Varies Air Terminal (Class II) Surface Base Of 8 Square-Inch

by user

on
Category: Documents
9

views

Report

Comments

Transcript

Varies Air Terminal (Class II) Surface Base Of 8 Square-Inch
�
Varies
NOTES:
ƀ" ETP Alloy 110 Copper
Air Terminal (Class II)
1. Install DMS Foundation at location shown in Plans.
Surface Base Of 8 Square-Inch
Minimum Contact Area
2. Extend Catwalk from DMS to outer edge of paved
Per NFPA 780-4.16.3
shoulder but not less than four feet in length.
Walk-In
Dynamic
3. If included, Install guardrail at location show in
Message Sign
Plans and in accordance with Design Standards
(DMS)
Index 400.
Catwalk
Varies
Varies
Drilled Shaft
Guardrail
See Note 3
See Note 2
Catwalk
See Note 1
Shoulder (Paved)
DMS Structure
Travel Lane
Travel Lane
Note: Actual number
Travel Lane
Travel Lane
and direction of travel
lanes varies.
Travel Lane
Ground
Line
19'-6" Min. Clearance
Shoulder
Travel Lane
TYPICAL ELEVATION VIEW
CANTILEVER SIGN STRUCTURE
TYPICAL PLAN VIEW
DMS CANTILEVER SIGN STRUCTURE
ƀ" ETP Alloy 110 Copper Air
�
�
Terminal (Class II) Surface
Base Of 8 Square-Inch
Minimum Contact Area
Per NFPA 780-4.16.3
Varies
Drilled Shaft
Varies
Guardrail
Catwalk
Shoulder (Paved)
DMS Structure
Catwalk
Travel Lane
Note: Actual number
Varies
See Note 3
Varies
and direction of travel
See Note 3
See Note 2
lanes varies.
Travel Lane
See Note 1
See Note 1
Travel Lane
Travel Lane
Drilled Shaft
Travel Lane
Travel Lane
Guardrail
Ground
11:
35:
50 AM
19'-6" Min. Clearance
Line
TYPICAL ELEVATION VIEW
SPAN SIGN STRUCTURE
11/30/2015
TYPICAL PLAN VIEW
DMS SPAN SIGN STRUCTURE
Shoulder
LAST
REVISION
07/01/15
REVISIO N
GENERAL LAYOUT
DESCRIPTION:
INDEX
FY 2016-17
DESIGN STANDARDS
DYNAMIC MESSAGE SIGN WALK-IN
NO.
18300
SHEET
NO.
1of 9
ƀ" ETP Alloy 110 Copper Air
Terminal (Class II) Surface
Base Of 8 Square-Inch
Minimum Contact Area
Per NFPA 780-4.16.3
2-2" Threaded Couplings
2-2" Threaded Couplings
2 Watertight Flexible Conduits
ƀ" ETP Alloy 110 Copper
(2" Power And 2" Communications)
Air Terminal (Class II)
2 Watertight Flexible Conduits
Surface Base Of 8
(2" Power And 2" Communications)
Square-Inch
Minimum Contact Area
Per NFPA 780-4.16.3
ƀ" ETP Alloy 110 Copper Air
Terminal (Class II) Surface
Base Of 8 Square-Inch
Minimum Contact Area
Per NFPA 780-4.16.3
Pole Mounted Cabinet
Pole Mounted Cabinet
2-2" Threaded
Guardrail
(if shown in Plans)
Couplings
2-2" Threaded
2-2" Rigid Metal Conduits
Couplings
With Std Sweeps
2-2" Rigid Metal Conduits
With Std Sweeps
Guardrail
Handhole
(if shown in Plans)
Handhole
One 2" PVC Conduit
One 2" PVC Conduit
For Electrical Service
For Electrical Service
One 2" PVC Conduit
One 2" PVC Conduit
For Fiber Optic
For Fiber Optic
One Communications,
One Communications,
2" PVC Conduit Spare
2" PVC Conduit Spare
(As Shown On Plans)
(As Shown On Plans)
Conduit Exit Oriented
See Sheet 3 for Conduit
In Necessary Direction
Details and Sheet 4 Ground
Rod Details
SPAN DMS
See Sheet 3 for Conduit
EVER DMS
L
CANTI
Details and Sheet 4 Ground
Rod Details
NOTES:
1. Conductors for grounding shall be connected to steel framework
that has been cleaned to base metal by use of bonding plates
having contact area of not less than 8 square inches or by welding
or brazing. Drilling and tapping the steel structure to accept a
threaded connector is also an acceptable method.
