rod Assembly 2" MIN. (See Inset A) 8" MAX. Pull Box Exothermic Weld Spare Conduit (2" PVC) #2 AWG To Ground Rod C As Required Fiber Optic Communication Conduit (2" PVC) (As Shown on Plans) #2 AWG To Ground Rod D As Required 11: 37: 17 AM Fiber Optic Communications Conduit (2" PVC) (As Shown On Plans) Grounding Conduit (2" PVC) 5 8" Spare Conduit (2" PVC) Diameter By 20' Long Copper-Clad Steel Ground Rods 12" Min. Driven Into Undisturbed Earth Power Conduit (2" PVC) To 36" Power Service Assembly Max. Grounding Conduit (2" PVC) 11/30/2015 40' Min. LAST REVISION 07/01/14 REVISIO N TYPICAL GROUND ROD DETAIL DESCRIPTION: INDEX FY 2016-17 DESIGN STANDARDS DYNAMIC MESSAGE SIGN WALK-IN NO. 18300 SHEET NO. 4 of 9 Vertical Hanger Spacing 5'-0" (Max.) 2" Threaded Couplings (2) Quantity And Spacing Of The Members Will Be Dictated By Locations Of Truss Connection Plates, Splices And 5'-0" (Max.) Spacing HANGER LOCATION DETAIL (Cantilever Sign Structure Shown, Span Sign Structure Similar) NOTES 1. Design Specifications: FDOT Structures Manual (current edition) and AASHTO Standard Specifications for Structural Supports for Highway Signs, Luminaires and Traffic Signals. 2. DMS and Hanger Design Wind Speed: 150 miles per hour. Maximum DMS weight for design: 4500 lb. 3. Shop drawings including the DMS connection are required and fabrication shall not begin until these shop drawings are approved. 4. Locate the sign horizontal on the structure as shown in the plans. Vertically center the sign enclosure with the centerline of the truss. 5. Before erection, after both the delivery of the DMS and the steel truss, the contractor shall carefully measure the exact locations for field drilling the ƀ" bolt holes in the vertical hangers and horizontal mounting member attached to the sign enclosure. Field locate holes to allow vertical hanger placement as shown on the plans with no conflicts with gusset or splice plates. 6. All steel items shall be galvanized as follows: All nuts, bolts and washersASTM F2329 All other steel itemsASTM A123 7. All bolt holes shall be equal to the bolt diameter plus Ƈ", prior to galvanizing. 8. All bolts shall have single self-locking nuts, or locking nut system, installed in 11: 37: 17 AM accordance with the manufacturer's recommendations. 9. Cost of the installation of the DMS on truss including the vertical hanger, associated members, and hardware shall be incidental to the cost of the sign structure. 10. Threaded couplings shall be located on sign side of column above the sign LAST REVISION 07/01/14 REVISIO N 11/30/2015 truss. DESCRIPTION: INDEX FY 2016-17 DESIGN STANDARDS DYNAMIC MESSAGE SIGN WALK-IN NO. 18300 SHEET NO. 5 of 9 Aluminum Zee 6061-T6 Structural Aluminum Zee 4x3.13x3.58 Horizontal Member W6x9 Attached To The Internal Framework And Included With The DMS Sign ASTM A709, Gr.36 Steel W6x9 Hanger @ 5' (Max.) Spacing 2Ɓ" c/c DMS Sign Enclosure 6" ± U-Bolts Back Face Of DMS Sign Enclosure B 2-ƀ" Ø U-Bolts Truss Chord B 2-ƀ" Ø ASTM A325 U-Bolts Galv. With Matching Lock Nuts Truss Chord 2Ɓ" 3 Truss Chord 2Ɓ" � Holes For A ƀ" Ø Bolts A Dia. +ƀ " See Truss Data Sheet Z ee Beam s Equally Spaced SECTION A-A � Truss Chord C � Holes For � Holes For � Holes For ƀ" Ø Bolts ƀ" Ø U-Bolts ƀ" Ø U-Bolts C 11: 37: 18 AM 6" ± SECTION B-B SECTION C-C Field Drill Holes And Provide 2-½" Ø ASTM A325 Bolts Galvanized With Matching Lock Nuts LAST REVISION 07/01/14 REVISIO N 11/30/2015 END VIEW DESCRIPTION: INDEX FY 2016-17 DESIGN STANDARDS DYNAMIC MESSAGE SIGN WALK-IN NO. 18300 SHEET NO. 6 of 9 DMS Enclosure Lighting AC Service SPD Power Entry Distribution, Breakers, and SPD UPS Equipment Cabinet SPD GFI Field Tech Computer Electrical Convenience (Temporary Service Breaker Outlets Connection) Convenience Equipment Outlets UPS Power With SPD See Note 6 See Note 4 SPD Sign SPD Controller OR OR SPD Managed Field Ethernet Switch LAN / WAN See Note 1 SPD Voltage, Opto, Temp., Air Flow, Sign Controller Humidity And Interface Filter Sensors Climate & Display Temperature Modules Control See Note 3 Field Tech Computer (Temporary Service Connection) Dial-up Telephone and Modem (optional) LEGEND NOTES: 11: 37: 19 AM Data 1. Provide single ethernet connection from the managed field ethernet switch to either the sign controller interface in cabinet or sign controller in sign 11/30/2015 enclosure. 