2. If steel framework is to be drilled and tapped to accept threaded
connector, the threaded connector shall be galvanized and have at
least 5 threads fully engaged and secured with a jam nut to the
steel framework.
3. Bends in the conduit shall not be less than the minimum bending
radius for the cable contained in the conduit.
4. Catwalk and handrail design and installation shall comply with AISC,
11:
35:
51 AM
AASHTO, and OSHA requirements as applicable.
5. All data, fiber optic and power cables for the DMS shall be completely
encased within the sign structure or in conduit.
11/30/2015
6. Permanently stamp/mark foundation to conduit locations.
7. Transition conduit in foundation to underground conduit with appropriate
LAST
REVISION
07/01/15
REVISIO N
reducer outside the limits of the foundation.
DESCRIPTION:
INDEX
FY 2016-17
DESIGN STANDARDS
DYNAMIC MESSAGE SIGN WALK-IN
NO.
18300
SHEET
NO.
2 of 9
Two Watertight 2" Flexible Conduits
Air Ternimal
For Electrical Service And
Top Truss Chord
Communications
3
4"
2-2" Threaded Couplings
Door Hinge
5
For Power And Communications
11 Gauge
2' Max
Access Door
Handhole Cover
DMS
NOTES:
Removable Top Plate
1.
Two J-Hooks To Support
10
3
4"
Air Terminal
7 8"
DMS Cabinet may be pole or ground mounted
Door Latch / Handle
depending on project requirements.
2
R=
Separately Power And
Communications Cable
2.
5
16"
See sheet 4 for additional conduits for
grounding. The number and placement of
Hole, Typ.
Conduit Entrance Location
Handrail
conduits are approximate.
Per DMS Manufacturer
Field adjust pole-mounted DMS cabinet height
Back Truss Chord
HANDHOLE COVER
3.
Post
to achieve best access for maintenance personnel
given site conditions as directed by the Engineer.
Avoid conflicts with stiffeners, handhole and
maintenance of anchor bolts.
Grating
1
4"
A
Dia. Stainless Steel
5"
Hex Head Screws, Typ.
Tack Welded
Cover Clip, Typ.
4" x
3
8"
10"
A
Catwalk
Handhole
Frame Made
Full Penetration Weld
21
R
=
2"
Continuous With A
Bottom Truss Chord
Pole
Mounted
Full Penetration
Cabinet
2-2" Threaded
Weld
Couplings For
2-2" Rigid Metal
Rigid Metal Conduit
Conduits With
Ground
Mounted
HANDHOLE FRAME
Std Sweeps
Cabinet
Handhole
4"
Top Of Conduits
Fiber Optic Splice Box
(See Index 17700)
Finished Grade (Varies)
Spare
Spare
Conduit
Conduit
(2" PVC)
(2" PVC)
3
8"
1'
-0"
Fiber Optic Pull Box Or
Partial Penetration Weld
See Note 3
Varies 2'
-6" to 4'
-0"
1"
Wire Screen - See Spec. 649-6
1
4"
Handhole Frame
Stainless Steel
Hex Head Screws, Typ.
Tack Welded
Cover Clip Typ.
Finished Grade (Varies)
11 Gauge Handhole Cover
Power Conduit
SECTION A-A
(2" PVC) To Power
Service Assembly
Transition Conduit Outside Foundation
(Thru Handhole)
Fiber Optic
11:
35:
52 AM
Communications
Conduit (2" PVC)
(As Shown On Plans)
Spare Conduit (2" PVC)
Fiber Optic Communications Conduit
(2" PVC) (As Shown On Plans)
2" PVC Grounding Conduits
Power Conduit (2" PVC)
LAST
REVISION
07/01/14
REVISIO N
11/30/2015
To Power Service Assembly
Grounding Conduit (2" PVC)
TYPICAL DMS CONDUIT DETAIL
CANTILEVER/SPAN SIGN STRUCTURE
DESCRIPTION:
INDEX
FY 2016-17
DESIGN STANDARDS
DYNAMIC MESSAGE SIGN WALK-IN
NO.
18300
SHEET
NO.
3 of 9
20' Radius Each
ƀ" ETP Alloy 110 Copper Air
"Sphere Of Influence"
2' Min.
Terminal (Class II) Surface
Base Of 8 Square-Inch
Minimum Contact Area
Per NFPA 780-4.16.3
4'
40'
Min.
(Typical)
Ground Rod D
Ground Rod A
Sign Structure
Foundation
Ground Rod C
Dynamic Message
Shoulder
Travel Lane
Travel Lane
Sign (DMS)
Per
Clear Zone
Requirements
Ground Rod B
#2 AWG Tin-Plated
Bare Solid Copper
Ground Wire. Bond
To Air Terminal And
Ground Rod With
Exothermic Weld
Catwalk
GROUND ROD PLACEMENT DETAIL
(TYPICAL)
#2 AWG Tin-Plated
Bare Solid Copper
Wire Continuous To
Pole
Mounted
Air Terminal
#2 AWG Tin-Plated
Cabinet
Bare Copper Wire
To Ground Rods B,
C AND D As Required
Ground
Mounted
Cabinet
Ground Wire From DMS
Cabinet To Ground Rod
#2 AWG Tin-Plated
Bare Solid Copper
Handhole
Wire to Pole
Mounted or Ground
Mounted Cabinet
INSET 'A'
#2 AWG Tin-Plated Bare
Solid Copper Ground Wire
To Air Terminal
Ground Wire to DMS Cabinet
Ground Rod A
Primary Ground
Finished Grade
Ground Rod B
Power Conduit
(2" PVC) To Power
Sercive Assembly
18" M in.
As Required
Finished Grade
Rod Assembly
2" MIN.
(See Inset A)
8" MAX.
Pull Box
Exothermic Weld
Spare Conduit (2" PVC)
#2 AWG To Ground Rod C As Required
Fiber Optic Communication Conduit
(2" PVC) (As Shown on Plans)
#2 AWG To Ground Rod D As Required
11:
35:
53 AM
Fiber Optic
Communications
Conduit (2" PVC)
(As Shown On Plans)
Grounding Conduit (2" PVC)
5
8"
Spare Conduit (2" PVC)
Diameter By 20' Long
Copper-Clad Steel Ground Rods
12"
Min.
Driven Into Undisturbed Earth
Power Conduit (2" PVC) To
36"
Power Service Assembly
Max.
Grounding Conduit (2" PVC)
11/30/2015
40' Min.
LAST
REVISION
07/01/14
REVISIO N
TYPICAL GROUND ROD DETAIL
DESCRIPTION:
INDEX
FY 2016-17
DESIGN STANDARDS
DYNAMIC MESSAGE SIGN WALK-IN
NO.
18300
SHEET
NO.
4 of 9
Vertical Hanger Spacing 5'-0" (Max.)
2" Threaded Couplings (2)
Quantity And Spacing Of The Members Will Be Dictated By Locations Of
Truss Connection Plates, Splices And 5'-0" (Max.) Spacing
HANGER LOCATION DETAIL
(Cantilever Sign Structure Shown, Span Sign Structure Similar)
NOTES
1.
Design Specifications: FDOT Structures Manual (current edition) and AASHTO Standard
Specifications for Structural Supports for Highway Signs, Luminaires and Traffic Signals.
2.
DMS and Hanger Design Wind Speed: 150 miles per hour. Maximum DMS weight for design:
4500 lb.
3.
Shop drawings including the DMS connection are required and fabrication shall not begin until
these shop drawings are approved.
4.
Locate the sign horizontal on the structure as shown in the plans. Vertically center the sign
enclosure with the centerline of the truss.
5.