2. Locate cabinet as shown in plans. 3. Serial data link is for communications directly to the DMS controller. 4. Cabinet must include at least one breaker to control all cabinet power. 5. AC service entrance may be located in cabinet or sign housing. 6. UPS equipment location may vary. Diagram indicates functional Ethernet SIGN AND CABINET WIRING DIAGRAM Power SPD Surge Protection Device LAST REVISION 07/01/14 REVISIO N requirements that uninterrupted power must be available in cabinet and sign housing. DESCRIPTION: INDEX FY 2016-17 DESIGN STANDARDS DYNAMIC MESSAGE SIGN WALK-IN NO. 18300 SHEET NO. 7 of 9 Lifting Eyes Lifting Eye Reserved For Ventilation 3. 5" Sunshields (All Sides But Pole Side) (As Required) 19" EIA Rack With Tapped 10-32 Threaded Holes Light/Shelf Switch Managed Field Ethernet Managed Field Ethernet Switch Switch FO Patch Panel Document Drawer/Shelf Document Drawer/Shelf Document Drawer/Shelf 5. 5" Generator Power Connection FO Patch Panel 1. 75" FO Patch Panel 3. 5" Managed Field Ethernet Sign Controller 46" ( Typ. ) Sign Controller 3. 5" Sign Controller Light/Shelf 3. 5" 1. 75" Light/Shelf Generator Power Connection GFI Protected Convenience Outlet SPDs Data Data 12" Main Circuit Breaker Ethernet For Portable Tools Secondary Circuit Breakers SPD Protected Power Distribution Assembly Outlets For Service Entrance, Breakers, Primary AC Filter, Terminal Communications 19.75" (Typ.) Hardware Blocks, Ground Bussbar Terminal Strips 24" (Typ.) LEFT SIDE VIEW 2-2" Rigid Metal Conduits FRONT VIEW POLE MOUNTED CABINET 22" (Typ.) RIGHT SIDE VIEW NOTES: 1. Cabinet layout is for pole or ground mounted installations. 2. All dimensions and equipment locations are approximate. 3. Conduit entrances are at bottom of cabinet. 4. Minimum number of duplex outlets is three, (2) SPD protected and (1) GFI protected. 11: 37: 20 AM 5. Either an access controller or local access panel shall be provided to provide full access to DMS for control, programming and troubleshooting. 6. Load center shall be sized for connected equipment and convenience outlets with at least one main disconnect and three circuit breakers. 8. Power Distribution Assembly component layout, orientation CABINET LAYOUT 1 and location may vary. LAST REVISION 07/01/14 REVISIO N 11/30/2015 7. Batteries and UPS may be located in sign housing or cabinet. DESCRIPTION: INDEX FY 2016-17 DESIGN STANDARDS DYNAMIC MESSAGE SIGN WALK-IN NO. 18300 SHEET NO. 8 of 9 Lifting Eye 2. 6" 2. 6" Lifting Eyes Light/Shelf Light/Shelf Reserved for Ventilation Light/Shelf Sign Controller Managed Field Sign Controller Ethernet Switch Managed Field Ethernet Switch FO Patch Panel Document Document Drawer/Shelf Drawer/Shelf Power Distribution 52. 85" ( Typ. ) Power Distribution UPS Batteries (varies) See Note 8 on See Note 8 on SPD Protected Sheet 8. Sheet 8. Outlets For Batteries (varies) Ethernet Batteries (varies) 7" +/- UPS 10" +/- 62" ( Typ. ) FO Patch Panel See Note 8 on Sheet 8. Communications Convenience Outlet For Portable Tools 120 VAC SPD Data Data GFI Protected Bus Bars Power SPD SPDs 5.5" 1. 67" Term inal Strips Hardware Load Center 19.75" 32.5" (Typ.) 24" (Typ.) 30" (Typ.) 19" EIA Rack With Tapped 10-32 Threaded Holes FRONT VIEW GROUND MOUNTED CABINET RIGHT SIDE VIEW 11/30/2015 11: 37: 22 AM LEFT SIDE VIEW LAST REVISION 07/01/14 REVISIO N CABINET LAYOUT 2 DESCRIPTION: INDEX FY 2016-17 DESIGN STANDARDS DYNAMIC MESSAGE SIGN WALK-IN NO. 18300 SHEET NO. 9 of 9