Before erection, after both the delivery of the DMS and the steel truss, the contractor shall
carefully measure the exact locations for field drilling the ƀ" bolt holes in the vertical
hangers and horizontal mounting member attached to the sign enclosure. Field locate holes to
allow vertical hanger placement as shown on the plans with no conflicts with gusset or splice
plates.
6. All steel items shall be galvanized as follows:
All nuts, bolts and washersASTM F2329
All other steel itemsASTM A123
7.
All bolt holes shall be equal to the bolt diameter plus Ƈ", prior to galvanizing.
8. All bolts shall have single self-locking nuts, or locking nut system, installed in
11:
35:
54 AM
accordance with the manufacturer's recommendations.
9. Cost of the installation of the DMS on truss including the vertical hanger,
associated members, and hardware shall be incidental to the cost of the sign
structure.
10. Threaded couplings shall be located on sign side of column above the sign
LAST
REVISION
07/01/14
REVISIO N
11/30/2015
truss.
DESCRIPTION:
INDEX
FY 2016-17
DESIGN STANDARDS
DYNAMIC MESSAGE SIGN WALK-IN
NO.
18300
SHEET
NO.
5 of 9
Aluminum Zee
6061-T6 Structural
Aluminum Zee 4x3.13x3.58
Horizontal Member
W6x9
Attached To The Internal
Framework And Included
With The DMS Sign
ASTM A709, Gr.36 Steel W6x9
Hanger @ 5' (Max.) Spacing
2Ɓ" c/c
DMS Sign Enclosure
6" ±
U-Bolts
Back Face Of
DMS Sign Enclosure
B
2-ƀ" Ø U-Bolts
Truss Chord
B
2-ƀ" Ø ASTM A325 U-Bolts
Galv. With Matching Lock Nuts
Truss Chord
2Ɓ"
3
Truss Chord
2Ɓ"
� Holes For
A
ƀ" Ø Bolts
A
Dia. +ƀ "
See Truss Data Sheet
Z ee Beam s Equally Spaced
SECTION A-A
� Truss Chord
C
� Holes For
� Holes For
� Holes For
ƀ" Ø Bolts
ƀ" Ø U-Bolts
ƀ" Ø U-Bolts
C
11:
35:
55 AM
6" ±
SECTION B-B
SECTION C-C
Field Drill Holes And Provide
2-½" Ø ASTM A325 Bolts
Galvanized With Matching
Lock Nuts
LAST
REVISION
07/01/14
REVISIO N
11/30/2015
END VIEW
DESCRIPTION:
INDEX
FY 2016-17
DESIGN STANDARDS
DYNAMIC MESSAGE SIGN WALK-IN
NO.
18300
SHEET
NO.
6 of 9
DMS Enclosure
Lighting
AC
Service
SPD
Power
Entry
Distribution,
Breakers, and
SPD
UPS
Equipment Cabinet
SPD
GFI
Field Tech Computer
Electrical
Convenience
(Temporary Service
Breaker
Outlets
Connection)
Convenience
Equipment
Outlets
UPS
Power
With SPD
See Note 6
See Note 4
SPD
Sign
SPD
Controller
OR
OR
SPD
Managed Field
Ethernet Switch
LAN / WAN
See Note 1
SPD
Voltage, Opto,
Temp., Air Flow,
Sign Controller
Humidity And
Interface
Filter Sensors
Climate &
Display
Temperature
Modules
Control
See Note 3
Field Tech Computer
(Temporary Service
Connection)
Dial-up Telephone
and Modem (optional)
LEGEND
NOTES:
11:
35:
55 AM
Data
1.
Provide single ethernet connection from the managed field ethernet switch
to either the sign controller interface in cabinet or sign controller in sign
11/30/2015
enclosure.
2.
Locate cabinet as shown in plans.
3.
Serial data link is for communications directly to the DMS controller.
4.
Cabinet must include at least one breaker to control all cabinet power.
5.
AC service entrance may be located in cabinet or sign housing.
6.
UPS equipment location may vary. Diagram indicates functional
Ethernet
SIGN AND CABINET WIRING DIAGRAM
Power
SPD
Surge Protection Device
LAST
REVISION
07/01/14
REVISIO N
requirements that uninterrupted power must be available in cabinet and sign housing.
DESCRIPTION:
INDEX
FY 2016-17
DESIGN STANDARDS
DYNAMIC MESSAGE SIGN WALK-IN
NO.
18300
SHEET
NO.
7 of 9
Lifting Eyes
Lifting Eye
Reserved For Ventilation
3.
5"
Sunshields
(All Sides But Pole Side)
(As Required)
19" EIA Rack With Tapped
10-32 Threaded Holes
Light/Shelf
Switch
Managed Field Ethernet
Managed Field Ethernet
Switch
Switch
FO Patch Panel
Document Drawer/Shelf
Document Drawer/Shelf
Document Drawer/Shelf
5.
5"
Generator Power
Connection
FO Patch Panel
1.
75"
FO Patch Panel
3.
5"
Managed Field Ethernet
Sign Controller
46" (
Typ.
)
Sign Controller
3.
5"
Sign Controller
Light/Shelf
3.
5"
1.
75"
Light/Shelf
Generator Power
Connection
GFI Protected
Convenience Outlet
SPDs
Data
Data
12"
Main Circuit Breaker
Ethernet
For Portable Tools
Secondary
Circuit Breakers
SPD Protected
Power Distribution Assembly
Outlets For
Service Entrance, Breakers,
Primary AC Filter, Terminal
Communications
19.75" (Typ.)
Hardware
Blocks, Ground Bussbar
Terminal Strips
24" (Typ.)
LEFT SIDE VIEW
2-2" Rigid Metal Conduits
FRONT VIEW
POLE MOUNTED CABINET
22" (Typ.)
RIGHT SIDE VIEW
NOTES:
1. Cabinet layout is for pole or ground mounted installations.
2. All dimensions and equipment locations are approximate.
3. Conduit entrances are at bottom of cabinet.
4. Minimum number of duplex outlets is three, (2) SPD
protected and (1) GFI protected.
11:
35:
56 AM
5. Either an access controller or local access panel shall be
provided to provide full access to DMS for control, programming and
troubleshooting.
6. Load center shall be sized for connected equipment and convenience
outlets with at least one main disconnect and three circuit breakers.
8. Power Distribution Assembly component layout, orientation
CABINET LAYOUT 1
and location may vary.
LAST
REVISION
07/01/14
REVISIO N
11/30/2015
7. Batteries and UPS may be located in sign housing or cabinet.
DESCRIPTION:
INDEX
FY 2016-17
DESIGN STANDARDS
DYNAMIC MESSAGE SIGN WALK-IN
NO.
18300
SHEET
NO.
8 of 9
Lifting Eye
2.
6"
2.
6"
Lifting Eyes
Light/Shelf
Light/Shelf
Reserved for Ventilation
Light/Shelf
Sign Controller
Managed Field
Sign Controller
Ethernet Switch
Managed Field
Ethernet Switch
FO Patch Panel
Document
Document
Drawer/Shelf
Drawer/Shelf
Power Distribution
52.
85" (
Typ.
)
Power Distribution
UPS
Batteries (varies)
See Note 8 on
See Note 8 on
SPD Protected
Sheet 8.
Sheet 8.
Outlets For
Batteries (varies)
Ethernet
Batteries (varies)
7" +/-
UPS
10" +/-
62" (
Typ.
)
FO Patch Panel
See Note 8 on
Sheet 8.
Communications
Convenience Outlet
For Portable Tools
120 VAC SPD
Data
Data
GFI Protected
Bus Bars
Power
SPD
SPDs
5.5"
1.
67"
Term inal Strips
Hardware
Load Center
19.75"
32.5" (Typ.)
24" (Typ.)
30" (Typ.)
19" EIA Rack With Tapped
10-32 Threaded Holes
FRONT VIEW
GROUND MOUNTED CABINET
RIGHT SIDE VIEW
11/30/2015
11:
35:
57 AM
LEFT SIDE VIEW
LAST
REVISION
07/01/14
REVISIO N
CABINET LAYOUT 2
DESCRIPTION:
INDEX
FY 2016-17
DESIGN STANDARDS
DYNAMIC MESSAGE SIGN WALK-IN
NO.
18300
SHEET
NO.
9 of 9